Plan Review Details - Permit 03121642
Plan Review Stops For Permit 03121642
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-07-02 Cont ID  
Sent By rbrown Date 2004-07-02 Time 10:20 Rev Time 0.00
Received By rbrown Date 2004-07-01 Time 08:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-05-12 Cont ID  
Sent By rbrown Date 2004-05-12 Time 18:58 Rev Time 0.00
Received By rbrown Date 2004-05-11 Time 08:19 Sent To  
Notes
2004-05-11 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 2/17/04:
  
 1) HANDWRITTEN RESPONSE ON COMMENT SHEET
 IS NOTED.THE NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
  
 2) HANDWRITTEN COMMENT RESPONSE IS NOTED
 IMPACT FEES. THE PLANS SHALL BE TAKEN TO
 PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) FBC* 105.13.1SPECIAL INSPECTOR.
 SUBMITTAL OF THE STRUCTURAL INSPECTION
 PLAN IS NOTED.SIGNED/SEALED COPIES OF
 THE THRESHOLD INSPECTOR AGREEMENT MUST
 ALSO BE SUBMITTED BEFORE A BUILDING
 PERMIT CAN BE ISSUED.BLANK FORMS ARE
 AVAILABLE FROM THIS OFFICE IF REQUIRED.
 THREE COPIES OF ALL PLANS AND OTHER
 DOCUMENTS ARE REQUIRED FOR PERMITTING
 PURPOSES.
  
 5) FBC TABLE 600FIRE RESISTANCE RATING
 FOR TYPE II CONSTRUCTION.SHEET A-101,
 THE COMMENT RESPONSE, REVISING THE
 CONSTRUCTION TYPE IS NOTED, BUT IT IS
 SHOWN AS "TYPE II (1 HOUR PROTECTED)".
 THE REQUIRED FIRE RESISTANCE RATINGS FOR
 THE STRUCTURAL ELEMENTS OF A TYPE II
 BUILDING EXCEED 1 HOUR.REMOVE THE
 REFERENCE TO "(1 HOUR PROTECTED)" FROM
 SHEETS A-101, A-117, A-118, A-119 AND
 A-120.
 NOTE: ALSO, FOR TYPE II CONSTRUCTION,
 THE EAST AND WEST WALLS ARE REQUIRED TO
 HAVE A 3-HOUR FIRE RESISTANCE RATING AS
 THEY ARE WITHIN 3 FEET OF THEIR
 RESPECTIVE PROPERTY LINE.AMEND SHEETS
 A-117, A-118 AND A-119.
  
 11) FBC 11-9.1.2ACCESSIBLE UNITS.
 THE COMMENT RESPONSE ADDED TO
 SHEET A-101 IS NOTED, BUT IS NOT FULLY
 CODE COMPLIANT AS FOLLOWS:
 (A) FBC 11-9.2.2(3) & (6)DOOR WIDTHS.
 BATHROOM DOORS 204, 207 AND 266 SHALL
 HAVE AT LEAST 32 INCHES CLEAR OPENING
 WITH THE DOOR OPEN 90 DEGREES MEASURED
 BETWEEN THE FACE OF THE DOOR AND THE
 OPPOSITE STOP.DOOR SCHEDULE A-604
 SHOWS 2'-8" WIDE DOORS.AMEND THE
 SCHEDULE.
 (B) FBC 11-9.2.2(4) ACCESSIBLE STORAGE.
 FOR THE ACCESSIBLE ROOMS/SUITES, AMEND
 THE PLANS TO DEMONSTRATE COMPLIANCE WITH
 THE REQUIREMENT FOR ACCESSIBLE CLOSETS/
 SHELVES.SEE ALSO FBC 11-4.25
 (C) FBC 11-9.2.2(7)KITCHEN COUNTER/
 SINK/CABINETS.FOR THE ACCESSIBLE
 ROOMS/SUITES, AMEND THE PLANS TO
 DEMONSTRATE COMPLIANCE WITH THE
 REQUIREMENT FOR A MAXIMUM HEIGHT OF 34",
 ABOVE FINISH FLOOR, FOR THE THE COUNTER/
 SINK AND FOR 50% OF THE STORAGE SPACE IN
 CABINETS AND FRIDGE-FREEZER TO BE WITHIN
 THE REACH RANGES OF FBC 11-4.2.5 AND
 FBC 11-4.2.6
  
 20) FBC* TABLE 2306.1SHEET A-501,
 DETAIL 2. THE COMMENT RESPONSE IS NOTED.
 THE DETAIL STILL SHOWS 5/8" PLYWOOD,
 OVER CORRUGATED GALVANIZED METAL DECK,
 NAILED TO "SUPPORT" WITH 8D COMMON
 NAILS.THE PROPOSED 8D COMMON NAILS ARE
 NOT APPROPRIATE FOR FIXING THE 5/8"
 PLYWOOD TO CORRUGATED GALVANIZED METAL
 DECK.AMEND THE DETAIL.
  
 22) SHEET S-9 CONNECTORS SCHEDULE AND
 SHEET S-11 SECTION 2.THE COMMENT
 RESPONSE REVISING THE SCHEDULE IS NOTED,
 BUT THE SCHEDULE NOW SHOWS THAT THE
 UPLIFT CAPACITY OF TWO META22 (AND TWO
 HETAL20) EMBEDDED ANCHOR IS ASSUMED TO
 BE TWICE THAT OF A SINGLE ANCHOR.
 REFERENCE TO THE 2004 SIMPSON CATALOGUE
 WILL SHOW THAT A DOUBLE EMBEDDED ANCHOR
 INSTALLATION DOES NOT HAVE DOUBLE THE
 UPLIFT CAPACITY OF A SINGLE ANCHOR
 INSTALLATION IF THE FAILURE MODE IS
 CONCRETE CONE PULL-OUT.AMEND THE
 SCHEDULE.
  
 23) PROVISO:
 SHEETS A-502 & A-505, PLANTER AND
 OBELISK ATTACHMENT DETAILS.ADDITION OF
 DETAILS 15 AND 16 (SHEET S-10) IS NOTED.
 THE SHOP DRAWINGS SHALL BE SUBMITTED TO
 THE THIS OFFICE FOR REVIEW.
  
 25) FBC 13-103.1.2THIS COMMENT HAS NOT
 BEEN PROPERLY ADDRESSED.BEFORE A
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
 ALSO, ADD THE OWNER'S NAME AND THE ZIP
 CODE (33401) TO THE PROJECT INFORMATION
 ON SHEET 1.
  
 26) FBC 13-103.1.1.1THIS COMMENT HAS
 NOT BEEN PROPERLY ADDRESSED. THE
 PROFESSIONAL RESPONSIBLE FOR THE DESIGN
 OF THE ELECTRICAL SYSTEMS SHALL ALSO
 SIGN THE ENERGY CODE COMPLIANCE FORM,
 AND ADD HIS LICENSE, NUMBER TO CERTIFY
 COMPLIANCE.
  
 27) PRODUCT APPROVALS.SUBMITTAL OF ONE
 COPY OF THE STATEWIDE PRODUCT APPROVAL
 LISTING COVER SHEET IS NOTED FOR THE
 FIXED WINDOWS, CASEMENT WINDOWS,
 EXTERIOR DOORS, STORM PANEL SHUTTERS,
 ROOF TILE, ROOF UNDERLAYMENT AND ROOF
 MEMBRANE.SUBMIT THREE COPIES OF ALL
 PRODUCT APPROVALS WITH THE PROPOSED
 PRODUCTS, SIZES AND OPTIONS HIGHLIGHTED.
 ALSO, SUBMIT PRODUCT APPROVALS FOR THE
 PROPOSED 4-PLY BUILT-UP ROOF SYSTEM, THE
 EXTERIOR METAL SINGLE DOORS AND THE
 MULLIONS (OR STOREFRONT) FOR THE
 RESTAURANT AND COURTYARD TRANSOMS.
 THE FOLLOWING COMMENTS APPLY TO THOSE
 STATEWIDE PRODUCT APPROVAL LISTINGS THAT
 WERE ALREADY SUBMITTED:
 (A) FRENCH DOORS.THE SUBMITTAL OF
 STATEWIDE PRODUCT APPROVAL LISTING COVER
 SHEET FL253 IS NOTED.THE LISTING IS
 FOR THREE DIFFERENT DOOR TYPES AND
 REFERS TO A SEPARATE MIAMI-DADE PRODUCT
 APPROVAL FOR EACH ONE.MARK THE LISTING
 TO SHOW WHICH DOOR TYPE IS PROPOSED AND
 INCLUDE THREE COPIES OF THE RELEVANT
 MIAMI-DADE PRODUCT APPROVAL.
 COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,
 WWW.MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH
 _APP.ASP
 (B) FIXED WINDOWS.THE SUBMITTAL OF
 STATEWIDE PRODUCT APPROVAL LISTING COVER
 SHEET FL243 IS NOTED.THE LISTING IS
 FOR EIGHT DIFFERENT WINDOW TYPES AND
 REFERS TO A SEPARATE MIAMI-DADE PRODUCT
 APPROVAL FOR EACH ONE.MARK THE LISTING
 TO SHOW WHICH WINDOW TYPE IS PROPOSED
 AND INCLUDE THREE COPIES OF THE RELEVANT
 MIAMI-DADE PRODUCT APPROVAL.
 COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,
 WWW.MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH
 _APP.ASP
 (C) CASEMENT WINDOWS.THE SUBMITTAL OF
 STATEWIDE PRODUCT APPROVAL LISTING COVER
 SHEET FL245 IS NOTED.THE LISTING IS
 FOR FOUR DIFFERENT WINDOW TYPES AND
 REFERS TO A SEPARATE MIAMI-DADE PRODUCT
 APPROVAL FOR EACH ONE.MARK THE LISTING
 TO SHOW WHICH WINDOW TYPE IS PROPOSED
 AND INCLUDE THREE COPIES OF THE RELEVANT
 MIAMI-DADE PRODUCT APPROVAL.
 COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,
 WWW.MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH
 _APP.ASP
 (D) CLAY ROOF TILE.THE SUBMITTAL OF
 STATEWIDE PRODUCT APPROVAL LISTING COVER
 SHEET FL738 IS NOTED.THE LISTING
 PROVIDES A WEB-LINK TO THE SBCCI
 EVALUATION REPORT DOCUMENT USED TO
 EVALUATE THE PRODUCT.INCLUDE THREE
 COPIES OF THE SBCCI EVALUATION REPORT
 MARKED TO SHOW WHICH PRODUCT IS TO BE
 USED.
 (E) STORM SHUTTER.THE SUBMITTAL OF
 STATEWIDE PRODUCT APPROVAL LISTING COVER
 SHEET FL347 IS NOTED.THE LISTING
 PROVIDES A WEB-LINK TO THE MIAMI-DADE
 PRODUCT APPROVAL DOCUMENT USED TO
 EVALUATE THE PRODUCT.INCLUDE THREE
 COPIES OF THE MIAMI-DADE PRODUCT
 APPROVAL MARKED TO SHOW WHAT SPAN AND
 ANCHOR SPACING IS PROPOSED. ON WHICH
 OPENINGS ARE THEY TO BE USED?NOTE: FOR
 COMMERCIAL STRUCTURES, REMOVABLE STORM
 PANELS MAY NOT BE USED ABOVE THE FIRST
 (GROUND) FLOOR.
  
 29) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-20 Cont ID  
Sent By rbrown Date 2004-02-20 Time 21:12 Rev Time 0.00
Received By rbrown Date 2004-02-17 Time 11:10 Sent To  
Notes
2004-02-17 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) FBC* 105.13.1SPECIAL INSPECTOR.A
 STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT FOR THE CONSTRUCTION OF
 A THRESHOLD BUILDING.A THRESHOLD
 BUILDING IS ANY BUILDING WHICH IS
 GREATER THAN THREE STORIES OR 50 FEET IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY WITH 5,000 SQFT AREA AND
 GREATER THAN 500 OCCUPANTS.THREE
 COPIES OF THE PLANS AND OTHER DOCUMENTS
 WILL BE REQUIRED FOR PERMITTING PURPOSES
  
 4) 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM NAME, ADDRESS AND
 TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND
 DATED SEAL
 - INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
 THE ARCHITECTURAL BUSINESS LICENSE
 NUMBER STATED ON THE PLANS, ARC001407,
 IS NOT CORRECT.IT SHOULD BE AAC001407.
 AMEND THE TITLE BLOCK ON EACH SHEET.
 ALSO THE NAME AND LICENSE NUMBER ON THE
 SEAL OF JOSE LUIS GONZALEZ PEROTTI COULD
 NOT BE VERIFIED ON STATE DBPR WEBSITE
 WWW.MYFLORIDALICENSE.COM/DEFAULT.ASP
 AS ALL SEARCHES RETURNED 'NO RESULTS
 FOUND'.PROVIDE DOCUMENTATION TO VERIFY
 THE LICENSE STATUS.ONE COPY OF SHEET
 A-001 HAS BEEN RETAINED FOR OUR FILE.
  
 5) FBC 1511.1.3ALLOWABLE HEIGHT.
 SHEET A-108.THE ROOFTOP STRUCTURES
 MUST BE CONSIDERED AS AN ADDITIONAL
 STORY AS THEY ARE BEING USED FOR
 PURPOSES OTHER THAN TO HOUSE MECHANICAL
 EQUIPMENT OR TO SHELTER VERTICAL SHAFT
 OPENINGS IN THE ROOF.THEREFOR THE
 BUILDING EXCEEDS THE 65 FEET MAXIMUM
 HEIGHT PERMITTED FOR A TYPE IV BUILDING
 WITH 1-HOUR PROTECTION AND A RESIDENTIAL
 OCCUPANCY, PER TABLE 500.AMEND THE
 CONSTRUCTION TYPE/PLANS.
  
 6) FBC 503.3.3.2MEZZANINE, SHEET A-103
 MEZZANINES SHALL NOT EXCEED 1/3 OF THE
 AREA OF THE ROOM IN WHICH THEY ARE
 LOCATED AND ENCLOSED SPACE UNDER THE
 MEZZANINE SHALL NOT BE CONSIDERED IN THE
 DETERMINATION OF THAT AREA.THE 'LOFTS'
 AND THE ELEVATOR MACHINE ROOM, PUMP
 ROOM, ELECTRICAL ROOM AND LAUNDRY DO NOT
 QUALIFY AS MEZZANINES AND MUST THEREFOR
 BE CONSIDERED AS AN ADDITIONAL STOREY.
 AMEND THE CONSTRUCTION TYPE/PLANS (SEE
 COMMENT ABOVE).
  
 7) FBC* 102.2.4FIRE DISTRICT - ROOF.
 ROOF COVERINGS IN THE FIRE DISTRICT
 SHALL CONFORM TO THE REQUIREMENTS OF
 CLASS A OR B ROOF COVERINGS.ANNOTATE
 THE PLANS TO DEMONSTRATE COMPLIANCE.
  
 8) FBC* 102.2.7FIRE DISTRICT - TRIM.
 SHEETS A-201 TO A-303 SHOW 'CYPRESS
 OUTRIGGERS AND T&G EAVES'. ARCHITECTURAL
 TRIM ON BUILDINGS LOCATED IN THE FIRE
 DISTRICT SHALL BE CONSTRUCTED OF
 APPROVED NON-COMBUSTIBLE MATERIALS OR
 FIRE RETARDANT TREATED WOOD.AMEND THE
 PLANS TO DEMONSTRATE COMPLIANCE.
  
 9) FBC 11-4.13.4 SHEET A-102, ACCESSIBLE
 DOORS.CORRIDOR DOOR 148 IS SHOWN AS
 HAVING TWO INDEPENDENTLY OPERATED DOOR
 LEAVES.AT LEAST ONE LEAF SHALL HAVE A
 MINIMUM CLEAR OPENING OF 32 INCHES.
 AMEND THE PLAN.
  
  
  
 10) FBC 11-4.13.6SHEET A-102,
 MANEUVERING CLEARANCES AT DOORS.ADD A
 DIMENSION TO THE PLAN AT RESTAURANT DOOR
 157 TO ENSURE THAT A CLEARANCE OF AT
 LEAST 18" IS PROVIDED BETWEEN THE STRIKE
 EDGE OF THE DOOR AND THE ADJACENT WALL
 ON THE PULL SIDE OF THE DOOR.
  
 11) FBC 11-9.1.2ACCESSIBLE SUITES.
 AMEND/ANNOTATE THE PLANS TO SHOW WHICH
 SUITES ARE TO BE MADE ACCESSIBLE AND
 PROVIDE THE RELEVANT DIMENSIONED PLANS
 TO DEMONSTRATE COMPLIANCE WITH ALL PARTS
 OF FBC 11-9.2.2
  
 12) FBC 11-9.1.3PERSONS WITH HEARING
 IMPAIRMENTS.ANNOTATE THE PLANS TO SHOW
 WHICH SUITES, IN ADDITION TO THOSE
 REQUIRED TO BE ACCESSIBLE, ARE TO COMPLY
 WITH FBC 11-9.3 (VISUAL ALARMS,
 NOTIFICATION DEVICES AND TELEPHONES).
  
 13) FBC 11-4.9.4STAIR HANDRAILS.AT
 THE TOP OF THE STAIR, HANDRAILS SHALL
 EXTEND HORIZONTALLY, AT LEAST 12 INCHES
 BEYOND THE TOP RISER.AT THE BOTTOM OF
 THE STAIR, HANDRAILS SHALL CONTINUE TO
 SLOPE, BEYOND THE BOTTOM RISER, FOR A
 DISTANCE EQUAL TO THE WIDTH OF ONE RISER
 AND THEN EXTEND HORIZONTALLY FOR A
 FURTHER 12 INCHES.AMEND THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 14) SHEET A-118MEZZANINE LEVEL.NO
 FIRE-RATING IS SHOWN FOR THE WALL
 BETWEEN SUITE 101 AND THE ADJACENT
 REAR EXIT CORRIDOR.
  
 15) FBC 3003.4.1ELEVATOR, STRETCHER
 REQUIREMENTS.AT LEAST ONE OF THE
 ELEVATORS SHALL BE ABLE TO ACCOMMODATE
 A 76" LONG, 24" WIDE AMBULANCE STRETCHER
 IN THE HORIZONTAL POSITION.THAT
 ELEVATOR SHALL BE IDENTIFIED WITH
 SIGNAGE.AMEND THE PLANS TO DEMONSTRATE
 COMPLIANCE.
  
 16) FBC 1007.8.2.1SPIRAL STAIRS IN
 SUITES 100, 102, 103, 104, 106 AND 108.
 PROVIDE DETAILS TO DEMONSTRATE
 COMPLIANCE WITH THE REQUIREMENTS FOR
 SPIRAL STAIRS.
  
 17) FBC 1608.2.1SHEET A-502, DETAIL 6.
 THE NOTE ABOUT HANDRAIL LOAD IS NOTED
 BUT IT IS INCOMPLETE.STAIR HANDRAILS
 SHALL BE DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB AND A LINE
  
  
  
  
 LOAD OF 50 PLF.THESE LOADS SHALL NOT
 BE APPLIED SIMULTANEOUSLY BUT SHALL BE
 APPLIED INDIVIDUALLY AT ANY POINT, AND
 IN ANY DIRECTION, TO PRODUCE MAXIMUM
 STRESS IN EACH OF THE COMPONENTS OR
 SUPPORTS.AMEND/ANNOTATE THE PLANS.
  
 18) FBC 1608.2.2 ALL GUARDRAILS SHALL BE
 DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB APPLIED IN
 ANY DIRECTION AT THE TOP OF THE
 GUARDRAIL, A CONCENTRATED HORIZONTAL
 LOAD OF 200 LB APPLIED ON A 1 SQ FT AREA
 AT ANY POINT, AND A LINE LOAD OF 50 PLF
 APPLIED HORIZONTALLY AT THE REQUIRED
 GUARDRAIL HEIGHT WITH A SIMULTANEOUS
 LINE LOAD OF 100 PLF APPLIED VERTICALLY
 DOWNWARD ON THE TOP OF THE GUARDRAIL.
 THESE LOADS SHALL NOT BE APPLIED
 SIMULTANEOUSLY (UNLESS NOTED ABOVE) BUT
 SHALL BE APPLIED INDIVIDUALLY TO PRODUCE
 MAXIMUM STRESS IN EACH OF THE COMPONENTS
 OR SUPPORTS.AMEND/ANNOTATE THE PLANS.
  
 19) FBC 1015.3SHEET A-502, DETAIL 9.
 A 6" SPHERE SHALL NOT PASS THROUGH THE
 TRIANGULAR OPENING FORMED BY A TREAD, A
 RISER AND THE BOTTOM EDGE OF THE
 GUARDING.ANNOTATE THE DETAIL TO
 DEMONSTRATE COMPLIANCE.
  
 20) FBC* TABLE 2306.1SHEET A-501,
 DETAIL 2.FASTENING OF PLYWOOD WOOD
 SHEATHING SHALL BE 4" O.C. AT THE EDGES
 IN ZONE 3.AMEND THE NOTE.ALSO,
 CLARIFY THE MEANS OF FASTENING THE
 PLYWOOD SHEATHING TO THE STRUCTURE
 BELOW (I.E. CORRUGATED METAL DECK).
  
 21) FBC 1606.3SHEET S-7.AMEND THE
 PLANS TO STATE THE CALCULATED WIND-
 INDUCED UPLIFT PRESSURES ON THE MEMBRANE
 SYSTEM ROOF OVER THE EQUIPMENT/
 MECHANICAL/TOILET ROOMS.
  
 22) SHEET S-9 CONNECTORS SCHEDULE AND
 SHEET S-11 SECTION 2.FROM A SEARCH ON
 THE SIMPSON WEBSITE WWW.STRONGTIE.COM
 AND THE 2004 CATALOG, THE SPECIFIED
 'ETA22' IS NOT A CURRENT SIMPSON ANCHOR
 REFERENCE.AMEND THE PLANS TO SPECIFY
 VALID ANCHOR REFERENES FOR WHICH THE
 UPLIFT CAPAPCITY CAN BE VERIFIED.
  
  
 23) FBC* 104.2.1.2SHEETS A-502 & A-505
 PLANTER AND OBELISK ATTACHMENT DETAILS.
 THE PLANS DO NOT INCLUDE SUFFICIENT
 INFORMATION ABOUT THE MATERIALS AND
 CONSTRUCTION TO DETERMINE SUITABILITY OF
 OF THE PROPOSED MEANS OF ATTACHMENT.
  
  
 24) FBC 1007SHEET A-502, DETAIL 5 -
 STAIR.THE DETAIL REFERS TO THE
 STRUCTURAL DRAWINGS.NO STAIR/LANDING
 LAYOUT DRAWINGS OR CONSTRUCTION DETAILS
 HAVE BEEN SUBMITTED.
  
 25) FBC 13-103.1.2BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 26) FBC 13-103.1.1.1THE PROFESSIONALS
 RESPONSIBLE FOR THE DESIGN OF THE
 BUILDING SHELL AND THE ELECTRICAL,
 LIGHTING, MECHANICAL AND PLUMBING
 SYSTEMS SHALL EACH SIGN THE ENERGY CODE
 COMPLIANCE FORM, TO CERTIFY COMPLIANCE.
  
 27) SUBMIT PRODUCT APPROVALS FOR THE
 WINDOWS, EXTERIOR DOORS, STORE FRONT,
 ROOF TILES AND MEMBRANE ROOFING.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
 LOCAL AND SITE-SPECIFIC PRODUCT APPROVAL
 FORMS ARE AVAILABLE FROM THIS OFFICE FOR
 PRODUCTS WHICH DO NOT HAVE A STATEWIDE
 APPROVAL LISTING.
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE, TO IDENTIFY
 WHICH PRODUCT OPTIONS/MATERIALS/SIZES
 ARE TO BE USED.
  
 28) A SEPARATE PERMIT APPLICATION WILL
 BE REQIRED FOR THE SWIMMING POOL.
  
 29) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-07-02 Cont ID  
Sent By dpalmer Date 2004-07-02 Time 09:19 Rev Time 0.50
Received By dpalmer Date 2004-07-02 Time 09:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-06-21 Cont ID  
Sent By dpalmer Date 2004-06-21 Time 09:38 Rev Time 2.00
Received By dpalmer Date 2004-06-17 Time 19:52 Sent To  
Notes
2004-06-21 00:00:00*** TEMP UNSAT *****
  
  
 1)NOTE: PLANS FOR NIGHT TIME/AFTER DUSK
 SWIMMING NOT NOTED.
 CALLED ENGINEER AND OWNERS REP.
 PHOTOMETRIC EITHER NEEDS TO BE STAMPED
 BY PALM BEACH COUNTY HEALTH DEPT FOR
 NIGHTIME SWIMMING OR NOTE NEEDS TO BE
 ADDED TO PLANS STATING "NO SWIMMING OR
 ACCESS AFTER DUSK"
  
 SHEET E-4A MAY BE CHANGED OUT W/OUT
 RESUB.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
2004-06-17 00:00:00TWO ROLLS AT ELEC/DVP'S DESK FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-04-27 Cont ID  
Sent By dpalmer Date 2004-04-27 Time 16:58 Rev Time 4.00
Received By dpalmer Date 2004-04-27 Time 16:58 Sent To  
Notes
2004-04-27 00:00:00*** UNSAT ***
  
 PLEASE SEE SOME COMMENTS FROM FIRST
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE IT APPEARS NOW USEAGE
 HAS NOW BEEN CLARIFIED FOR HOTEL USEAGE.
 PLEASE SEE 240.24B FOR LOCATIONS OF
 PANELS.
  
 2)NOTE: PLEASE SEE NOTE;5 FROM FIRST
 REVIEW. PLEASE PROVIDE NOTE/INFORMATION
 IN REFERENCE TO LIGHTING FOR NIGHT TIME
 SWIMMING? PLEASE PROVIDE AS FOR WIND
 LOAD ON LT POLE PER FBC 140 MPH.
  
 3)NOTE: PLEASE SEE TWO PANEL HC'S SHOWN
 ON RISER.
  
 4)NOTE: PLEASE SEE NOTE: 13 FROM FIRST
 REVIEW. PLEASE PROVIDE ALL INFORMATION
 FOR FIRE PUMP AND ASSOC EQUIPMENT.
 695.4B1, 230.76,230.79,110.27
 PLEASE NOTE: LOCATION OF DISC MEANS FOR
 FIRE PUMP, 695.3, 230.72.
 LOCATION OF MAINS PER NEC AND FIRE DEPT
 SHUTTING DOWN OF FIRE PUMP.
 KNOW BOX ETC. LOCATION ON SECOND FLR
 HAS NOT BEEN APPROVED BY THIS OFFICE AT
 THIS TIME.
 PLEASE SUBMIT SPECS FOR ALL EQUIPMENT.
  
 5)NOTE: RESPONSE TO NOTE:9 FROM FIRST
 REVIEW MENTIONS GRC FOR ALL CONDUIT
 INSTALLATIONS / FEEDERS ETC. PLEASE
 VERIFY THIS. THIS IS ONLY A NOTE.
  
 PLEASE SEE FS 553.80(2)(B) FOR ANY
 COMMENTS BEING REPEATED FOR THE SAME
 COMMENTS. THIS NOTICE IS GIVEN ON
 SECOND REVIEWS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-02-12 Cont ID  
Sent By dpalmer Date 2004-02-11 Time 16:13 Rev Time 8.00
Received By dpalmer Date 2004-02-11 Time 07:39 Sent To  
Notes
2004-02-11 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE SEE 210.60A AND 210.52
 FOR RECEPT SPACING IN UNITS/ROOMS.
 THERE ARE MANY MISSING FOR 2' OF WALL
 SPACE AND W/IN 6' OF DOORWAYS.
  
 2)NOTE: PLEASE PROVIDE NOTE ON PLANS
 FOR REQUIRED BUSWAY/BUSDUCT CURBING PER
 368.8B(2)
  
 3)NOTE: PLEASE CLARIFY USEAGE. PERMIT
 APPLICATION AND PLANS CALL FOR A NEW
 5 STORY HOTEL. ELECTRICAL PLANS HAVE
 EACH INDIVIDUAL UNIT ON A SEPARATE
 ELECTRICAL METER FROM FPL. PLEASE
 PROVIDE INFORMATION FROM FPL AND OR HOW
 THIS FITS INTO BEING A HOTEL? IS BILLING
 FOR ALL METERS GOING TO ONE OWNER? ARE
 THESE "EXTENDED STAY" UNITS? ETC
 PLEASE PROVIDE FPL'S CONFORMATION OF
 THIS.
 THIS IS ALSO PROVIDING A POINT IN THE
 UDP TO RUN POWER TO OTHER LOCALS W/OUT
 BEING METERED FROM FPL.PLEASE VERIFY
 ALL OF THE ABOVE.
  
 4)NOTE: PLEASE PROVIDE ALL INFORMATION
 ON PLANS AND TITLE BLOCKS PER FAC
 61G1-16.004 FOR ARCH'S. THE ADDRESS
 IS REQ'D ON PLANS/ TITLE BLOCK.
 PLEASE ALSO SEE LICENSE INFORMATION FOR
 ARCH'S FIRM IS MISSING AS REQ'D PER
 ABOVE. PLEASE ALSO SEE FS 481.219 FOR
 REQ'D CERTIFICATE OF AUTHORIZATIONFOR
  
 5)NOTE: PLANS SHOW NEW POOL, HOWEVER
 POOL IS REQ'D TO BE UNDER A SEAPARATE
 PERMIT.
 PLEASE PROVIDE NOTE ON PLANS IN FOR
 TIMES OF PERMITTED SWIMMING. IF SWIMMING
 IS GOING TO BE AFTER DUSK. A PHOTOMETRIC
 STUDY WILL BE REQUIRED AND PLANS WILL
 ALSO REQ'D TO BE STAMPED BY THE PALM
 BEACH COUNTY HEALTH DEPT.
  
 6)NOTE:PLEASE SEE PANEL "HA", SHOW CIR-
 -CUIT FOR DRYER AT 5KW, HOWEVEROCP
 IS SHWON AT 2P-20A?
  
 7)NOTE: PLEASE SEE "DWELLING UNIT"
 DEFINITION IN NEC AND OTHER CODES.
 PLEASE SEE USAGE AND THE AMOUNT OF
 LAUNDRY FIXTURES REQ'D.
 PLEASE SEE PLUMB COMMENTS.
 THIS QUESTION WILL COINCIDE WITH NOTE
 #3 ABOVE.
  
 8)NOTE: PLEASE "UDP", SHOWN AS BEING MLO
 WITH TWO MAINS IN EQUIPMENT, HOWEVER
 "UDP" IS SHOWN AS HAVING 42 SPACES??
 PLEASE SEE THIS IS NOT PERMITTED DUE TO
 THE AMOUNT OF SPACES FOR A POSSIBLE
 ADDITION OF 33 MORE MAINS? (1P BRKRS).
 PLEASE SEE 230.71.A MCB MAY BE INSTALL
 -ED?
  
 9)NOTE: PLEASE SEE ALL PANEL SCHEDULES,
 FEEDERS/ RISER DIAGRAM IS MISSING
 EQUIPMENT GROUNDING CONDUCTORS PER
 250.110,250.24 ETC , SIZE PER 250.122
  
 10)NOTE: PLEASE PROVIDE COMPLETE FIXTURE
 SCHEDULE.
  
 11)NOTE: PLEASE SEE AREAS REQUIRED TO
 MEET 700.16.
 PLEASE ALSO SEE FIRE REVIEW COMMENTS
 FOR EM/EXT LTS REQUIRED. SEE EM/EXT FIX-
 -TURES SHOWN INDICATE HAVING AN EMERGEN-
 -CY BALLAST,HOWEVER NO INDICATION OF
 BATTERY BACK UP PER 700.12
  
 12)NOTE: PLEASE INDICATE/SHOW ALL HEIGHT
 -S FOR ALL ELECTRICAL DEVICES PER
 FHAR 24CFR 100.205. (FAIR HOUSING)
  
 13)NOTE: PLEASE PROVIDE ALL INFORMATION
 FOR FIRE PUMP. PLEASE ALSO PROVIDE
 INFORMATION ON RISER DIAGRAM FOR FIRE
 PUMP. PLEASE SEE 695.4B1
 PLEASE ALSO SEE 230.76, 230.79 FOR
 DISCONNECTING MEANS. PLEASE ALSO NOTE
 SIGNAGE FOR FIRE PUMP/LOCATION ETC IS
 REQ'D TO BE NOTED ONPLANS.(SIGNAGE)
  
 14)NOTE: PLEASE SEE RISER DIAGRAMS SHOWS
 FUTURE CONDUITS FOR RESTARUANT, YET
 ON THE RIGHT HAND SIDE OF E-7 , NOTE
 MENTIONS A 3P-400A MCB? PLEASE CLARIFY
 IF A MAIN IS GOING TO BE INSTALLED AT
 THIS TIME. IF SO, PLEASE PROVIDE INFOR-
 -MATION FOR DISC. IF NOT, PLEASE ADJUST.
  
 15)NOTE: PLEASE SEE GUTTER SIZE SHOWN,
 RISER APPEAR TO BE A MISPRINT FOR THE
 SIZE OF 12"X12"X6",, SHOULD BE 6'?
  
 16)NOTE: PLEASE SEE PANEL "HB", SHOWN
 AS 22.5 A'S. (MISPRINT)? 225A'S.
 "HB" HAS 200A OCP FEED.
  
 17)NOTE: PLEASE NOTE ON PLANS ALL
 ELECTRICAL WORK TO MEET 2002 NEC.
  
 18)NOTE: PLEASE SEE LOAD CALCULATIONS
 ON E-6, SHOWN AS 48 UNITS? PLEASE VERIFY
 THE OTHER 8 MISSING UNITS?
 215.5
  
 19)NOTE: PLEASE SEE 215.3,230.42 ETC,
 ALL CONTINUOUS LOADS ARE ALSO TO BE
 SHOWN AT 125%, NOT JUST THE LARGEST
 MOTOR LOAD.
  
 20)NOTE: PLEASE SEE THAT ELEVATOR MAINS
 ARE SHOWN AS ELEV 1,2 WHICH IS FINE.
 HOWEVER, THEY ARE ALSO MAINS 5,6?
 PLEASE ADJUST NOTES.
  
 21)NOTE: PLEASE SEE SD LOCATIONS TO
 MEETNFPA-72 8-1.4.1.6.2
 PLEASE SEE 8-1.4.2, SD'S REQUIRMENTS
 W/IN 20'OF COOKING APPLIANCES. PLEASE
 ALSO SEE 3' FROM BATH DOORS. PLEASE
 SEE WHICH TYPE ARE PERMITTED.
  
 PLEASE SEE ONE SET OF PLANS HAVE MOST
 ITEMS HIGHLIGHTED. PLEASE SEE, RAILING
 AREA OF SECOND FLOOR MEZZ UNITS ARE
 CONSIDERED WALL SPACE PER NEC, AND ARE
 REQ'D TO MEET 210.52 ALSO.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2004-04-20 Cont ID  
Sent By mamini Date 2004-04-20 Time 10:25 Rev Time 1.00
Received By mamini Date 2004-04-20 Time 10:25 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-01-23 Cont ID  
Sent By mamini Date 2004-01-23 Time 10:44 Rev Time 1.00
Received By mamini Date 2004-01-23 Time 10:44 Sent To  
Notes
2004-01-23 00:00:00FAILED:
 1. PLEASE SUBMIT CIVIL PLANS ONLY TO THE
 PUBLIC UTILITIES & ENGINEERING SERVICES
 FOR THEIR REVIEW AND APPROVAL OF ALL THE
 CONNECTIONS TO CITY SERVICES, ATT;MANNY
 GONZALEZ 659-8040 EXT. 2306
 2. ALL PARKING STALLS MUST BE PAINTED
 4" DOUBLE STRIPES, PER CITY REQUIREMENT.
 3. PLEASE STATE IF, GARBAGE WILL BE CITY
 OR PRIVATE PICK UP, IF CITY THEN SIZE
 AND LOCATION MUST BE APPROVED BY THE
 SANITATION DEPARTMENT, JOHNNY THOMAS
 659-8048 EXT. 2273.
 4. ANY WORK WITHIN FERN AND THE ALLEY'
 R.O.W REQUIRES PERMIT FROM THE PUBLIC
 UTILITIES AND ENGINEERING, NOTE TO G.C
 5. PLEASE PROVIDE STORM WATER CALC. FOR
 OUR REVIEW AND APPROVAL, INCLUDE
 PERVIOUS AND IMPERVIOUS AREA FOR THE
 TOTAL SITE.
 6. PLEASE CONTACT RODNEY COMPO FOR SIZE,
 ISTALLATION AND INSPECTION OF THE
 PROPOSED GREASE/WATER SEPARATOR AT
 837-4051 EXT. 4047, NOTE TO G.C
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-06-11 Cont ID  
Sent By mcarsill Date 2004-06-11 Time 12:19 Rev Time 0.00
Received By mcarsill Date 2004-06-11 Time 12:19 Sent To  
Notes
2004-06-11 00:00:001) LOCKING CAPS ARE TO BE INSTALLED
 ON FDC.
  
 2) THE TWO BURNER DEVICE IN ROOMS IS
 A STOVE OR HOT PLATE ARRANGEMENT.
 PLEASE ADVISE.
  
 3) TACTILE SIGNAGE SHOULD BE LOCATED
 AT STAIR OPENINGS NOT INSIDE THE
 STAIRS.
  
 4) LOW WALL DETAIL SHALL RESIST
 HORIZONTAL AND VERTICAL LOADS EXPECTED
 TO BE PLACED UPON IT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-04-23 Cont ID  
Sent By mcarsill Date 2004-04-23 Time 15:36 Rev Time 0.00
Received By mcarsill Date 2004-04-23 Time 15:36 Sent To  
Notes
2004-04-23 00:00:001) TACTILE SIGNAGE REQUIRED AT EXIT
 DOOR LOCATIONS.
  
 2) ALL SHAFTWAYS LARGE ENOUGH FOR
 PERSONS TO FALL INTO MUST BE IDENTIFIED
 BY SIGNAGE "SHAFTWAY".
  
 3) KNOX-BOX LOCKING CAPS REQUIRED
 ON FIRE DEPARTMENT CONNECTION.
  
 4) PANIC HARDWARE REQUIRED ON EXIT
 DOORS LOCATED FOR THE POOL DECK.
  
 5) WHAT PREVENTS PERSONS FROM LEAVING
 THE EXTERIOR DOOR NEAR SUITE 105 AND
 GOING DIRECTLY INTO THE VEHICULAR EXIT
 DRIVE LANE.
  
 6) ARE THE STAIRS ON THE ROOF TERRACE
 SLIP RESISTANT?
  
 7) THE BUILDING ADDRESS IS NOTED ON
 THE FRONT ELEVATION. WILL THE LOCATION
 BE CLEARLY VISIBLE AT ITS MOUNTING
 HEIGHT. PLEASE ADVISE.
  
 8) SIGNS REQUIRED IN STAIRWELLS
 INDICATING STAIR IDENTITY, TERMINUS
 LOCATIONS AT TOP AND BOTTOM, ETC.
  
 9) ALL FIRE RATED DOORS SHALL BE
 EQUIPED WITH SELF-CLOSING DEVICES
 TO CAUSE THE DOORS TO POSITIVELY LATCH.
  
 10) SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE ALARM SYSTEM AND
 FIRE SPRINKLER SYSTEM.
  
 11) WHAT PREVENTS VEHICULAR DAMAGE
 TO THE FIRE-LINE BACKFLOW DEVICE.
  
 12) THE MINIMUM SIZE FIRE LINE SHALL
 BE AT LEAST 6 INCHES. ON SHEET FP1
 THREE INCH LINES ARE SHOWN. PLEASE
 ADVISE.
  
 13) THE REQUIRED FIRE ALARM SYSTEM SHALL
 UL LISTED FOR CENTRAL STATION SERVICE.
  
 14) THE FIRE ALARM SYSTEM CIRCUITS
 SHALL BE CLASS A, STYLE D OR FULLY
 ADDRESSABLE.
  
 15) NO ELECTRICAL ALLOWED IN STAIRWELL
 EXCEPT REQUIRED EMERGENCY LIGHTING
 EQUIPMENT FOR THE STAIRWELLS.
  
 16) THE FIRE PUMP ROOM IS REQUIRED
 TO HAVE EMERGENCY LIGHTING.
  
 17) REQUIRED SMOKE DETECTORS APPEAR
 TO BE MISSING FROM SEVERAL UNITS
 LOCATED ON THE SECOND FLOOR. SOME
 UNITS HAVE SMOKE DETECTORS IN THE
 HALLWAY AND SOME DO NOT. PLEASE
 EXPLAIN RATIONALE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-01-22 Cont ID  
Sent By mcarsill Date 2004-01-22 Time 15:32 Rev Time 0.00
Received By mcarsill Date 2004-01-22 Time 15:32 Sent To  
Notes
2004-01-22 00:00:001) TAMPER SWITCHES, CHAIN AND LOCK
 ARE REQUIRED ON FIRE LINE BACKFLOW
 DEVICE.
  
 2) PROPOSED FIRE DEPARTMENT CONNECTION
 SHALL BE BE WITHIN 150 FEET OF A
 FIRE HYDRANT.
  
 3) A KNOX-BOX WILL BE REQUIRED.
  
 4) A TEMPORARY STANDPIPE WILL BE
 REQUIRED WHEN THE BUILDING REACHES
 THREE STORIES OR THIRTY FEET IN
 HEIGHT.
  
 5) STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 6) WILL THE PARALLEL PARKING SPACES
 ON FERN STREET INTERFERE WITH THE
 FIRE DEPARTMENT CONNECTION LOCATION.
  
 7) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 8) PLEASE INDICATE ALL FIRE
 EXTINGUISHER LOCATIONS.
  
 9) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWING. A MINIMUM 6" HIGH
 NUMBERS ARE REQUIRED.
  
 10) PLEASE INDICATE PRESCRIPTIVE
 CODE REQUIREMENTS FOR ALL HANDRAILS
 AND GUARDRAILS.
  
 11) EMERGENCY INSTRUCTIONS ARE REQUIRED
 IN EACH GUESTROOM.
  
 12) NO COMBUSTIBLES ARE ALLOWED IN
 RETURN AIR PLENUMS.
  
 13) SOME EXIT SIGNS APPEAR TO BE
 MISSING FROM PAGE E-1.
  
 14) EMERGENCY LIGHTS NEEDED IN BATHROOMS
 ON FIRST FLOOR.
  
 15) EMERGENCY LIGTING REQUIRED IN FIRE
 PUMP ROOM.
  
 16) SMOKE DETECTORS APPEAR TO BE
 MISSING IN SEVERAL LOCALES ON PAGE E-3.
  
 17) FUTURE RESTAURANT AREA IS TO BE
 FIRE SPRINKLER PROTECTED PRIOR TO
 HOTEL REQUESTING A C OF O.
  
 18) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER AND FIRE ALARM
 SYSTEM.
  
 19) SHAFTS LARGE ENOUGH FOR PERSONS
 TO FALL INTO SHALL BE MARKED SHAFTWAY.
  
 20) PLEASE INDICATE ROOMS DESIGNATED
 FOR THE HEARING IMPAIRED AND DESIGNATE
 FIRE ALARM VISUAL DEVICES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-08 Cont ID  
Sent By csiegber Date 2004-06-08 Time 11:32 Rev Time 0.00
Received By csiegber Date 2004-06-08 Time 11:32 Sent To  
Notes
2004-06-08 00:00:00TO COMM BD#43

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-14 Cont ID  
Sent By csiegber Date 2004-04-14 Time 12:22 Rev Time 0.00
Received By csiegber Date 2004-04-14 Time 12:22 Sent To  
Notes
2004-04-14 00:00:00TO COMM BD#64 INCLUDE Z/ROLLS ON RACK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-23 Cont ID  
Sent By csiegber Date 2004-02-23 Time 10:25 Rev Time 0.00
Received By rbrown Date 2003-12-30 Time 08:25 Sent To  
Notes
2004-01-22 00:00:0012/30/2003 TO Z
 TO COMM BD#49
2003-12-30 00:00:00ALSO DMP HOLD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-06-23 Cont ID  
Sent By pkrauss Date 2004-06-23 Time 11:13 Rev Time 1.30
Received By pkrauss Date 2004-06-23 Time 09:03 Sent To  
Notes
2004-06-23 00:00:00PROVISO:
 PLEASE NOTE, PLANS INDICATE FUTURE
 ITCHEN & RESTAURANT BUT NO ALLOWANCE OR
 INDICATION FOR EXHAUST FROM GREASE DUCT.
 EXHAUST FROM GREASE DUCT SHALL BE A
 MINIMUM OF 10 FT FROM PROPERTY LINES,
 ADJACENT BUILDINGS, AND AIR INTAKES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-04-24 Cont ID  
Sent By pkrauss Date 2004-04-24 Time 07:00 Rev Time 2.15
Received By pkrauss Date 2004-04-24 Time 07:00 Sent To  
Notes
2004-04-24 00:00:00DENIED:
 RESPONSE #2
 DRYER DUCT TO PENETRATE AT PLENUM BOX
 CEILING DIFFUSER.PLEASE INDICATE THE
 HEIGHT OF THE CEILING DIFFUSER.PER
 2001 FBC(M) 504.4, EXHAUST TERMINATION
 SHALL BE NON-SCREENED WITH A BACKDRAFT
 DAMPER.PLEASE PROVIDE DETAIL OF DRYER
 TERMINATION.PROVIDE ADDITIONAL
 INFORMATION ON THE DRYER; (A) COMMERCIAL
 OR RESIDENTAL (B) DOES IT EXHAUST MORE
 THAN 200 CFM (C) DEVELOPED LENGTH
 EXCEEDS 25 FT.
  
 PROVISO:
 PLEASE NOTE, THE DIRECTIONAL BEARING ON
 THE A/C PLANS CONFLICT WITH THE
 ARCHITECTURAL PLANS.
  
 PLAN SHEET AC-4 POOL EQUIPMENT ROOM,
 10 FT SEPARATION REQUIRED BETWEEN THE
 EXHAUST & INTAKE LOUVER.
  
 PLEASE NOTE, PLANS INDICATE EXHAUST &
 FRESH AIR INTAKE TEMINATING IN THE
 CEILING OF THE VEHICULAR DRIVE THRU.
 EXHAUST SHALL TERMINATE AS TO NOT CREATE
 A NUISANCE (2001 FBC(M) 401.5.2).FRESH
 AIR INTAKES SHALL BE LOCATED AS TO NOT
 RECIRCULATE NOXIOUS CONTAMINANTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-02-20 Cont ID  
Sent By pkrauss Date 2004-02-20 Time 07:44 Rev Time 2.30
Received By pkrauss Date 2004-02-20 Time 06:31 Sent To  
Notes
2004-02-20 00:00:00DENIED:
 1.PLAN SHEET AC-2, FIRE DAMPERS ON
 THE SUPPLY DUCT TO AHU-1 & EF-5 ARE
 INDICATED IN THE MIDDLE OF THE CORRIDOR
 AND NOT IN THE RATED WALL.PLEASE
 RELOCATE.
  
 2.PLAN SHEET AC-2, EXHAUST FROM THE
 DRYER RUNS TO A PLENUM BOX.PLEASE
 CLARIFY TERMINATION OF EXHAUST.
  
 3.DUCTS PENETRATING ONE FLOOR SHALL
 BE PROTECTED BY A FIRE DAMPER AT FLOOR
 PENETRATION.DUCTS PENETRATING MORE
 THAN ONE FLOOR SHALL BE PROTECTED BY A
 SHAFT ENCLOSURE PER 2001 FBC(M) 607.4.
  
 4.AC-3 DUCTS PENETRATING RATED WALLS
 WITHOUT FIRE DAMPERS SHALL COMPLY WITH
 2001 FBC(M) 607.1.3 #3 ITEMS 1 THROUGH
 4. SOME DUCTS ARE LESS THAN 5 FT BEFORE
 AN OPENING.PLEASE CLARIFY.
  
 5.PLAN SHEET AC-6, EXHAUST RISERS
 APPEAR TO TERMINATE BELOW THE ROOF,
 PLEASE CLARIFY.PROVIDE DETAIL OF
 CAP/FAN FOR ROOF TERMINATION.
  
 6.PLEASE INDICATE WHAT WILL BE STORED
 IN THE POOL/SPA EQUIPMENT ROOM.
 PROVIDE INFORMATION AND AMOUNTS OF ANY
 CHEMICALS THAT MAY BE STORED IN THIS
 AREA.
  
 7.PLEASE PROVIDE COMBUSTION AIR
 CALCULATIONS FOR THE GAS WATER HEATERS.
 PROVIDE DETAIL FOR THE VENTING OF
 WATER HEATERS.
  
 8.PLAN SHEET A-102 INDICATES FUTURE
 KITCHEN/RESTAURANT, NO INDICATION OF
 WHERE THE EXHAUST FOR THE HOOD MIGHT
 TERMINATE.PLEASE NOTE, TERMINATION
 FOR GREASE DUCT SHALL COMPLY WITH 2001
 FBC(M) 506.3.14.3.EXHAUST SHALL NOT
 TERMINATE WHERE PROTECTED OPENINGS ARE
 REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-06-22 Cont ID  
Sent By kstevens Date 2004-06-22 Time 08:01 Rev Time 1.00
Received By kstevens Date 2004-06-21 Time 18:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-04-29 Cont ID  
Sent By kstevens Date 2004-04-29 Time 07:52 Rev Time 2.00
Received By kstevens Date 2004-04-28 Time 18:50 Sent To  
Notes
2004-04-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 A) FROM PREVIOUS REVIEW: COMMENT NUMBER
 SHALL REMAIN THE SAME TO AVOID CONFUSION
 2) SHOW COMPLIANCE WITH SECTION 11-9.1.2
 ACCESSIBLE UNITS, SLEEPING ROOMS, AND
 SUITES. - RESPONSE NOTED, BUT THE SHOWER
 SHOWN IN THESE THREE UNITS ARE NOT ROLL-
 IN SHOWERS. SEE ATTACHED SHEET, FIG. 57,
 SHOWING EXAMPLE OF ROLL-IN SHOWER.
 4) SHOW COMPLIANCE WITH SECTION 11-9.1.4
 CLASSED OF SLEEPING ACCOMMODATIONS. RE-
 SPONSE NOTED, PLEASE INDICATE TYPES OF
 SLEEPING ACCOMMODATION AVAILABLE TO CON-
 FIRM THAT ALL CLASSES ARE REPRESENTED.
 7) SHT P-1 CLEANOUTS REQUIRED NEAR JUNC-
 TION OF BLDG DRAIN AND BLDG SEWER. 2-WAY
 C/O'S MAY BE USED. 708.3.5 - RESPONSE
 NOTED, BUT CLEANOUTS ARE NOT SHOWN. ALSO
 SHOW CLEANOUTS MENTIONED ABOVE ON BLDG
 DRAIN ISOMETRIC SHEET P-8.
 8) SHT P-1 ALL UNITS, ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. KITCHEN SINK SHALL DISCHARGE
 DOWN-STREAM OF THE WET VENT. 909.1 -
 RESPONSE NOTED - PLEASE HAVE CHANGES
 REFLECTED ON THE SANITARY RISER DIAGRAM
 ALSO.
 18- F. DELIVERY PRESSURE NOT INDICATED
 ON PLANS. INDICATE THE DELIVERY PRESSURE
 (PSI) PER FBC-2001 FUEL GAS CODE SECTION
 402.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-02-02 Cont ID  
Sent By kstevens Date 2004-01-31 Time 15:46 Rev Time 5.00
Received By kstevens Date 2004-01-31 Time 15:43 Sent To  
Notes
2004-01-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
  
 1) SHT C-6 GREASE/WATER INTECEPTOR SHALL
 BE SIZED BY RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE MGR. PER WASTE ORD. #2938.
 PLEASE CONTACT MR. COMPO AT (561) 837-
 4074.
 2) SHOW COMPLIANCE WITH SECTION 11-9.1.2
 ACCESSIBLE UNITS, SLEEPING ROOMS, AND
 SUITES.
 3) SHOW COMPLIANCE WITH SECTION 11-9.1.3
 SLEEPING ACCOMMODATIONS FOR PERSONS WITH
 HEARING IMPAIRMENTS.
 4) SHOW COMPLIANCE WITH SECTION 11-9.1.4
 CLASSES OF SLEEPING ACCOMMODATIONS.
 5) SHOW COMPLIANCE WITH SECTION 11-9.2.3
 HOTEL, MOTEL AND CONDOMINIUM SPECIAL
 ACCESSIBILITY FEATURE.
 6) SHT P-1 MEN'S AND WOMEN'S RESTROOMS
 #'S 148 & 135, FLOOR DRAINS ARE NOT VEN-
 TED. CORRECT ON THE FLOOR PLAN AND SANT.
 RISER DIAGRAM. 901.2.1
 7) SHT P-1 CLEANOUTS REQUIRED NEAR JUNC-
 TION OF BLDG DRAIN AND BLDG SEWER. 2-WAY
 C/O'S MAY BE USED. 708.3.5
 8) SHT P-1 ALL UNITS, ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. KITCHEN SINK SHALL DISCHARGE
 DOWN-STREAM OF THE WET VENT. 909.1
 9) SHT P-1 IDENTIFY SANITARY LINE AND
 STACK LOCATED IN WALL BETWEEN BDRM 130
 AND CORRIDOR. IDENTIFY STACK.
 10) SHT P-1 GAS PIPE DROPING DOWN FROM
 SHT P-2 BY STAIRWAY #1 NOT SHOWN ON P-1
 SHEET. PLEASE CLAIRFY. 104.2.1
 11) SHT P-6 TABLE 906.1 MAXIMUM DISTANCE
 FROM TRAP TO VENT IS 10 FEET. FLOOR
 DRAIN IN MECH. ROOM BACK TO VENT SEEMS
 TO EXCEED THIS DISTANCE.
 12) SHT P-7 SANT. RISER S/8 SHOWS FLOOR
 SINKS ON 2ND, 3RD, 4TH, & 5TH FLOORS.
 SHT P-2 SHOWS S/8 UP TO MEZZ. FLOOR AT
 COL. LINE "D" BETWEEN LAUNDRY & ELECTRIC
 ROOM BUT NOT SHOWN ABOVE ON SHTS P-3, P-
 4, OR P-5, NOR DOES IT SHOW FLOOR SINKS
 ON ANY OF THESE FLOORS. SHT P-8 SHOWS
 S/8 PICKING UP A WASH MACHINE AND THEN
 VENTING THRU THE ROOF. PLEASE CLAIRFY.
 104.2.1
 13) A FLOOR DRAIN IS REQUIRED IN THE
 LAUNDRY PER SECTION 412.4.
 14) SHT P-7 WATER ISOMETRICS ALL UNITS.
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 FROM RISERS. 604.9 - WATER HAMMER ARREST
 ORS ARE REQUIRED AT THE WASH MACHINES,
 DISHWASHERS, AND ICE MAKERS, AND SHALL
 BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING PER
 PDI-WH 201 AND MANUF. INSTALLATION IN-
 STRUCTIONS.
 15) SHT P-9 WATER PIPING DRISTRIBUTION
 ISOMETRIC, ICE MACHINE RISER. WATER
 HAMMER ARRESTORS ARE REQUIRED AT EACH
 WASH MACHINE PER 604.9. WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIX-
 TURE IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING. PDI-WH 201 AND MANUF. INSTALL.
 INSTRUCTIONS.
 16) P-10 STORM WATER RISER DIAGRAM, THE
 HORIZONTAL PIPE SIZE IS NOT CORRECT
 WHERE 4"SD (2060 SF) & 4"SD (2160 SF)
 MAXIMUM 1600 SF FOR 4" PIPE @ 1/8" PER
 FOOT. SIZE ALL HORIZONTAL PIPE SECTIONS.
 17) SHT P-12 ALL PUMPS SHALL BE LISTED
 BY AN APPROVED TESTING AGENCY. SUBMIT
 MANUF. SPECS SHEETS. 303.4
 18) SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION REQUIRED:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 SHOW VENTING IF DIRECT VENT.
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2004-07-23 Cont ID  
Sent By agiannio Date 2004-07-23 Time 11:27 Rev Time 0.00
Received By agiannio Date 2004-07-23 Time 11:27 Sent To  
Notes
2004-07-23 00:00:00PROVISO:
 1)ROOF TERRACE.AREA OF LANDSCAPING
 MEETS CODE; DETAILED PLANS REQUIRED FOR
 APPROVAL BEFORE CO IS ISSUED.
 2) PARKING.PARKING CONTRACT MUST BE
 APPROVED BEFORE FINAL CO PURSUANT TO
 DAC APPROVAL

Review Stop Z ZONING
Rev No 3 Status F Date 2004-06-21 Cont ID  
Sent By aaponte Date 2004-06-21 Time 14:29 Rev Time 0.00
Received By aaponte Date 2004-06-21 Time 14:29 Sent To  
Notes
2004-06-21 00:00:00ARTICLE IV SEC 94-107 (C)(5)(E) REQUIRES
 LANDSCAPE ON THE ROOFTOP TERRACE AREA.
 PLEASE SUBMIT INFORMATION THAT
 DEMONSTRATES COMPLIANCE WITH THIS
 REQUIREMENT.
 ARTICLE IV SEC 94-107 (G)(3) STATES THAT
 TREES SHALL NOT BE LESS THAN 14 FEET IN
 HEIGHT WITH A SPREAD OF NO LESS THAN 6
 FEET.
 PLEASE PROVIDE INFORMATION THAT CONFIRMS
 YOUR COMPLIANCE WITH THE PARKING
 REQUIREMENTS PURSUANT TO DAC
 APPROVAL.

Review Stop Z ZONING
Rev No 2 Status F Date 2004-04-22 Cont ID  
Sent By aaponte Date 2004-04-22 Time 14:05 Rev Time 0.50
Received By aaponte Date 2004-04-22 Time 14:05 Sent To  
Notes
2004-04-22 00:00:001. ARTICLE IV SECTION 94-107(C)(5)(E)
 REQUIRES LANDSCAPE ON THE ROOFTOP
 TERRACE AREA. PLEASE SUBMIT INFORMATION
 THAT DEMONSTRATES COMPLIANCE WITH THIS
 REQUIREMENT.
 2. ARTICLE IV SECTION 94-107(C)(5)(G)(1)
 REQUIRES A MINIMUM FIVE-FOOT WIDE
 WALKWAY SURROUNDING THE POOL.
 3. ARTICLE IV SECTION 94-107(G)(2), (3)
 AND (4) REQUIRE STREET TREES AND
 LANDSCAPE UNITS IN THE PUBLIC RIGHT OF
 WAY. PLEASE DEMONSTRATE COMPLIANCE WITH
 THESE REQUIREMENT.
 4. MEZZANINE LEVEL ABOVE KITCHEN IS LIMI
 TED TO MECHANICAL SPACE. EQUIPMENT ROOMS
 ARE PERMITTED, HOWEVER LAUNDRY ROOM MUST
 BE RELOCATED.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-01-21 Cont ID  
Sent By csiegber Date 2003-12-30 Time 11:43 Rev Time 2.00
Received By agiannio Date 2004-01-21 Time 14:29 Sent To  
Notes
2004-01-21 00:00:00ARTICLE IV SECTION 94-107(B)(4) REQUIRES
 GARDEN WALLS AND FENCES NOT FACING THE
 STREET TO BE A MAXIMUM OF 72 INCHES IN H
 EIGHT. GARDEN WALLS DEPICTED ON THE DRAW
 INGS ARE 9'9" TALL AND EXCEED THE MAXIMU
 M HEIGHT PERMITTED.
 ARTICLE IV SECTION 94-107(C)(5)(E) REQUI
 RES LANDSCAPE ON THE ROOFTOP TERRACE ARE
 A. PLEASE SUBMIT INFORMATION THAT DEMONS
 TRATES COMPLIANCE WITH THIS REQUIREMENT.
 ARTICLE IV SECTION 94-107(G)(2), (3) AND
 (4) REQUIRE STREET TREES AND LANDSCAPE
 UNITS IN THE PUBLIC RIGHT OF WAY. PLEASE
 DEMONSTRATE COMPLIANCE WITH THESE REQUI
 REMENTS.