Plan Review Details - Permit 04020306
Plan Review Stops For Permit 04020306
Review Stop G GAS REVIEW
Rev No 1 Status P Date 2004-02-19 Cont ID  
Sent By kstevens Date 2004-02-19 Time 17:03 Rev Time 0.50
Received By kstevens Date 2004-02-19 Time 17:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-02-18 Time 10:44 Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 10:44 Sent To P
Notes
2004-02-18 00:00:00TO GAS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-02-09 Time 13:59 Rev Time 0.00
Received By csiegber Date 2004-02-09 Time 13:59 Sent To P
Notes
2004-02-09 00:00:00TO GAS

Review Stop P PLUMBING
Rev No 2 Status N Date 2004-02-19 Cont ID  
Sent By kstevens Date 2004-02-19 Time 17:05 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-02-13 Cont ID  
Sent By csiegber Date 2004-02-18 Time 10:44 Rev Time 1.00
Received By kstevens Date 2004-02-13 Time 17:59 Sent To  
Notes
2004-02-13 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1) SUBMIT MANUF. SPEC. SHEETS FOR THE
 REGULATORS. THEY SHALL BE APPROVED BY
 A RECOGNIZED TESTING AGENCY.
 2) SUBMIT MANUF. SPEC. SHEETS FOR THE
 PE PIPED USED. APPROVAL BY AN APPROVED
 TESTING AGENCY REQUIRED.
 3) REGULATOR REQUIRED AT FUTURE FIRE
 LOGS.
 4) VALVE REQUIRED UPSTREAM OF REGULATORS
 FOR SERVICE.
 5) REGULATORS SHALL BE ACCESSIBLE PER
 410.1. SUBMIT INFO HOW THE REGULATOR
 UPSTREAM OF THE 1-1/4" PE PIPE WILL BE
 ACCESSIBLE. REGULATOR SHALL BE PROTECTED
 AGAINST CORROSION. SUBMIT A DETAIL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]