Plan Review Details - Permit 03121516
Plan Review Stops For Permit 03121516
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-06-23 Cont ID  
Sent By jgomez Date 2004-06-23 Time 09:03 Rev Time 0.50
Received By jgomez Date 2004-06-23 Time 09:03 Sent To PC
Notes
2004-06-23 00:00:00PRODUCT APPROVAL SUBMITTAL CHECKLIST:
 1-PROVIDE COPIES OF THE GARAGE DOOR
 DRAWINGS SUBMITTED TO SBCCI FOR
 APPROVAL. NEED DRAWINGS THAT WERE
 SIGNED AND SEALED ON THE DATE NOTED
 ON SBCCI EVALUATION REPORT.
 2-PROVIDE FLORIDA PRODUCT APPROVAL COVER
 PAGE FOR SPECIFIC ENTRY DOOR TO BE
 USED AND MATCHES DADE COUNTY NOA.
 BENCHMARK AND THERMA-TRU ARE TWO
 DIFFERENT MODELS.
 3-SIMONTON WINDOWS/DOORS PACKAGE IS
 INCOMPLETE. MISSING FLORIDA PRODUCT
 APPROVAL COVER PAGE FOR FIXED WINDOWS
 AND SLIDING GLASS DOORS USED.
 4-PROVIDE ALL INFORMATION REQUESTED ON
 PROVISO DATED 1-21-04. SEE ATTACHED
 COPY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-21 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:23 Rev Time 1.00
Received By jgomez Date 2004-01-21 Time 17:42 Sent To M
Notes
2004-01-21 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR ALL DOORS,WINDOWS
 GLASS BLOCK, MULLIONS, ROOF TILE AND
 STRUCTURAL CONNECTORS.
 2-REVISE DETAIL E/4. FASTENER SPECIFIED
 DOESN'T PROVIDE THE 2" MIN. EMBEDMENT.
 3-PROVIDE ENGINEERING CALCULATIONS FOR
 TRUSS FASTENERS THAT ARE DIFFERENT
 FROM THOSE TESTED AND PUBLISHED BY
 USP TO COMPLY WITH SECTION 1609.4.3
 FBC 2001.
 4-REVISE DETAIL A/4. WHERE ARE TABLES 6
 AND 8 CITED FROM?. SEE ASCE 7-98 OR
 FBC 2001.
 5-SHEET #7: A)REVISE DESIGN PRESSURES.
 SEE TABLES 1606.2B AND 1606.2E FBC.
 B)DESIGN PRESSURES SHOWN DON'T MATCH
 THOSE SHOWN ON SHEET 3.
 C)REVISE REAR PORCH FLOOR PLAN AND ROOF
 PLAN NOTES REGARDING WOOD BEAM SINCE
 IT WAS CHANGED TO CONCRETE BEAM.
 D)WINDOWS SHOWN ON EXTERIOR ELEVATION
 DON'T MATCH WINDOW SCHEDULE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-13 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:43 Rev Time 2.00
Received By jgomez Date 2004-01-13 Time 12:17 Sent To PC
Notes
2004-01-13 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR: A)SLIDER WINDOW.
 B)GLASS BLOCK. C)ROOF TILE. D)SINGLE
 HUNG WINDOWS. E)ENTRY DOOR WITH SIDE-
 LITE. F)SLIDING GLASS DOORS. G)WINDOW
 MULLIONS. H)TRUSS CONNECTORS.
 3-ARCHITECT TO PROVIDE ALL REQUIREMENTS
 OF CHAPTER 481 FLORIDA STATUTES WHEN
 SUBMITTING DWGS FOR PUBLIC RECORDS.
 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY AND
 REVISE DETAIL SHOWING ALL REQUIRED
 COMPONENTS OF THE LISTED ASSEMBLY.
 5-GARAGE BUCK DETAIL E/4 & NOTES ON DWG
 #2 DON'T MATCH. CHECK FASTENER SIZE.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC REGARDING STEEL STRESS.
 B)SPECIFY SIZE OF USP RT STRAPS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENER. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-SHEET #7: A)CLARIFY WHERE IS USP EHUH
 28-3 CONNECTOR TAKEN FROM?. UNABLE TO
 FIND IT IN 2003 USP CATALOGUE.SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)MISSING ONE CONNECTOR AT GIRDER TRUSS
 IN REAR PORCH. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 C)CLARIFY CALCULATED DESIGN PRESSURES
 AT OPENINGS. WHY SAME PRESSURES FOR
 DIFFERENT OPENING SIZE AND LOCATION.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 D)WINDOWS SHOWN ON REAR ELEVATION DON'T
 MATCH WINDOW SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-06 Cont ID  
Sent By jleech Date 2004-01-03 Time 11:14 Rev Time 0.33
Received By dpalmer Date 2004-01-06 Time 06:55 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:23 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 12:23 Sent To B
Notes
2004-02-27 00:00:00TO JG DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-16 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:43 Rev Time 0.00
Received By csiegber Date 2004-01-16 Time 16:43 Sent To B
Notes
2004-01-16 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-13 Cont ID  
Sent By mmclean Date 2004-01-13 Time 14:34 Rev Time 0.00
Received By jgomez Date 2003-12-24 Time 13:19 Sent To PC
Notes
2003-12-29 00:00:0012/24/03 TO Z
 12/29/03 TO E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-22 Cont ID  
Sent By pkrauss Date 2004-01-22 Time 12:59 Rev Time 0.25
Received By pkrauss Date 2004-01-22 Time 12:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-06 Cont ID  
Sent By jgomez Date 2004-01-21 Time 17:43 Rev Time 0.33
Received By pkrauss Date 2004-01-06 Time 13:27 Sent To B
Notes
2004-01-06 00:00:00DENIED:
 RETURN AIR JUMPER FROM THE MASTER
 BEDROOM IS NOT SIZED PROPERLY.ALL AIR
 TO THE MASTER SUITE IS TO BE INCLUDED
 IN THE CALCULATION FOR TOTAL SUPPLY
 AIR. RETURN AIR SHALL BE SIZED
 ACCORDING TO THE TOTAL OF SUPPLY AIR.
 PLEASE REVISE PLANS ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-03 Cont ID  
Sent By jleech Date 2004-01-03 Time 11:14 Rev Time 0.25
Received By jleech Date 2004-01-03 Time 11:14 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-01-06 Cont ID  
Sent By mmclean Date 2004-01-06 Time 11:58 Rev Time 0.00
Received By mmclean Date 2004-01-06 Time 11:58 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-12-24 Cont ID  
Sent By dpalmer Date 2004-01-06 Time 06:57 Rev Time 0.00
Received By mmclean Date 2003-12-24 Time 15:14 Sent To I
Notes
2003-12-24 00:00:00DENIED, MUST MEET FRONT SETBACK FOR
 FRONT LOAD GARAGE OF 20FT CALLED CONTR
 LEFT MSG