Plan Review Details - Permit 04020057
Plan Review Stops For Permit 04020057
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2004-10-13 Cont ID  
Sent By shill Date 2004-10-13 Time 14:06 Rev Time 0.50
Received By shill Date 2004-10-13 Time 14:06 Sent To E
Notes
2004-10-13 00:00:00REVISION A1 DATED 10/5/4

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-07-16 Cont ID  
Sent By csiegber Date 2004-10-05 Time 15:08 Rev Time 0.50
Received By shill Date 2004-07-16 Time 17:46 Sent To E
Notes
2004-07-16 00:00:00REVISED A1 & A2 ADDRESSING PROVISOS

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-06-30 Cont ID  
Sent By csiegber Date 2004-07-12 Time 13:49 Rev Time 1.50
Received By shill Date 2004-06-30 Time 17:25 Sent To  
Notes
2004-06-30 00:00:00PROVISO - REVISE SHEETS AS NOTED ON
 PLAN
  
 TABLE 600 FOR EAST SIDE
 REVISE AS PER HISTORIC
 ATTACHMENT FOR HANDRAIL, REVISED WALL
 SECTION

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-06-29 Cont ID  
Sent By shill Date 2004-06-29 Time 15:49 Rev Time 1.00
Received By shill Date 2004-06-29 Time 15:48 Sent To  
Notes
2004-06-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)HISTORIC APPROVAL REQUIRED.PLEASE
 HAVE THE PLANS STAMPED BY HISTORIC.
  
 3.)SEE THE PREVIOUS LISTS.HOW WILL
 THE HANDRAIL BE FASTENED TO COMPLY
 WITH FBC1608.2?IN OTHER WORDS, HOW
 WILL YOU ATTACH THIS TO THE WALL?THIS
 CORRECTION HAS BEEN ON EACH LIST; PLEASE
 HAVE THE ENGINEER CALL ME IF HE DOESN'T
 UNDERSTAND THE CORRECTION.
  
 4.)CONNECTOR MTS37 ISN'T IN THE
 CATALOG.YOU GAVE A SPEC SHEET FOR
 MST37.FASTENING STILL CONFLICTS.
 PLEASE SEE ATTACHED.FASTENING FOR SP5
 ALSO CONFLICTS (SEE ATTACHED).CHECK
 ALL CONNECTORS.PLEASE HAVE THE
 ENGINEER CONTACT ME IF HE DOES NOT
 UNDERSTAND THIS CORRECTION AS IT HAS
 BEEN MADE 3 TIMES WITHOUT BEING PROPERLY
 CORRECTED.
  
 5.)ALL OF THE OTHER PLANS SUBMITTED
 REFERRED TO FBC2001.NOW THE PLANS
 HAVE BEEN CHANGED TO FBC2002.THE
 GOVERNING CODE IS STILL FBC2001, PLEASE
 CORRECT.
  
 6.)A 4X FEE HAS BEEN CHARGED PER
 FS553.80(2)(B).

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-06-03 Cont ID  
Sent By shill Date 2004-06-03 Time 16:53 Rev Time 2.00
Received By shill Date 2004-06-03 Time 16:53 Sent To  
Notes
2004-06-03 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)HISTORIC APPROVAL REQUIRED.PLEASE
 HAVE THE PLANS STAMPED BY HISTORIC.
  
 3.)THE ENGINEER'S LICENSE NUMBER IS
 TO BE PRINTED ON EACH SHEET, FAC61G15-23
 002.
  
 4.)SEE PREVIOUS LISTS.HOW WILL THE
 HANDRAIL BE FASTENED TO COMPLY WITH
 FBC1608.2?YOU CANNOT JUST LIST A
 CODE SECTION; YOU MUST GIVE A
 SPECIFICATION AS TO HOW IT WILL BE
 BUILT WHICH IS TO BE IN COMPLIANCE WITH
 THIS CODE SECTION.DO NOT LIST CODE,
 PROVIDE SPECS.
  
 5.)SEE PREVIOUS LISTS.FLORIDA
 STATEWIDE, LOCAL OR SITE SPECIFIC
 PRODUCT APPROVALS REQUIRED.
 WWW.FLORIDABUILDING.ORG (PRODUCT
 APPROVAL, SEARCH PRODUCT APPROVAL).
 I HAVE PRINTED ONE AS A SAMPLE.ANY
 PRODUCT APPROVALS NOT SUBMITTED
 PROPERLY BEFORE PERMIT ISSUANCE WILL
 REQUIRE SEPARATE PERMITS WITH SEPARATE
 FEES.SUBMIT TWO COPIES OF ALL PRODUCT
 APPROVALS.
  
 6.)SEE PREVIOUS LISTS, PROVIDE
 DESIGN UPLIFT INFORMATION.
  
 7.)PROVIDE MANUFACTURER SPECS FOR
 MTS30.THE FASTENING STILL CONFLICTS
 WITH MY CATALOG, PERHAPS YOU HAVE
 OTHER INFORMATION.CONFIRM THAT THE
 SPECS ARE CONSISTENT WITH THE PLAN
 BEFORE RESUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-04-21 Cont ID  
Sent By pkrauss Date 2004-05-25 Time 11:38 Rev Time 1.50
Received By shill Date 2004-04-20 Time 12:43 Sent To Z
Notes
2004-04-20 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST, COMMENTS
 2,6,7, SECOND PART OF 8, 9,10, 12, AND
 15.A COPY HAS BEEN PROVIDED.
  
 2.)SEE PREVIOUS LIST, #10.THE
 FLORIDA STATEWIDE, LOCAL OR SITE
 SPECIFIC PRODUCT APPROVAL IS REQUIRED
 FOR THE WINDOWS, DOORS AND SHUTTERS
 IN ADDITION TO THE TEST REPORTS
 PROVIDED.PROVIDE A LIST OF ALL
 CONNECTORS WITH THE FLORIDA PRODUCT
 APPROVAL.FAC9B-72,
 WWW.FLORIDABUILDING.ORG
  
 3.)PROVIDE THE DISTANCE BETWEEN THE
 TWO BUILDINGS.SHOW COMPLIANCE WITH
 FBC TABLE 600.PROVIDE AN ELEVATION OF
 THE EAST SIDE OF THE PORTION OF THE
 BUILDING (MAIN RESIDENCE) THAT FACES
 THE 2 STORY ACCESSORY BUILDING.
  
 4.)COMMENT #15 WAS APPARENTLY
 ADDRESSED BY SHOWING PRESSURES OF
 +50/-53 ON THE PLAN (A1), BUT THE NOTES
 STILL INDICATE 57 (TWO STORY).
  
 5.)NAILING FOR SIMPSON MTS30
 CONFLICTS WITH THE CATALOG; REVISE.
 CHECK ALL CONNECTORS.
  
 6.)SEPARATE PERMITS REQUIRED.
  
 7.)SEE ATTACHED FS553.80(2)(B).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-11 Cont ID  
Sent By dpalmer Date 2004-04-15 Time 18:32 Rev Time 4.00
Received By shill Date 2004-03-11 Time 13:01 Sent To  
Notes
2004-03-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)HISTORIC APPROVAL REQUIRED.
  
 3.)IMPROVEMENTS OVER 50% MUST COMPLY
 WITH FBC3401.7.2.6; NOTE ON PLAN.
  
 4.)PROVIDE A SURVEY FOR THIS PROPERTY.
  
 5.)THE ENGINEER'S LICENS NUMBER IS TO
 BE PRINTED ON EACH SHEET, FAC61G15-23.00
 2.
  
 6.)THE STAIR DETAIL 3-A1 DOES NOT
 COMPLY WITH FBC1007.3.1(1).DO THESE
 DIMENSIONS INDICATE EXISTING
 CONDITIONS?SEE FBC1001.3.
  
 7.)A1, SCOPE OF BUILDING WORK
 INDICATES AN UPSTAIRS KITCHEN.IS THIS
 CORRECT?NONE IS SHOWN ON THE FLOOR
 PLAN.
  
 8.)3-A1, HANDRAIL IS TO COMPLY WITH
 FBC1007.5 (34-38" ABOVE TREAD).ALSO
 MUST COMPLY WITH FBC1608.2.HOW WILL
 THE RAIL BE FASTENED TO COMPLY WITH
 FBC1608.2?
  
 9.)3-A1 SHOWS A STRAP SECURED TO
 A SLAB, CONFLICTS WITH THE OTHER DETAILS
 WHICH SHOW WOOD.
  
 10.) FLORIDA STATEWIDE, LOCAL OR SITE
 SPECIFIC PRODUCT APPROVALS REQUIRED.
 WWW.FLORIDABUILDING.ORG.PROVIDE A LIST
 OF ALL CONNECTORS WITH FLORIDA PRODUCT
 APPROVAL NUMBERS.
  
 11.)CORNER FRAMING DETAIL, APPLICATION
 CONFLICTS WITH USP CATALOG FOR RS100.
 ADDRESS.
  
 12.)PROVIDE DESIGN UPLIFT INFORMATION.
  
 13.)SPECIFY ALL CONNECTORS,
 CONTINUOUS FROM THE FOUNDATION THROUGH
 THE ROOF, ON ALL DETAILS.
  
 15.)THE DOOR PRODUCT APPROVAL HAS A
 LIMITATION OF +50/-53.IT APPEARS THAT
 THE DESIGN PRESSURE FOR THIS OPENING
 IS -57.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2004-10-14 Cont ID  
Sent By dpalmer Date 2004-10-14 Time 17:04 Rev Time 0.33
Received By dpalmer Date 2004-10-14 Time 17:04 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-07-20 Cont ID  
Sent By shill Date 2004-10-13 Time 14:06 Rev Time 0.25
Received By dpalmer Date 2004-07-20 Time 08:09 Sent To  
Notes
2004-07-20 00:00:00RESTAMP ONLY

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-06-16 Cont ID  
Sent By shill Date 2004-07-16 Time 17:54 Rev Time 0.50
Received By dpalmer Date 2004-06-16 Time 16:45 Sent To  
Notes
2004-06-16 00:00:00***REDLINED ***
  
 PLANS STILL SHOWS AN EQUIPMENT GROUNDING
 FROM METER TO MAIN.
 THIS SHALL NOT BE INSTALLED. 250.24/250.
 6

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-05-14 Cont ID  
Sent By mjacobs Date 2004-06-14 Time 15:10 Rev Time 0.33
Received By dpalmer Date 2004-05-14 Time 06:39 Sent To P
Notes
2004-05-14 00:00:00*********** UNSAT ***********
  
 1)NOTE: PLEASE SEE PLANS STILL HAVE
 PLACES WHERE 1999 NEC IS REFERENCED?
  
 2)NOTE: PLEASE SEE FAC 61G15-23.002
 PLEASE INCLUDE ALL INFORMATION ON TITLE
 BLOCK FOR ENGINEER. THIS IS REQ'D TO BE
 PRINTED ON PLANS. PLEASE ALSO SEE FS
 471.025, A SIGNATURE IS REQ'D, PER
 FS AND FBPE'S INITIALS ARE NOT PERMITTED
 PLEASE NOTE: THIS IS TO PROTECT THE
 ENGINEER/ FIRMS.
 SIGNATURE INFORMATION HAS BEEN GONE OVER
 W/ MR BUCK AND HE IS NOW AWARE OF WHAT
 NEEDS TO BE DONE FOR THIS.
  
 3)NOTE: PLEASE SEE RISER, AN EQUIPMENT
 GROUND NOTE SHOWS AN EQUIP GRND FROM
 TO METER, AND FROM METER TO MAIN ALSO.
 PLEASE SEE 250.6,250.24, AN EQUIP GRND
 IS ONLY INSTALLED "AFTER THE FIRST MEANS
 OF DISC". PLEASE ADJUST RISER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-04-15 Cont ID  
Sent By csiegber Date 2004-05-11 Time 15:37 Rev Time 0.50
Received By dpalmer Date 2004-04-15 Time 18:11 Sent To B
Notes
2004-04-15 00:00:00********** UNSAT ***************
  
 1)NOTE: PLEASE SEE PLANS REFERENCE
 DIFFERENT NEC CODES. 2002, 2001 AND 1999
 WE ARE UNDER THE 2002 NEC AND ALL REF'S
 SHOULD BE TO THE 2002.
  
 2)NOTE: PLEASE SEE NOW AN EQUIPMENT
 GROUNDING CONDUCTOR IS NOW BEING SHOWN
 FROM METER TO THE FIRST MEANS OF DISC
 ALSO. PLEASE NOTE, THE EQUIPMENT GRND
 IS ONLY INSTALLED AFTER THE FIRST MEANS
 OF DISC. PER 250.24
  
 3)NOTE: PLEASE SEE 220.18 FOR A MIN OF
 5KW FOR DRYER TO BE FIGURED.
 PLEASE SEE PANEL SCHEDULE SHOWS 4.5KW,
 PLEASE ALSO SEE LOAD CALCULATIONS DO NOT
 INCLUDE DRYER.
 PLEASE SEE MICROWAVE THAT IS SHOWN ON
 LOAD CALCS IS NOT ON PANEL SCHEDULE.
  
 PLEASE VERIFY THE # OF ARC FAULT CIRCUIT
 -S SHOWN ON PANEL SCHEDULE.
  
 4)NOTE: PLEASE SEE 210.52E FOR MISSING
 FRONT AND REAR RECEPTS OF DWELLING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-02-13 Cont ID  
Sent By jleech Date 2004-04-12 Time 16:33 Rev Time 1.00
Received By dpalmer Date 2004-02-13 Time 05:56 Sent To P
Notes
2004-02-13 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 ALL INFORMATION REQ'D ON A TITLE BLOCK.
 PLANS DO NOT CONTAIN TITLE BLOCK.
 PLEASE ALSO SEE FS 471
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5 SHOWN FOR PANEL,NOT MAIN
  
 3)NOTE: PLEASE SEE A-4, REFERENCES 1999
 NEC. WE ARE UNDER THE 2002.
  
 4)NOTE: MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM MAIN TO PANEL. 250.110,
 250.24, SIZE PER 250.122
  
 5)NOTE: PLEASE SEE NOTE ON RISER MENTION
 -S WEATHERHEAD TO BE 3' ABOVE ROOF.
 PLEASE SEE THAT THIS MAY CHANGE DUE TO
 ACTUAL LOCATION AND CIRCUMSTANCES OF
 ROOF. FYI.
  
 6 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 7 )NOTE: PLEASE SEE MISSING REQ'D EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210.70 AND LS-101 5-8
 MISSING AR FRONT DOOR.
  
 8)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 20' FROM COOKING APPL.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 "PLEASE MOVE FIRST FLR CLOSER TO STAIRS"
  
 9)NOTE: PLEASE SHOW ANY LV/ TV/ PHONE
 ON PLANS AT THIS TIME, OR PLANS WILL BE
 REQ'D TO BE SUBMITTED AT TIME OF APPLI-
 -CATION. THIS IS ONLY A NOTE AND IS NOT
 REQ'D.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 15:08 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 15:08 Sent To B
Notes
2004-10-05 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-07-12 Cont ID  
Sent By csiegber Date 2004-07-12 Time 13:49 Rev Time 0.00
Received By csiegber Date 2004-07-12 Time 13:49 Sent To B
Notes
2004-07-12 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-06-14 Cont ID  
Sent By mjacobs Date 2004-06-14 Time 15:10 Rev Time 0.00
Received By mjacobs Date 2004-06-14 Time 15:09 Sent To E
Notes
2004-06-14 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-05-11 Cont ID  
Sent By csiegber Date 2004-05-11 Time 15:37 Rev Time 0.00
Received By csiegber Date 2004-05-11 Time 15:37 Sent To E
Notes
2004-05-11 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-04-01 Time 15:10 Rev Time 0.00
Received By csiegber Date 2004-04-01 Time 15:10 Sent To P
Notes
2004-04-01 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-03 Cont ID  
Sent By alange Date 2004-03-03 Time 14:36 Rev Time 0.00
Received By alange Date 2004-03-03 Time 14:36 Sent To B
Notes
2004-03-03 00:00:00TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-03 Cont ID  
Sent By csiegber Date 2004-02-03 Time 10:42 Rev Time 0.00
Received By csiegber Date 2004-02-02 Time 10:42 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2004-05-25 Cont ID  
Sent By pkrauss Date 2004-05-25 Time 11:36 Rev Time 0.30
Received By pkrauss Date 2004-05-25 Time 11:11 Sent To B
Notes
2004-05-25 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.ENERGY & MANUAL J CALCULATIONS
 INDICATE PTAC UNITS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-02-19 Cont ID  
Sent By kstevens Date 2004-05-25 Time 10:34 Rev Time 0.33
Received By pkrauss Date 2004-02-19 Time 12:57 Sent To B
Notes
2004-02-19 00:00:00NO MECHANICAL PLANS SUBMITTED.ENERGY
 CALCULATIONS INDICATE 3 PTAC (UNDUCTED)
 UNITS.

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-06-28 Cont ID  
Sent By dpalmer Date 2004-10-14 Time 17:04 Rev Time 1.00
Received By kstevens Date 2004-06-28 Time 14:15 Sent To  
Notes
2004-07-01 00:00:00PASSED/PROVISO
  
 TRAP REQUIRED FOR TUB ON SANT. RISER
 DIAGRAM.

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-05-25 Cont ID  
Sent By kstevens Date 2004-05-25 Time 10:16 Rev Time 1.00
Received By kstevens Date 2004-05-25 Time 10:16 Sent To M
Notes
2004-05-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT A4 SANITARY RISER DIAGRAM IS UN-
 CLEAR AND DOES NOT MEET CODE. SECTION
 104.2.1. - REMOVE ALL INFORMATION FROM
 THE SANITARY RISER DIAGRAM THAT HAS NO
 RELEVANCE TO THE RISER. THE FLOOR JOISTS
 MAKE THE RISER DIAGRAM IMPOSSIBLE TO
 REVIEW.
 - THE WASH MACHINE SHALL CONNECT TO THE
 STACK DOWNSTREAM OF THE KITCHEN SINK.
 - THE WASH MACHINE REQUIRES A STANDPIPE
 - THE TUB REQUIRES A TRAP
 - SEE RED LINE CORRECTIONS FOR DIAGRAM
 SECTIONS: 1002.1 - 802.4
  
 2) THE PERSONAL SIGNATURE OF THE ARCHIT-
 ECT SHALL APPEAR ON ALL ARCHITECTURAL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD.
 INITIALS ARE NOT ACCEPTABLE. FAC 61G1-16
 .003 & FS 481.2055.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-04-12 Cont ID  
Sent By dpalmer Date 2004-05-14 Time 06:39 Rev Time 1.00
Received By jleech Date 2004-04-12 Time 16:32 Sent To E
Notes
2004-04-12 00:00:00DENIED;
 PLUMBING RISER DIAGRAM NOT TO CODE. ASK
 YOUR PLUMBING CONTRACTOR TO DRAW ONE FOR
 YOU.
 NOTE 1 EXISTING SANITARY AND DRAIN FIELD
 TO BE REMOVED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-02-13 Cont ID  
Sent By csiegber Date 2004-04-01 Time 15:11 Rev Time 1.00
Received By jleech Date 2004-02-13 Time 12:59 Sent To M
Notes
2004-02-13 00:00:00DENIED;
 1.AUTOMATIC CLOTHES WASHER REQUIRED. SEE
 FBC PLUMBING TABLE 403.2 ONE AND TWO
 FAMILY DWELLINGS.
 2.SANITARY RISER DIAGRAM NOT TO CODE.
 KITCHEN SINK IS NOT VENTED, BATHROOM
 CANNOT BE INSTALLED AS DRAWN.
 3.IS W/H 30 OR 50 GAL.?
 4.H2O RISER DIAGRAM, SHOCK ARRESTORS NOT
 AIR CHAMBERSARE REQUIRED PER SEC 604.9
 5.PLUMBING NOTE #1. BUILDING SEWER IS
 REQUIRED TO BE INSTALLED TO THE PUBLIC
 SEWER SYSTEM. SEPIC TANK NEEDS TO BE
 REMOVED.
 6.NOTE # 10 REMOVE NOTE HOT WATER SHOULD
 120 DEG. ONLY COMMERCIAL DISHWASHER
 REQUIRE 180 DEG. WATER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2004-05-03 Cont ID  
Sent By shill Date 2004-04-21 Time 14:32 Rev Time 0.00
Received By mmclean Date 2004-05-03 Time 11:35 Sent To B
Notes
***NONE***