Plan Review Details - Permit 04020114
Plan Review Stops For Permit 04020114
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-08-19 Cont ID  
Sent By lsmith Date 2004-08-19 Time 16:11 Rev Time 0.50
Received By lsmith Date 2004-08-19 Time 16:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-23 Cont ID  
Sent By lsmith Date 2004-07-23 Time 13:14 Rev Time 0.50
Received By lsmith Date 2004-07-23 Time 13:14 Sent To  
Notes
2004-07-23 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. SEE PLUMBING COMMENTS ON BATHROOM
 REQUIREMENTS TO MEET CODE.
 2. SEE ELECTRICAL COMMENTS.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-08-19 Cont ID  
Sent By dpalmer Date 2004-08-19 Time 11:28 Rev Time 0.50
Received By dpalmer Date 2004-08-19 Time 11:23 Sent To  
Notes
2004-08-19 00:00:00****** NOTES REDLINED *****
  
 SIGN CIRCUIT STILL SHOWN ON WITH SAME
 CIRCUIT AS SHOW WINDOWS. THIS MUST BE
 ON SEPARATE CIRCUITS. 210.62,220.12,
 600.5
  
 PLEASE SEE VALUE FOR COMPLETE SCOPE OF
 WORK IS TO BE ADJUSTED BY BLDG PLAN
 REVIEW.
 ***************************************
 AN ELECTRICAL PERMIT WILL BE REQUIRED
 FOR NEW WORK AND TO CORRECT ELECTRICAL
 WORK UNDER PREVIOUS PERMIT NOT TO CODE.
 ***************************************

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-08-13 Cont ID  
Sent By dpalmer Date 2004-08-13 Time 13:16 Rev Time 0.50
Received By dpalmer Date 2004-08-13 Time 13:13 Sent To  
Notes
2004-08-13 00:00:00*** UNSAT ***
  
 PLEASE SEE THE FOLLOWING COMMENTS.
 PLANS ARE COMING BACK FOR PLUMB COMMENTS
  
 1)NOTE: PLEASE SEE REQUIRED SIGN CIRCUIT
 PER 600.5 IS SHOWN ON SAME CIRCUIT WITH
 SHOW WINDOWS. THESE ARE EACH REQUIRED TO
 BE ON SEPARATE CIRCUITS.
  
 2)NOTE: PLEASE SEE PLANS INDICATE A NEW
 WATER HEATER AND CIRCUIT YET PANEL
 SCHEDULE INDICATES EXISTING WH?
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE SEE NEW RECEPT #29 TO
 ALSO BE GFI. 210.8
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-07-14 Cont ID  
Sent By csiegber Date 2004-08-11 Time 14:52 Rev Time 1.00
Received By dpalmer Date 2004-07-14 Time 09:57 Sent To  
Notes
2004-07-14 00:00:00*************** UNSAT **************
  
 PLEASE SEE THAT PLANS SUBMITTED
 FOR ELECTRICAL REVIEW ARE NOT THE SAME
 AS SUBMITTED UNDER A SEPARATE ELECTRICAL
 PERMIT. # 04050876
 PLEASE SEE THAT DUE TO CHANGE IN OCCU-
 -PANCY ALL ELETCRICAL WORK AND PLANS
 MUST BE BROUGHT UP TO CODE FOR COMM
 MERCHANTILE OCCUPIED BLDG.
 PLANS SUBMITTED UNDER SEPARATE PERMIT
 DID NOT MEET COMPLETE CODE COMPLIANCE
 FOR ITS INTENT AND USE.
  
 1)NOTE: PLEASE SEE 600.5 FOR MISSING
 REQUIRED SIGN CIRCUIT.
  
 2)NOTE: PLEASE SEE 210.62 FOR MIN REQ-
 -UIRED SHOW WINDOW RECEPTS.
  
 3)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS.
  
 4)NOTE: PLEASE SEE SEC'S/ FEEDERS ARE
 NOT LARGE ENOUGH FOR SERVICE SIZE SHOWN.
 PLEASE SEE 310.16.
  
 5 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 6)NOTE: PLEASE SEE THAT RAISED SEAL FOR
 ARCHITECT MUST BE CLEAR AND VISABLE WITH
 ALL INFORMATION ON SAID SEAL.
 FS 481.221
  
 7)NOTE: PLEASE SEE 210.8B3 FOR MIN
 GFI RECEPTS TO MEET CODE COMPLIANCE FOR
 KITCHEN AREA.
  
 8)NOTE: PLEASE SEE 3-PHASE BREAKERS
 SHOWN ON PANEL SCHEDULE YET, SERVICE IS
 SHOWN AS 1-PHASE? ALONG W/ LOAD DETAIL?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-08-19 Cont ID  
Sent By nmccray Date 2004-08-19 Time 15:12 Rev Time 0.00
Received By nmccray Date 2004-08-19 Time 15:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-07-14 Cont ID  
Sent By mcarsill Date 2004-07-14 Time 15:23 Rev Time 0.00
Received By mcarsill Date 2004-07-14 Time 15:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-08-18 Cont ID  
Sent By csiegber Date 2004-08-18 Time 09:15 Rev Time 0.00
Received By csiegber Date 2004-08-18 Time 09:15 Sent To  
Notes
2004-08-18 00:00:00TO COMM BD#9

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-08-11 Cont ID  
Sent By csiegber Date 2004-08-11 Time 12:32 Rev Time 0.00
Received By csiegber Date 2004-08-11 Time 14:52 Sent To  
Notes
2004-08-11 00:00:00TO COMM BD#21

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-07-09 Cont ID  
Sent By kstevens Date 2004-07-10 Time 16:00 Rev Time 0.00
Received By csiegber Date 2004-07-09 Time 16:23 Sent To P
Notes
2004-07-09 00:00:00TO COMM BD#6

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-07-09 Cont ID  
Sent By csiegber Date 2004-07-09 Time 09:39 Rev Time 0.00
Received By csiegber Date 2004-07-09 Time 09:39 Sent To Z
Notes
2004-07-09 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-11 Cont ID  
Sent By csiegber Date 2004-06-11 Time 16:30 Rev Time 0.00
Received By csiegber Date 2004-06-11 Time 16:30 Sent To Z
Notes
2004-06-11 00:00:00TO Z/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-03 Cont ID  
Sent By csiegber Date 2004-06-03 Time 09:01 Rev Time 0.00
Received By csiegber Date 2004-06-03 Time 09:01 Sent To P
Notes
2004-06-03 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-03 Cont ID  
Sent By csiegber Date 2004-02-03 Time 16:28 Rev Time 0.00
Received By csiegber Date 2004-02-03 Time 16:28 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-07-16 Cont ID  
Sent By pkrauss Date 2004-07-16 Time 07:17 Rev Time 0.15
Received By pkrauss Date 2004-07-16 Time 07:10 Sent To  
Notes
2004-07-16 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-08-19 Cont ID  
Sent By kstevens Date 2004-08-19 Time 14:51 Rev Time 0.33
Received By kstevens Date 2004-08-19 Time 14:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-08-11 Cont ID  
Sent By csiegber Date 2004-08-18 Time 09:15 Rev Time 0.75
Received By kstevens Date 2004-08-11 Time 17:22 Sent To  
Notes
2004-08-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 1) DUE TO CHANGE OF OCCUPANCY THE TOILET
 ROOM SHALL HAVE TO COMPLY WITH 11-4.22,
 11-4.16, 11-4.19 AND ALL SUBSECTIONS.
 - PLEASE SUBMIT A DETAIL SHOWING COMPLI-
 ANCE.
 FROM PREVIOUS REVIEW:
 2) PER COMMENT RESPONSE FOR A GREASE IN-
 TERCEPTOR, A SAMPLE POINT SHALL BE RE-
 QUIRED ON SANITARY LINE FROM DELI AREA
 AND UPSTREAM OF THE TOILET ROOM. PLEASE
 SHOW ON PLANS AND ON SANT. RISER DIAGRAM
 SECTION 104.2.1. - THE SANT. IS SHOWN AS
 DRAINING THE OPPOSITE DIRECTION, AND IF
 THIS IS THE CASE, THE TOILET ROOM SHALL
 CONNECT DOWNSTREAM OF THE HAND SINK WITH
 THE SAMPLE POINT UPSTREAM OF THAT CONN-
 ECTION. SOIL SYSTEM SHALL NOT DRAIN THRU
 THE SAMPLE POINT.
 FROM PREVIOUS REVIEW:
 5) INFORMATION MISSING ON THE TITLE
 BLOCK REQUIRED FOR FAC 61G1-16.004(6), A
 SPACE FOR PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT. FS 481.2055.
 FROM PREVIOUS REVIEW:
 6) THE ORIGINAL PERMIT APPLICATION IS
 REQUIRED FOR PERMIT.
 NEW COMMENT:
 1B) MOP SINK SHALL BE VENTED. SEE RED
 LINE CORRECTION OF RISER DIAGRAM FOR
 EXAMPLE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-07-10 Cont ID  
Sent By kstevens Date 2004-07-10 Time 15:29 Rev Time 1.25
Received By kstevens Date 2004-07-10 Time 15:29 Sent To I
Notes
2004-07-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) DUE TO CHANGE OF OCCUPANCY THE TOILET
 ROOM SHALL HAVE TO COMPLY WITH 11-4.22,
 11-4.16, & 11-4.19 AND ALL SUBSECTIONS.
 2) PER COMMENT RESPONSE FOR A GREASE IN-
 TERCEPTOR, A SAMPLE POINT SHALL BE RE-
 QUIRED ON SANITARY LINE FROM DELI AREA
 AND UPSTREAM OF THE TOILET ROOM. PLEASE
 SHOW ON PLANS AND ON SANT. RISER DIAGRAM
 SECTION 104.2.1
 3) PER TABLE A DRINKING FOUNTAIN IS RE-
 QUIRED. ALSO SEE SECTION 410.1
 4) UNABLE TO READ INFORMATION REQUIRED
 ON SEAL OF PLANS. INFORMATION REQUIRED
 PER FAC 61G1-16.001/002 & FS 481.2055.
 A NEW SEAL MAY BE REQUIRED.
 5) INFORMATION MISSING ON THE TITLE
 BLOCK REQUIRED BY FAC 61G1-16.004
 (6) A SPACE FOR PRINTED NAME OF THE PER-
 SON SEALING THE DOCUMENT.
 6) THE ORIGINAL APPLICATION IS REQUIRED
 FOR PERMIT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-02-13 Cont ID  
Sent By csiegber Date 2004-07-09 Time 16:23 Rev Time 1.25
Received By kstevens Date 2004-02-13 Time 14:35 Sent To  
Notes
2004-02-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
  
 1) SANT. RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS. 909.1 ONLY THE FIX-
 TURES WITHIN THE BATHROOM GROUP SHALL
 CONNECT TO THE WET-VENTED HORIZONTAL
 BRANCH DRAIN. ANY ADDITIONAL FIXTURES
 SHALL DISCHARGE DOWNSTREAM OF THE WET
 VENT. THE MOP BASIN AND HAND SINK SHALL
 CONNECT DOWNSTREAM OF THE BATHROOM FIX-
 TURES.
 2) SECTION 3401.2.2.1 IF THE OCCUPANCY
 CLASSIFICATION OR OCCUPANCY SUBCLASSI-
 FICATIONS OF ANY EXISTING BUILDING OR
 STRUCTURE IS CHANGED, THE BUILDING,
 ELECTRICAL, GAS, MECHANICAL AND PLUMBING
 SYSTEMS SHALL BE MADE TO CONFORM TO THE
 INTENT OF THE TECHNICAL CODES AS REQUIR-
 ED BY THE BUILDING OFFICIAL.
 3) INDICATE TYPE OF OCCUPANCY THIS WILL
 BE.
 4) IF OCCUPANCY IS A FOOD SERVICE TYPE,
 AS INDICATED BY FIXTURES BEING ADDED, IT
 WILL BE REQUIRED TO CONTACT RODNEY COMPO
 ENVIRONMENTAL COMPLIANCE WASTE ORD #2938
 -96. (561) 837-4074 - THIS IS TO DETER-
 MINE IF A GREASE INTECEPTOR IS REQUIRED.
 5) THE TYPE OF OCCUPANCY SHALL DETERMINE
 IF THE DBPR HOTEL AND RESTURANT DIVISION
 OR PALM BEACH COUNTY HEALTH UNIT WILL BE
 REQUIRED TO REVIEW THE PLANS.
 6) MORE INFORMATION REQUIRED. SUBMIT A
 FLOOR PLAN FOR THE BUILDING INDICATING
 ALL ROOMS, TOILET ROOMS, DRINKING
 FOUNTAINS ECT. SECTION 104.2.1.2
 7) OTHER COMMENTS MAY BE FORTHCOMMING
 ACCORDING TO RESPONSE TO THESE COMMENTS.
 8) ALL DRAWINGS SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-07-09 Cont ID  
Sent By sgraham Date 2004-07-09 Time 15:44 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2004-07-09 00:00:00THE BLDG MUST BE USED AS A DELI, NOT A
 GROCERY STORE.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-06-10 Cont ID  
Sent By csiegber Date 2004-07-09 Time 09:39 Rev Time 0.00
Received By mmclean Date 2004-06-10 Time 14:24 Sent To P
Notes
2004-06-15 00:00:00PER GRACE JOYCE, PLANNER 659-8031 IT
 LOOKS LIKE A CONV. STORE(ONLY DELI IS
 OK) MM
2004-06-10 00:00:00DENIED, CHANGE USE TO DELI/CONVIENCE
 STORE.