Plan Review Details - Permit 04010266
Plan Review Stops For Permit 04010266
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-03-04 Cont ID  
Sent By rmcdouga Date 2004-03-04 Time 13:55 Rev Time 1.50
Received By rmcdouga Date 2004-03-04 Time 13:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-03-01 Cont ID  
Sent By btrobaug Date 2004-03-03 Time 11:45 Rev Time 2.00
Received By rmcdouga Date 2004-03-01 Time 16:09 Sent To  
Notes
2004-03-01 00:00:00DENIED
  
 1) THE PLAN REVIEW NUMBER FOR THE
 COUNTY IMPACT FEES STAMPED ON SHEET 5 OF
 THE PLANS DOES NOT MATCH THE PLAN
 REVIEW NUMBER ON THE PAID RECEIPT.
  
 2) THE CHANGE TO THE NUMBER OF NAILS FOR
 THE JL 210 CONNECTOR ON SHEET 5B IS
 REQUIRED TO BE INITIALED AND DATED BY
 THE DESIGNER OF RECORD WHEN IT IS RED
 LINED BY HAND.
  
 3) THE STORM PANEL SUBMITTAL IS REQUIRED
 TO INCLUDE THE MANUFACTURER'S SPECS. AND
 INSTALLATION DRAWINGS. SEE ITEM 6.1 OF
 THE ICC REPORT. THE INSTALLATION
 SCHEDULE IS REQUIRED TO SPECIFY THE
 ANCHOR TYPE AND SPACING. SEE SAMPLE FORM
 ATTACHED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-11 Cont ID  
Sent By btrobaug Date 2004-02-20 Time 15:53 Rev Time 2.50
Received By rmcdouga Date 2004-02-11 Time 10:31 Sent To  
Notes
2004-02-11 00:00:00DENIED
  
 1) SUBMIT 2 COPIES OF A SURVEY.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE PLANS ARE REQUIRED TO BE STAMPED
 BY PALM BEACH COUNTY FOR IMPACT FEES.
  
 4) PROVIDE A SQFT BREAKDOWN OF THE
 STRUCTURE. (A/C AREA, GARAGE, COVERED
 PORCHES, ETC.)
  
 5) REVISE THE GLASS BLOCK DETAIL ON 4S2
 TO A ONE HOUR FIRE RATED ASSEMBLY. SEE
 UL LISTING # R11679.
  
 6) INDICATE SIZE AND LOCATION OF ATTIC
 ACCESS AS REQUIRED BY FBC 2309.6.
  
 7) TRUSS CONNECTOR JL 210 REQUIES (8)
 10D X 1-1/2" NAILS TO THE TRUSS. PLEASE
 REVISE TRUSS ANCHOR SCHEDULE ON 5B.
  
 8) THE ATTIC AREA LISTED ON THE ENERGY
 CALCS. DOES NOT INCLUDE THE AREA OF THE
 COFFERED CEILINGS IN THE GREAT ROOM AND
 FOYER.
  
 9) WINDOW #5 IN THE SCHEDULE ON SHEET 5
 IS LOACTED IN BEDROOM 3, NOT IN THE DEN.
  
 10) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11) THE ENGINEERED INSTALLATION
 INSTRUCTIONS ARE REQUIRED FOR THE CLOPAY
 GARAGE DOORS.
  
 12)SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. THE
 ENGINEERING AND INSTALLATION INSTRUCT-
 IONS ARE REQUIRED. INDICATE THE SPECIFIC
 MOUNT TYPES AND ANCHORS THAT WILL BE
 USED.
  
 13) SHEET 5B ROOF FRAMING DETAILS DOES
 NOT HAVE A TITLE BLOCK AND IS NOT SIGNED
 AND SEALED. OTHER SHEETS APPEAR TO BE
 MISSING THE EMBOSSED SEAL. PLEASE
 CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-03-03 Cont ID  
Sent By btrobaug Date 2004-02-20 Time 15:53 Rev Time 0.50
Received By btrobaug Date 2004-02-20 Time 15:36 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-14 Cont ID  
Sent By csiegber Date 2004-02-19 Time 12:15 Rev Time 0.75
Received By btrobaug Date 2004-01-14 Time 14:47 Sent To M
Notes
2004-01-14 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 ON THE PLANS FOR CODE COMPLIANCE.
  
 1} THE 1/0 FEEDER FROM THE METER TO THE
 PANEL IS NOT LARGE ENOUGH FOR 200
 AMPS.SEE 310.15(B)(6).
  
 2} THERE ARE 4 SMALL APPLIANCE CIRCUITS
 SHOWN IN THE LOAD CALCS (6000/1500=4)
 BUT ONLY 3 IN THE PANEL SCHEDULE,PLEASE
 CORRELATE.
  
 3} THE DINING ROOM & MORNING
 (BREAKFAST)ROOM WIRE SIZE LISTED ON THE
 SCHEDULE
 MUST BE # 12 PER210.52(B)(1),SMALL APP.
  
 4}THE RANGE CALCULATION MUST COMPLY WITH
 220.19.8KW MIN.
  
 5} THE OCP @60 AMPS IS TOO LARGE FOR THE
 #8 WIRE FOR THE RANGE LISTED ON THE
 PANEL SCHEDULE PER310.16.
  
 6} THE GARAGE RECEPTACLES DO NOT COMPLY
 WITH 210.8(A)(2),GFI.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-19 Cont ID  
Sent By csiegber Date 2004-02-19 Time 12:15 Rev Time 0.00
Received By csiegber Date 2004-02-19 Time 12:15 Sent To E
Notes
2004-02-19 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-18 Cont ID  
Sent By mmclean Date 2004-02-19 Time 10:35 Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 10:32 Sent To Z
Notes
2004-02-18 00:00:00TO MM/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2004-02-11 Cont ID  
Sent By mmclean Date 2004-01-08 Time 12:01 Rev Time 0.00
Received By rmcdouga Date 2004-01-07 Time 14:42 Sent To  
Notes
2004-01-08 00:00:00TO SFD RACK/E
2004-01-07 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-29 Cont ID  
Sent By btrobaug Date 2004-01-14 Time 15:25 Rev Time 0.50
Received By hmoser Date 2004-01-29 Time 18:41 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-02-02 Cont ID  
Sent By hmoser Date 2004-01-29 Time 18:42 Rev Time 0.25
Received By jleech Date 2004-02-02 Time 12:31 Sent To B
Notes
2004-02-02 00:00:00NO PLUMBING PLAN REVIEW. NO RISER
 DIAGRAM.

Review Stop Z ZONING
Rev No 2 Status P Date 2004-02-19 Cont ID  
Sent By mmclean Date 2004-02-19 Time 10:35 Rev Time 0.00
Received By mmclean Date 2004-02-19 Time 10:35 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-01-08 Cont ID  
Sent By csiegber Date 2004-02-18 Time 10:32 Rev Time 0.00
Received By mmclean Date 2004-01-08 Time 12:01 Sent To I
Notes
2004-01-08 00:00:00DENIED, NEED SETBACKS ON SITE PLANS
 CALLED CONTR