Plan Review Details - Permit 04010648
Plan Review Stops For Permit 04010648
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-06-17 Cont ID  
Sent By alange Date 2004-06-17 Time 13:55 Rev Time 0.25
Received By alange Date 2004-06-17 Time 13:54 Sent To  
Notes
2004-06-17 00:00:00REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-04-09 Cont ID  
Sent By csiegber Date 2004-06-11 Time 10:50 Rev Time 0.33
Received By alange Date 2004-04-09 Time 10:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-04-08 Cont ID  
Sent By alange Date 2004-04-08 Time 15:00 Rev Time 0.50
Received By alange Date 2004-04-08 Time 15:00 Sent To  
Notes
2004-04-08 00:00:00DENIED
  
 PLANS NOT STAMPED WITH IMPACT FEES.
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-04-07 Time 11:48 Rev Time 1.25
Received By alange Date 2004-04-01 Time 08:50 Sent To  
Notes
2004-04-01 00:00:00DENIED
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-29 Cont ID  
Sent By alange Date 2004-03-30 Time 14:44 Rev Time 2.50
Received By alange Date 2004-03-29 Time 14:21 Sent To  
Notes
2004-03-29 00:00:00DENIED
 1. BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.BUILDING VALUE OF $250,000 IS TOO
 LOW.AN ADJUSTED VALUE OF $288,687 HAS
 BEEN APPLIED.ADJUSTED VALUE IS BASED
 UPON SBCCI BUILDING VALUATION DATA.
 ADDITIONAL PERMIT FEES OF $390.74 ARE
 DUE BEFORE PERMIT CAN BE ISSUED.
  
 3.MANY PRODUCT APPROVALS ARE EITHER
 MISSING OR INCOMPLETE.SUBMIT 2 COPIES
 OF ALL REQUIRED PRODUCT APPROVALS
 ACCORDING TO RULE 9B-72.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.SUBMIT A WINDOW AND DOOR SCHEDULE
 INCLUDING SIZE AND TYPE OF PRODUCT AND
 LOCATION WERE THEY ARE LOCATION ON THE
 BUILDING RESPECTIVELY.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-03-16 Cont ID  
Sent By btrobaug Date 2004-03-16 Time 08:35 Rev Time 0.50
Received By btrobaug Date 2004-03-16 Time 07:43 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-11 Cont ID  
Sent By csiegber Date 2004-06-11 Time 10:50 Rev Time 0.00
Received By csiegber Date 2004-06-11 Time 10:50 Sent To B
Notes
2004-06-11 00:00:00TO AL DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-07 Cont ID  
Sent By csiegber Date 2004-04-07 Time 11:48 Rev Time 0.00
Received By csiegber Date 2004-04-07 Time 11:48 Sent To B
Notes
2004-04-07 00:00:00TO AL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-30 Cont ID  
Sent By alange Date 2004-03-30 Time 14:44 Rev Time 0.00
Received By alange Date 2004-03-30 Time 14:44 Sent To B
Notes
2004-03-30 00:00:00TO AL DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-29 Cont ID  
Sent By mmclean Date 2004-03-04 Time 14:55 Rev Time 0.00
Received By csiegber Date 2004-01-14 Time 16:20 Sent To  
Notes
2004-03-04 00:00:001/14/04 TO Z
 TO Z/RESUB
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-03-22 Cont ID  
Sent By jleech Date 2004-03-20 Time 08:54 Rev Time 0.33
Received By pkrauss Date 2004-03-22 Time 11:56 Sent To B
Notes
2004-03-22 00:00:00PROVISO:
 1.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 2.RETURN AIR REQUIRED FROM THE DEN
 AREA PER 2001 FBC(M) 601.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-03-20 Cont ID  
Sent By jleech Date 2004-03-20 Time 08:54 Rev Time 0.25
Received By jleech Date 2004-03-20 Time 08:54 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-03-04 Cont ID  
Sent By mmclean Date 2004-03-04 Time 14:55 Rev Time 0.00
Received By mmclean Date 2004-03-04 Time 14:55 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-01-20 Cont ID  
Sent By csiegber Date 2004-01-14 Time 16:21 Rev Time 0.75
Received By gjoyce Date 2004-01-20 Time 10:23 Sent To  
Notes
2004-01-20 00:00:00SIDE LOAD GARAGE S/B IS 15 FEET, PLAN
 SHOWS 10'