Plan Review Details - Permit 04010561
Plan Review Stops For Permit 04010561
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-05 Cont ID  
Sent By hpiskura Date 2004-02-11 Time 16:41 Rev Time 0.00
Received By hpiskura Date 2004-02-11 Time 16:40 Sent To ENG
Notes
2004-02-11 00:00:00THE CITY OF WEST PALM BEACH IS LOCATED
 IN A 140 MPH ZONE AND THE "MOBILE MINI"
 MDS 003138 IS DESIGNED FOR 130 MPH WIND
 ZONE AND WILL NOT BE PERMITTED.
  
 THE SITE PLAN IS NOT SIGNED AND SEALED
 AND LACKS DIMEMSIONS.PLEASE REVISE AS
 NECESSARY AND INCLUDE HC ACCESS FROM
 THE PUPLIC RIGHT OF WAY.FBC 104.2.4.
  
 PROVIDE SPECIFIC CONSTRUCTION DETAILS
 FOR THE HC RAMP,INCLUDING THE BUILDING
 INSTALLATION FF HEIGHT.FBC 104.2
  
 PROVIDE A NOTICE OF ACCEPTANCE REPORT
 AND OR TESTING FOR THE ABS PADS TO BE
 USED FOR THE FOUNDATION.FBC 103.7

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2004-01-26 Cont ID  
Sent By dpalmer Date 2004-01-26 Time 13:23 Rev Time 0.33
Received By dpalmer Date 2004-01-26 Time 12:58 Sent To  
Notes
2004-01-26 00:00:00********* NO REVIEW *********
  
 SUBMIT PLANS/RISER DIAGRAM W/ PERMIT
 APPLICATION FOR TRAILER HOOK UP.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-02-12 Cont ID  
Sent By hpiskura Date 2004-03-05 Time 15:15 Rev Time 0.50
Received By mamini Date 2004-02-12 Time 09:12 Sent To  
Notes
2004-02-12 00:00:00FAILED:
 1. PLEASE SUBMIT CIVIL/ SITE PLAN
 SHOWING CONNECTION TO THE CITY SERVICES,
 WATER, SEWER, DRAINAGE,METER AND
 BACKFLOWS.
 2. PLEASE NOTE THAT CONNECTIONS MUST
 ALSO BE APPROVED BY THE PUBLIC UTILITIES
 AND ENGINEERING PRIOR TO SUBMITTING TO
 THE BUILDING DEPARTMENT, 659-8040 MANNY
 GONZALEZ.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-01-29 Cont ID  
Sent By mcarsill Date 2004-01-29 Time 07:16 Rev Time 0.00
Received By mcarsill Date 2004-01-29 Time 07:16 Sent To  
Notes
2004-01-29 00:00:001) PLEASE INDICATE IN WRITING HOW
 LONG THE PROPOSED TRAILER WILL BE
 LOCATED ON THE SITE.
  
 2) BUILDING ADDRESS WILL BE REQUIRED.
  
 3) PORTIONS OF OKEECHOBEE BOULEVARD
 AND ALABAMA AVENUE ARE LOCATED IN
 THE CITY FIRE LIMITS. TYPE VI
 CONSTRUCTION IS NOT ALLOWED IN THE
 CITY FIRE LIMITS. PLEASE SEE APPENDIX
 F OF THE LOCAL AMENDMENTS TO THE
 FLORIDA BUILDING CODE.
  
 4) PLEASE SHOW EXIT SIGNS, EMERGENCY
 LIGHTS AND EXIT SIGNS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-12 Cont ID  
Sent By mamini Date 2004-05-06 Time 16:39 Rev Time 0.00
Received By csiegber Date 2004-01-13 Time 09:37 Sent To  
Notes
2004-01-22 00:00:00TO COMM BD#22
2004-01-13 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-29 Cont ID  
Sent By pkrauss Date 2004-01-29 Time 17:28 Rev Time 0.20
Received By pkrauss Date 2004-01-29 Time 17:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-24 Cont ID  
Sent By kstevens Date 2004-01-24 Time 08:01 Rev Time 0.25
Received By kstevens Date 2004-01-24 Time 08:01 Sent To  
Notes
2004-01-24 00:00:00DENIED
  
  
 SUBMIT A SITE PLAN THAT SHOWS LOCATION
 OF WATER METER, AN RPZ BACKFLOW, AND THE
 LOCATION OF THE SEWER CONNECTION. IF NO
 SEWER CONNECTION, PERMIT FROM THE HEALTH
 DEPT. IS REQUIRED FOR HOLDING TANKS
 PRIOR TO RESUBMITTING TO CITY FOR REVIEW
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2004-01-20 Cont ID  
Sent By gjoyce Date 2004-01-20 Time 10:29 Rev Time 1.00
Received By gjoyce Date 2004-01-20 Time 10:29 Sent To  
Notes
2004-01-20 00:00:00NEEDS MINOR PD AMENDMNET
 (2) SITE PLANS REQUIRED MEETING ALL CODE
 REQUIREMENTS PER ERIC S