Plan Review Details - Permit 03121563
Plan Review Stops For Permit 03121563
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-22 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:28 Rev Time 1.00
Received By jgomez Date 2004-01-22 Time 15:49 Sent To M
Notes
2004-01-22 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR WINDOWS, DOORS,
 MULLIONS, GLASS BLOCK, ROOF TILE AND
 STRUCTURAL CONNECTORS.
 2-REVISE DETAIL E/4. 3" TAPCON DOESN'T
 PROVIDE THE 2" MIN. PENETRATION.
 3-PROVIDE ENGINEERING CALCS FOR ANCHOR
 FASTENERS DIFFEENT THAN THOSE TESTED
 AND PUBLISHED BY USP TO COMPLY WITH
 SEC. 1609.4.3 FBC 2001 REGARDING THE
 STEEEL STRESS INCREASE.
 4-REVISE DETAIL A/4. WHERE ARE TABLES 6
 AND 8 TAKEN FROM? SEE FBC 2001 AND
 ASCE 7-98.
 5-SHEET #7: A)REVISE DESIGN PRESSURES
 FOR EXTEIOR OPENINGS. SEE TABLES
 1606.2B AND 1606.2E FBC 2001.
 B)DESIGN PRESSURES SHOWN ON THIS SHEET
 DON'T MATCH THOSE SHOWN ON SHEET 3.
 C)REVISE REAR PORCH FLOOR PLAN AND ROOF
 PLAN NOTES REGARDING WOOD BEAM,. SINCE
 IT WAS CHANGED TO CONCRETE BEAM.
 D)WINDOWS SHOWN ON EXTERIOR ELEVATION
 DON'T MATCH WINDOW SCHEDULE. REVISE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-12 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:41 Rev Time 2.00
Received By jgomez Date 2004-01-12 Time 09:19 Sent To PC
Notes
2004-01-12 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-STORM SHUTTERS: REVISE KEY PLAN AND
 INSTALLATION SCHEUDLE TO MATCH PLANS.
 NEED EMERGENCY EGRESS THAT COMPLIES
 WITH SEC. 1005.4.5 FBC 2001.
 B)CLEARLY INDICATE ANCHOR TYPE & SPACING
 TO BE USED ACCORDING TO EDGE DISTANCE
 PANEL SPAN, CONNECTION TYPE, DESIGN
 PRESSURES & STRUCTURE TO BE ATTACHED
 TO (MASONRY OR CONCRETE).
 3-PROVIDE FLORIDA PRODUCT APPROVAL FOR:
 A)HORIZONTAL SLIDER WINDOW. NEED THE
 APPROVED DRAWINGS.
 B)GLASS BLOCK.
 C)ROOF TILE (FBC APPROVAL IS PENDING).
 D)SINGLE HUNG WINDOWS.
 E)ENTRY DOOR WITH SIDELITE ASSEMBLY.
 F)SLIDING GLASS DOORS.
 G)WINDOW MULLIONS.
 H)TRUSS CONNECTORS.
  
 4-ARCHITECT TO HAVE ALL HIS INFORMATION
 ON TITLE BLOCK AND SIGN AND DATE DWGS
 AS REQ'D BY CHAPTER 481 FL STATUTES.
 SEE 61G1-16004 F.A.C.
 5- 1HR FIRE RATED GLASS BLOCK ASSEMBLY
 NEED SPECIFIC UL LISTED ASSEMBLY AND
 REVISE DETAIL TO SHOW ALL COMPONENTS
 SPECIFIED ON THE UL ASSEMBLY. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 6-CLARIFY GARAGE DOOR BUCK SPECS.DETAIL
 E/4 AND NOTES ON DWG #2 DON'T MATCH.
 CHECK SIZE OF FASTENER TO ALLOW 2"
 EMBEDMENT. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 7-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC 2001.
 B)PROVIDE SPECIFIC SIZE OF USP RT
 CONNECTOR TO BE USED. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 8-ENGINEER TO SPECIFY ROOF TILE FASTENER
 AS REQ'D BY SEC. 104.2.1.1 OF CITY
 AMENDMENTS TO FBC 2001
 9-REVISE WINDOW BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 10-SHEET #7: A)CLARIFY WHERE IS USP
 EHUH 28-3 TAKEN FROM? UNABLE TO FIND
 IN 2003 CATALOGUE. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 B)MISSING SPECS FOR CONNECTOR AT ONE END
 OF GIRDER TRUSS AT REAR PORCH. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 C)REAR ELEVATION: CLARIFY CALCULATED
 PRESSURES FOR OPENINGS. WHY SAME
 PRESSURES FOR DIFFERENT OPENING SIZE
 AND LOCATION. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 **CLEARLY INDICATE TYPE OF WINDOW. DWG
 SHOW FIXED WINDOWS WHICH DOESN'T MATCH
 WINDOW SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-06 Cont ID  
Sent By jleech Date 2004-01-03 Time 10:19 Rev Time 0.33
Received By dpalmer Date 2004-01-06 Time 07:48 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:28 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 12:28 Sent To B
Notes
2004-02-27 00:00:00TO JG DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 16:03 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 16:03 Sent To B
Notes
2004-02-11 00:00:00TO JG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-16 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:41 Rev Time 0.00
Received By csiegber Date 2004-01-16 Time 16:41 Sent To B
Notes
2004-01-16 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-12 Cont ID  
Sent By mmclean Date 2004-01-12 Time 10:02 Rev Time 0.00
Received By jgomez Date 2003-12-24 Time 13:22 Sent To PC
Notes
2003-12-29 00:00:0012/24/03 TO Z
 12/29/03 TO E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-22 Cont ID  
Sent By pkrauss Date 2004-01-22 Time 16:24 Rev Time 0.25
Received By pkrauss Date 2004-01-22 Time 16:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-06 Cont ID  
Sent By jgomez Date 2004-01-22 Time 15:49 Rev Time 0.33
Received By pkrauss Date 2004-01-06 Time 12:53 Sent To B
Notes
2004-01-06 00:00:00DENIED:
 RETURN AIR JUMPER FROM THE MASTER
 BEDROOM IS NOT SIZED PROPERLY.ALL AIR
 TO THE MASTER SUITE IS TO INCLUDED IN
 CALCULATION FOR TOTAL SUPPLY AIR.
 RETURN AIR SHALL BE SIZED ACCORDING TO
 THE TOTAL OF SUPPLY AIR.PLEASE REVISE
 PLANS ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-03 Cont ID  
Sent By jleech Date 2004-01-03 Time 10:19 Rev Time 0.25
Received By jleech Date 2004-01-03 Time 10:19 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-01-06 Cont ID  
Sent By mmclean Date 2004-01-06 Time 11:51 Rev Time 0.00
Received By mmclean Date 2004-01-06 Time 11:51 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-12-24 Cont ID  
Sent By dpalmer Date 2004-01-06 Time 07:48 Rev Time 0.00
Received By mmclean Date 2003-12-24 Time 14:53 Sent To I
Notes
2003-12-24 00:00:00DENIED, NEED TO MEET FRONT SETBACK FOR
 FRONT LOAD GARAGE OF 20FT CALLED CONTR
 LEFT MSG