Plan Review Details - Permit 03121499
Plan Review Stops For Permit 03121499
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-22 Cont ID  
Sent By csiegber Date 2004-05-18 Time 12:30 Rev Time 1.00
Received By jgomez Date 2004-01-22 Time 12:01 Sent To M
Notes
2004-01-22 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR ALL DOORS,WINDOWS
 GLASS BLOCK, ROOF TILE, MULLIONS AND
 STRUCTURAL CONNECTORS.
 2-REVISE DETAIL E/4. FASTENER SPECIFIED
 DOESN'T PROVIDE 2" MIN. EMBEDMENT.
 3-PROVIDE ENGINEERING CALCULATIONS FOR
 TRUSS ANCHORS WITH DIFFERENT FASTENERS
 AS TESTED AND PUBLISHED BY USP TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001.
 4-REVISE DETAIL A/4. WHERE ARE TABLES 6
 AND 8 TAKEN FROM?. SEE FBC 2001 OR
 ASCE 7-98.
 5-SHEET #7: A)REVISE DESIGN PRESSURES AT
 EXTERIOR OPENINGS. SEE TABLES 1606.2B
 AND 1606.2E FBC 2001.
 B)DESIGN PRESSURES SHOWN ON THIS SHEET
 DON'T MATCH THOSE SHOWN ON SHEET 3.
 C)REVISE REAR PORCH FLOOR PLAN AND ROOF
 PLAN RELATING TO WOOD GIRDER, SINCE IT
 WAS CHANGED TO CONCRETE BEAM.
 D)WINDOWS SHOWN ON EXTERIOR ELEVATION
 DON'T MATCH WINDOW SCHEDULE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-13 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:43 Rev Time 2.00
Received By jgomez Date 2004-01-13 Time 17:09 Sent To PC
Notes
2004-01-13 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR: A)SLIDER WINDOWS
 B)GLASS BLOCK. C)ROOF TILE. D)SINGLE
 HUNG WINDOWS. E)ENTRY DOOR WITH SIDE-
 LITE. F)SLIDING GLASS DOORS. G)WINDOW
 MULLIONS. H)TRUSS CONNECTORS.
 3-ARCHITECT TO PROVIDE ALL REQUIREMENTS
 OF CHAPTER 481 FLORIDA STATUTES WHEN
 SUBMITTING DWGS FOR PUBLIC RECORDS.
 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY AND
 REVISE DETAIL TO SHOW ALL COMPONENTS
 REQUIRED ON SUCH LISTING. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-GARAGE BUCK DETAIL E/4 & NOTES ON DWG
 #2 DON'T MATCH. CHECK FASTENER SIZE.
 6-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC REGARDING STEEL STRESS.
 B)SPECIFY SIZES FOR USP RT STRAPS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENER. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-SHEET #7: A)WHERE IS USP EHUH 28-3
 TAKEN FROM?. UNABLE TO FIND IN 2003
 USP CATALOGUE. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 B)MISSING ONE CONNECTOR AT GIRDER TRUSS
 LOCATED AT REAR PORCH. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 C)WHY DESIGN PRESSURES ARE THE SAME FOR
 OPENINGS WITH DIFFERENT SIZE/LOCATION.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 D)WINDOWS SHOWN ON REAR ELEVATION DON'T
 MATCH WINDOW SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-06 Cont ID  
Sent By jleech Date 2004-01-03 Time 10:23 Rev Time 0.33
Received By dpalmer Date 2004-01-06 Time 13:27 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-05-18 Time 12:29 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 12:21 Sent To B
Notes
2004-02-27 00:00:00TO JG DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 15:59 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 15:59 Sent To B
Notes
2004-02-11 00:00:00TO JG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-16 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:43 Rev Time 0.00
Received By csiegber Date 2004-01-16 Time 16:43 Sent To B
Notes
2004-01-16 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-13 Cont ID  
Sent By mmclean Date 2004-01-13 Time 17:22 Rev Time 0.00
Received By jgomez Date 2003-12-24 Time 13:17 Sent To PC
Notes
2003-12-29 00:00:0012/24/03 TO Z
 12/29/2003 TO E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-22 Cont ID  
Sent By pkrauss Date 2004-01-22 Time 15:40 Rev Time 0.25
Received By pkrauss Date 2004-01-22 Time 15:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-06 Cont ID  
Sent By jgomez Date 2004-01-22 Time 12:01 Rev Time 0.33
Received By pkrauss Date 2004-01-06 Time 13:22 Sent To B
Notes
2004-01-06 00:00:00DENIED:
 RETURN AIR JUMPER FROM THE MASTER
 BEDROOM IS NOT SIZED PROPERLY.ALL AIR
 TO THE MASTER SUITE IS TO BE INCLUDED
 IN THE CALCULATION FOR TOTAL SUPPLY
 AIR.RETURN AIR SHALL BE SIZED
 ACCORDING TO THE TOTAL OF SUPPLY AIR.
 PLEASE REVISE PLANS ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-03 Cont ID  
Sent By jleech Date 2004-01-03 Time 10:23 Rev Time 0.25
Received By jleech Date 2004-01-03 Time 10:23 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-01-06 Cont ID  
Sent By dpalmer Date 2004-01-06 Time 13:27 Rev Time 0.00
Received By mmclean Date 2004-01-06 Time 11:56 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-12-24 Cont ID  
Sent By kmcvey Date 2003-12-24 Time 10:34 Rev Time 0.00
Received By mmclean Date 2003-12-24 Time 14:58 Sent To I
Notes
2003-12-24 00:00:00DENIED, NEED TO MEET FRONT SETBACK FOR
 FRONT LOAD GARAGE TO 20FT CALLED CONTR
 LEFT MSG