Plan Review Details - Permit 04010349
Plan Review Stops For Permit 04010349
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-01-27 Cont ID  
Sent By pkrauss Date 2004-01-21 Time 12:36 Rev Time 0.75
Received By alange Date 2004-01-27 Time 15:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2004-01-12 Cont ID  
Sent By csiegber Date 2004-01-09 Time 08:51 Rev Time 0.50
Received By btrobaug Date 2004-01-12 Time 16:09 Sent To P
Notes
2004-01-12 00:00:00 
 PLEASE PROVIDE DRAWINGS PER 215.5 AND
 CALCS PER 220.3.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-09 Cont ID  
Sent By csiegber Date 2004-01-09 Time 08:51 Rev Time 0.00
Received By csiegber Date 2004-01-09 Time 08:51 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-21 Cont ID  
Sent By kstevens Date 2004-01-17 Time 09:58 Rev Time 0.33
Received By pkrauss Date 2004-01-21 Time 12:31 Sent To B
Notes
2004-01-21 00:00:00PROVISO:
 1.RETURN AIR REQUIRED FROM BEDROOM
 AREAS.SEE THE ATTACHED SCHEDULE FOR
 PROPER SIZING FOR RETURNS OR TRANSFER
 GRILLES. 2001 FBC(M) 601.4.
  
 2.4" MINIMUM CLEARANCE REQUIRED AROUND
 AHU.2001 FBC(M) 603.1.3.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-01-17 Cont ID  
Sent By btrobaug Date 2004-01-12 Time 16:09 Rev Time 0.25
Received By kstevens Date 2004-01-17 Time 09:58 Sent To M
Notes
2004-01-17 00:00:00NO PLUMBING PLANS SUBMITTED - PLUMBING
 PERMIT REQUIRED