Plan Review Details - Permit 03121526
Plan Review Stops For Permit 03121526
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-02-20 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:07 Rev Time 0.50
Received By jgomez Date 2004-02-20 Time 12:16 Sent To PC
Notes
2004-02-20 00:00:00SUBMITTAL IN RESPONSE TO PROVISO DATED
 1-16-04.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-20 Cont ID  
Sent By csiegber Date 2004-02-11 Time 15:58 Rev Time 2.00
Received By jgomez Date 2004-01-16 Time 16:50 Sent To M
Notes
2004-01-16 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR: ALL DOOR/WINDOW
 TYPES, GLASS BLOCK, MULLIONS, ROOF
 TILE AND STRUCTURAL CONNECTORS.
 2-DETAIL E/4: REVISE FASTENER SIZE TO
 ACHIEVE 2" MIN. EMBEDMENT. ALSO,REVISE
 NOTES ON DWG #2 TO BE CONSISTENT. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 3-PROVIDE ENGINEERING CALCULATIONS FOR
 FASTENERS SPECIFIED ON TRUSS ANCHOR
 SCHEDULE TO SHOW COMPLIANCE WITH SEC.
 1609.4.3 FBC 2001 WHICH DOESN'T ALLOW
 STEEL STRESS TO BE INCREASED.
 4-DETAIL A/4: ROOF TILE FASTENERS NOTES
 REFER TO TABLES 6 AND 8. CLARIFY WHERE
 ARE THESE TABLES COMING FROM? SEE FBC
 2001 OR ASCE 7-98.
 5-SHEET A-7: A)REVISE DESIGN PRESSURES
 AT EXTEIOR OPENINGS. SEE TABLES
 1606.2B AND 1606.2E FBC 2001. PROVIDE
 ENGINEERING CALCS FOR DIFFERENT DESIGN
 PRESSURES. SECTION 104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001.
 B)DESIGN PRESSURES SHOWN ON SHEET 3B AND
 SHEET 7 DON'T MATCH. REVISE AS REQ'D.
 C)REVISE REAR PORCH FLOOR PLAN AND ROOF
 FRAMING PLAN NOTES AND TRUSS ANCHOR TO
 MATCH. NOTE THAT BEAM WAS CHANGED FROM
 GIRDER TRUSS TO CONCRETE BEAM. REVISE
 TRUSS CONNECTOR ACCORDINGLY. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 D)WNDOWS SHOWN ON ELEVATION DON'T MATCH
 THOSE SPECIFIED ON WINDOW SCHEDULE.
 REVISE AS REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-13 Cont ID  
Sent By pkrauss Date 2004-01-06 Time 13:37 Rev Time 2.00
Received By jgomez Date 2004-01-13 Time 09:25 Sent To PC
Notes
2004-01-13 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR: A)SLIDER WINDOW
 B)GLASS BLOCK. C)ROOF TILE. D)SINGLE
 HUNG WINDOWS. E)ENTRY DOOR WITH SIDE-
 LITE. F)SLIDING GLASS DOORS. G)WINDOW
 MULLIONS. H)TRUSS CONNECTORS.
 3-ARCHITECT TO PROVIDE ALL REQUIREMENTS
 OF CHAPTER 481 FLORIDA STATUTES WHEN
 SUBMITTING DWGS FOR PUBLIC RECORDS.
 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY AND
 REVISE DETAIL SHOWING ALL COMPONENTS
 FOR SUCH ASSEMBLY. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 5-GARAGE BUCK DETAIL E/4 & NOTES ON DWG
 #2 DON'T MATCH. CHECK FASTENER SIZE.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC REGARDING STEEL STRESS.
 B)SPECIFY SIZE OF USP RT STRAPS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENER. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-SHEET #7: A)CLARIFY WHERE IS USP EHUH
 28-3 CONNECTOR TAKEN FROM?. UNABLE TO
 FIND IT IN 2003 USP CATALOGUE.SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)MISSING ONE CONNECTOR AT GIRDER TRUSS
 IN REAR PORCH. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 C)CLARIFY DESIGN PRESSURES CALCULATED.
 WHY SAME PRESSURES FOR DIFFERENT SIZE
 AND LOCATION OF OPENING. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 D)WINDOWS SHOWN ON REAR ELEVATION DON'T
 MATCH WINDOW SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-06 Cont ID  
Sent By jleech Date 2004-01-03 Time 11:21 Rev Time 0.33
Received By dpalmer Date 2004-01-06 Time 06:42 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:07 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 12:07 Sent To B
Notes
2004-02-27 00:00:00TO JG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 15:58 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 15:58 Sent To B
Notes
2004-02-11 00:00:00TO JG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-13 Cont ID  
Sent By mmclean Date 2004-01-13 Time 09:43 Rev Time 0.00
Received By jgomez Date 2003-12-24 Time 13:21 Sent To PC
Notes
2003-12-29 00:00:0012/24/03 TO Z
 12/29/03 TO E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-23 Cont ID  
Sent By pkrauss Date 2004-01-23 Time 12:03 Rev Time 0.25
Received By pkrauss Date 2004-01-23 Time 12:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-06 Cont ID  
Sent By jgomez Date 2004-01-20 Time 08:28 Rev Time 0.33
Received By pkrauss Date 2004-01-06 Time 13:36 Sent To B
Notes
2004-01-06 00:00:00DENIED:
 RETURN AIR JUMPER FROM THE MASTER
 BEDROOM IS NOT SIZED PROPERLY.ALL AIR
 TO THE MASTER SUITE IS TO BE INCLUDED
 IN THE CALCULATION FOR TOTAL SUPPLY
 AIR.RETURN AIR SHALL BE SIZED
 ACCORDING TO THE TOTAL OF SUPPLY AIR.
 PLEASE REVISE PLANS ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-03 Cont ID  
Sent By jleech Date 2004-01-03 Time 11:21 Rev Time 0.25
Received By jleech Date 2004-01-03 Time 11:21 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-01-06 Cont ID  
Sent By mmclean Date 2004-01-06 Time 12:00 Rev Time 0.00
Received By mmclean Date 2004-01-06 Time 12:00 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-12-24 Cont ID  
Sent By dpalmer Date 2004-01-06 Time 06:43 Rev Time 0.00
Received By mmclean Date 2003-12-24 Time 15:03 Sent To I
Notes
2003-12-24 00:00:00DENIED, NEED TO MEET FRONT SETBACK FOR
 FRONT LOAD GARAGE OF 20FT CALLED CONTR
 LEFT MSG