Plan Review Details - Permit 03121519
Plan Review Stops For Permit 03121519
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-21 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:06 Rev Time 1.00
Received By jgomez Date 2004-01-21 Time 08:18 Sent To M
Notes
2004-01-21 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR ALL DOORS,WINDOWS
 GLASS BLOCK, ROOF TILE, MULLIONS AND
 STRUCTURAL CONNECTORS.
 2-REVISE DETAIL E/4. FASTENER SPECIFIED
 DOESN'T PROVIDE THE 2" MIN. EMBEDMENT.
 3-PROVIDE ENGINEERING CALCULATIONS FOR
 TRUSS ANCHOR FASTENERS THAT DIFFER
 FROM THOSE TESTED & PUBLISHED BY USP
 TO COMPLY WITH SEC. 1609.4.3 FBC 2001
 REGARDING THE STEEL STRESS.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 4-DETAIL A/4: ROOF TILE FASTENERS NOTE
 TABLES 6 AND 8. WHERE ARE THESE TABLES
 TAKEN FROM? WE USE FBC 2001 AND ASCE
 7-98. SEC. 104.2.1.2 CITY AMENDMENTS.
 5-SHEET #7: A)REVISE DESIGN PRESSURES.
 SEE TABLES 1606.2B & 1606.2E FBC 2001.
 B)DESIGN PRESSURES SHOWN DON'T MATCH
 DESIGN PRESSURES SHOWN ON SHEET 3.
 C)REVISE REAR PORCH FLOOR PLAN AND ROOF
 PLAN NOTES TO REFLECT CHANGE OF WOOD
 BEAM TO CONCRETE BEAM. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 D)WINDOWS SHOWN ON EXTERIOR ELEVATION
 DON'T MATCH WINDOW SCHEDULE. REVISE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-12 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:53 Rev Time 2.00
Received By jgomez Date 2004-01-12 Time 13:42 Sent To PC
Notes
2004-01-12 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR: A)SLIDER WINDOW
 B)GLASS BLOCK. C)ROOF TILE. D)SINGLE
 HUNG WINDOWS. E)ENTRY DOOR WITH SIDE-
 LITE ASSEMBLY. F)SLIDING GLASS DOORS.
 G)WINDOW MULLIONS. H)TRUSS CONNECTORS.
 3-ARCHITECT TO HAVE ALL HIS INFORMATION
 ON TITLE BLOCK AS REQUIRED BY CHAPTER
 481 FLORIDA STATUTES.
 4- 1HR FIRE RATED GLASS BLOCK ASSEMBLY
 NEED SPECIFIC UL LISTED ASSEMBLY AND
 REVISE DETAIL TO INCLUDE ALL REQUIRED
 COMPONENTS ON LISTED ASSEMBLY. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-CLARIFY GARAGE DOOR BUCK SPECS. DETAIL
 E/4 AND NOTES ON DWG #2 DON'T MATCH.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC/01 REGARDING STEEL STRESS
 B)SPECIFY SIZES FOR USP RT CONNECTORS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENER AS REQ'D BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-SHEET #7: A)CLARIFY WHER IS USP EHUH
 28-3 TAKEN FROM?. UNABLE TO FIND ON
 USP 2003 CATALOGUE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 B)MISSING CONNECTOR FOR REAR PORCH
 GIRDER. SEC. 104.2.1.2 CITY AMENDMENTS
 C)CLARIFY CALCULATED DESIGN PRESSURES.
 WHY SAME PRESSURES FOR DIFFERENT SIZE
 AND LOCATION OF OPENINGS?. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 D)SHOW TYPE OF WINDOWS ON REAR ELEVATION
 SEE WINDOW SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-06 Cont ID  
Sent By jleech Date 2004-01-03 Time 11:17 Rev Time 0.33
Received By dpalmer Date 2004-01-06 Time 06:48 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:06 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 12:06 Sent To B
Notes
2004-02-27 00:00:00TO JG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 15:59 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 15:59 Sent To B
Notes
2004-02-11 00:00:00TO JG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-16 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:53 Rev Time 0.00
Received By csiegber Date 2004-01-16 Time 16:53 Sent To B
Notes
2004-01-16 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-12 Cont ID  
Sent By mmclean Date 2004-01-12 Time 15:05 Rev Time 0.00
Received By jgomez Date 2003-12-24 Time 13:20 Sent To PC
Notes
2003-12-29 00:00:0012/24/03 TO Z
 12/29/03 TO E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-22 Cont ID  
Sent By pkrauss Date 2004-01-22 Time 13:29 Rev Time 0.25
Received By pkrauss Date 2004-01-22 Time 13:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-06 Cont ID  
Sent By jgomez Date 2004-01-21 Time 08:18 Rev Time 0.33
Received By pkrauss Date 2004-01-06 Time 13:15 Sent To B
Notes
2004-01-06 00:00:00DENIED:
 RETURN AIR JUMPER FROM THE MASTER
 BEDROOM IS NOT SIZED PORPERLY.ALL AIR
 TO THE MASTER SUITE IS TO BE INCLUDED
 IN THE CALCULATION FOR TOTAL SUPPLY
 AIR.RETURN AIR SHALL BE SIZED
 ACCORDING TO THE TOTAL OF SUPPLY AIR.
 PLEASE REVISE PLANS ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-03 Cont ID  
Sent By jleech Date 2004-01-03 Time 11:17 Rev Time 0.25
Received By jleech Date 2004-01-03 Time 11:17 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-01-06 Cont ID  
Sent By mmclean Date 2004-01-06 Time 11:55 Rev Time 0.00
Received By mmclean Date 2004-01-06 Time 11:55 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-12-24 Cont ID  
Sent By dpalmer Date 2004-01-06 Time 06:48 Rev Time 0.00
Received By mmclean Date 2003-12-24 Time 14:55 Sent To I
Notes
2003-12-24 00:00:00DENIED, NEED TO MEET FRONT SETBACK FOR
 FRONT LOAD GARAGE OF 20FT CALLED CONTR
 LEFT MSG