Plan Review Details - Permit 03121505
Plan Review Stops For Permit 03121505
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-06-22 Cont ID  
Sent By alange Date 2004-06-22 Time 10:33 Rev Time 1.00
Received By alange Date 2004-06-22 Time 10:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-04-08 Cont ID  
Sent By pkrauss Date 2004-06-22 Time 09:58 Rev Time 1.00
Received By alange Date 2004-04-08 Time 13:28 Sent To  
Notes
2004-04-08 00:00:00DENIED
 1.PRODUCT APPROVAL FOR SUN-TEK MFG.
 NOT APPROVED ON THE DCA BUILDING CODE
 INFORMATION SYSTEM PRODUCT APPROVAL SITE
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2.PLEASE SIGN BOTH COPIES OF ENERGY
 CALC'S.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-27 Cont ID  
Sent By hmoser Date 2004-01-14 Time 10:42 Rev Time 2.00
Received By alange Date 2004-01-27 Time 09:43 Sent To  
Notes
2004-01-27 00:00:00UNSAT
 1.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 2. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
 3.FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:ALL PRODUCT APPROVALS ARE
 MISSING.
 4.PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL
 J)AS REQUIRED BY THE 2001 FLORIDA
 ENERGYEFFICIENTCY CODE FOR BUILDING
 CONSTRUC- TION.
 5.SUBMIT WINDOW PRESSURES.
 6.SUBMIT A DETAIL FOR STONE VEENER
 ATTACHMENT METHODS.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-07-14 Cont ID  
Sent By btrobaug Date 2005-07-14 Time 09:14 Rev Time 0.50
Received By btrobaug Date 2005-07-14 Time 06:54 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-06 Cont ID  
Sent By btrobaug Date 2004-04-06 Time 16:19 Rev Time 0.75
Received By btrobaug Date 2004-04-06 Time 13:29 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-06 Cont ID  
Sent By kstevens Date 2004-04-02 Time 18:39 Rev Time 0.75
Received By dpalmer Date 2004-01-06 Time 13:13 Sent To P
Notes
2004-01-06 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE LIST AND SHOW ALL MIN
 CIRCUITING REQ'D ON PANEL SCHEDULE FOR
 NEW WORK. 210.12/ 210.11C3,
  
 2)NOTE: PLEASE CLARIFY IF BATH ROOM
 DOORS ARE MISSING FROM BEDROOM #2 AND
 FROM MASTER BEDROOM?
  
 3)NOTE: PLEASE SEE FBC CHAPTER 34, FOR
 ADDTIONS TO EXISTING BLDGS. PLEASE
 SHOW EXISTING ELECTRICAL THAT MEETS
 CODE OR THAT WILL BE REQ'D TO BE BROUGHT
 UP TO CODE.
  
 4)NOTE: PLEASE SEE NOTE ON RISER DIAGRAM
 , MENTIONS,,,IF BRKR DOES NOT FIT,
 PROVIDE DOUBLE LUG METER. PLEASE SEE
 230.72 FOR GROUPING OF MAINS ETC.
 PLEASE ALSO VERIFY THIS INFOMATION AT
 THIS TIME AND HAVE RISER DIAGRAM
 REFLECT CODE COMPLIANCE AND WHICH PATH
 WILL BE TAKEN.
 PLEASE ALSO SEE THAT RISER DIAGRAM SHOWS
 FPL SEC'S GOING INTO MAIN PANEL AND
 THEN OUT TO METER AND BACK TO MAIN
 PANEL. PLEASE SEE NEC. LINE AND LOAD IN
 PANEL IS NOT PERMITTED.
  
 5)NOTE: PLEASE SHOW LOCATION OF NEW
 PANEL.
  
 6)NOTE: PLEASE ALSO SHOW LOCATION OF
 NEW AHU. PANEL SCHEDUL SHOWS NEW CU, BUT
 NOT AHU????
  
 7)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANELS. 100A PANEL IS SHOWN AS MLO,
 AND PANEL SHOWS 100A MCB.
  
 8)NOTE: PLEASE SEE LOAD CALCULATIONS,
 SHOWS , SHOWS ADDITION BEING 1070 SQ FT
 AND YET TOTAL ON LOAD CALCS SHOWS SQ FT
 AT 1100 TOTAL??????
  
 PLEASE SUBMIT THE ABOVE INFORMATION AND
 PLEASE CORRELATE TO 2002 NEC. IF THERE
 ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-30 Cont ID  
Sent By adarroug Date 2005-06-30 Time 08:09 Rev Time 0.00
Received By adarroug Date 2005-06-30 Time 08:09 Sent To E
Notes
2005-06-30 00:00:00TO "BTROBAUG" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-15 Cont ID  
Sent By csiegber Date 2004-06-15 Time 14:33 Rev Time 0.00
Received By csiegber Date 2004-06-15 Time 14:33 Sent To M
Notes
2004-06-15 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-25 Cont ID  
Sent By csiegber Date 2004-03-25 Time 16:39 Rev Time 0.00
Received By csiegber Date 2004-03-25 Time 16:39 Sent To  
Notes
2004-03-25 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-02 Cont ID  
Sent By csiegber Date 2004-01-02 Time 08:20 Rev Time 0.00
Received By csiegber Date 2004-01-02 Time 08:20 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-24 Cont ID  
Sent By csiegber Date 2003-12-24 Time 09:54 Rev Time 0.00
Received By csiegber Date 2003-12-24 Time 09:54 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-06-22 Cont ID  
Sent By pkrauss Date 2004-06-22 Time 09:58 Rev Time 0.35
Received By pkrauss Date 2004-06-22 Time 09:31 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-14 Cont ID  
Sent By csiegber Date 2004-06-15 Time 14:33 Rev Time 0.50
Received By hmoser Date 2004-01-14 Time 10:42 Sent To B
Notes
2004-01-14 00:00:00PLAN DENIED
 NO ENERGY CALCULATIONS NO MANUAL(J)
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-04-02 Cont ID  
Sent By kstevens Date 2004-04-02 Time 18:39 Rev Time 0.75
Received By kstevens Date 2004-04-02 Time 18:39 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-10 Cont ID  
Sent By dpalmer Date 2004-01-06 Time 13:13 Rev Time 0.50
Received By kstevens Date 2004-01-10 Time 12:10 Sent To M
Notes
2004-01-10 00:00:00DENIED
 REFERENCE: FBC-2001 BUILDING
  
 1) A DOOR IS REQUIRED FOR THE BATHROOM
 SECTION 11-11 (SEE ATTACHED SHEET)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-31 Cont ID  
Sent By csiegber Date 2003-12-24 Time 09:54 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***