Plan Review Stops For Permit 04010183 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2004-01-09 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-01-06 |
Time |
12:12 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2004-01-09 |
Time |
12:54 |
Sent To |
|
|
Notes |
2004-01-09 00:00:00 | | | PROVISO | | ~~~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | A RISER DIAGRAM MUST BE SUBMITTED FOR | | REVIEW PER 215.5. PLEASE SUBMIT SAME AS | | A REVISION TO THIS PERMT OR A NEW | | PERMIT MAY BE APPLIED FOR AS A SERVICE | | CHANGE. | | THERE IS NO RECORD OF A PERMIT BEING | | ISSUED FOR THE "EXISTING" 200 AMP PANEL | | THAT IS REFERRED TO ON THE LOAD | | CALCULATION,PLEASE INCLUDE THAT WHEN | | APPLYING. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-01-06 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-01-06 |
Time |
12:11 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-01-06 |
Time |
12:11 |
Sent To |
E |
|
Notes |
|
|
|