Plan Review Details - Permit 03121489
Plan Review Stops For Permit 03121489
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:26 Rev Time 1.50
Received By jgomez Date 2004-01-27 Time 11:49 Sent To PC
Notes
2004-01-27 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR ALL DOOR & WINDOW
 TYPES, GLASS BLOCK, ROOF TILE AND
 STRUCTURAL CONNECTORS.
 2-DETAIL E/4 AND RESIDENTIAL NOTES ON
 DRAWING #2 DON'T MATCH. REVISE AS
 REQUIRED.
 3-CLARIFY/REVISE TRUSS ANCHOR SCHEDULE.
 CHECK FOR TYPOS FOR CLARIFICATION OF
 ANCHOR SPECS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 4-TYPICAL WALL SECTION DETAIL A/4. WHERE
 ARE TABLES 6 AND 8 SHOWN FOR ROOF TILE
 FASTENERS TAKEN FROM?. SEE SECTION
 1606.3.2 FBC 2001.
 5-SHEET #7: A)WINDOWS SHOWN ON REAR
 ELEVATION DON'T MATCH THOSE SPECIFIED
 ON WINDOW SCHEDULE.
 B)REVISE ALL NOTES SHOWN ON FLOOR PLAN &
 ROOF FRAMING PLAN. WOOD GIRDER WAS
 CHANGED TO CONCRETE BEAM. SPECIFY
 CORRECT ANCHOR AND DELETE NOTES THAT
 ARE NO APPROPRIATE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 6-SHEET #3: CLARIFY NOTE THAT READS:
 "UPLIFT FOR EACH TRUSS ARE MORE THAN
 THE MAXIMUM VALUE SHOWN FOR THE
 CONNECTOR SELECTED".SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-12 Cont ID  
Sent By hmoser Date 2004-01-26 Time 18:30 Rev Time 2.00
Received By jgomez Date 2004-01-12 Time 18:06 Sent To PC
Notes
2004-01-12 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR: A)SLIDER WINDOW.
 B)GLASS BLOCK. C)ROOF TILE. D)SINGLE
 HUNG WINDOWS. E)ENTRY DOOR WITH SIDE-
 LITE ASSEMBLY. F)SLIDING GLASS DOORS.
 G)WINDOW MULLIONS. H)TRUSS CONNECTORS.
 3-ARCHITECT TO HAVE ALL HIS INFORMATION
 AND REQUIREMENTS OF CHAPTER 481 FL.
 4- 1HR FIRE RATED GLASS BLOCK ASSEMBLY
 NEED SPECIFIC UL LISTED ASSEMBLY AND
 REVISE DETAIL TO INCLUDE ALL REQUIRED
 COMPONENTS ON LISTED ASSEMBLY.SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-CLARIFY GARAGE DOOR BUCK SPECS. DETAIL
 E/4 AND NOTES ON DWG #2 DON'T MATCH.
 REVISE AS REQUIRED.
 6-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC REGARD'G THE STEEL STRESS
 B)SPECIFY SIZES FOR USP RT CONNECTORS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 FASTENER AS REQ'D BY SEC. 104.2.1.1
 CITY AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-SHEET #7: A)CLARIFY WHERE IS USP EHUH
 28-3 CONNECTOR TAKEN FROM?. UNABLE TO
 FIND ON USP 2003 CATALOGUE. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)MISSING ONE CONNECTOR FOR REAR PORCH
 GIRDER TRUSS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 C)CLARIFY WHY THE DESIGN PRESSURES ARE
 THE SAME FOR DIFFERENT OPENING SIZE &
 LOCATION. SEC. 104.2.1.2 CITY AMENDM.
 D)WINDOWS SHOWN ON REAR ELEVATION DON'T
 MATCH WINDOW SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-06 Cont ID  
Sent By jleech Date 2004-01-03 Time 10:31 Rev Time 0.33
Received By dpalmer Date 2004-01-06 Time 07:09 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:26 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 12:26 Sent To B
Notes
2004-02-27 00:00:00TO JG DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 16:01 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 16:01 Sent To B
Notes
2004-02-11 00:00:00TO JG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-20 Cont ID  
Sent By csiegber Date 2004-01-20 Time 11:36 Rev Time 0.00
Received By csiegber Date 2004-01-20 Time 11:36 Sent To M
Notes
2004-01-20 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-12 Cont ID  
Sent By mmclean Date 2004-01-12 Time 18:26 Rev Time 0.00
Received By jgomez Date 2003-12-24 Time 13:15 Sent To PC
Notes
2003-12-29 00:00:0012/24/03 TO Z
 12/29/03 TO E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-26 Cont ID  
Sent By hmoser Date 2004-01-26 Time 18:30 Rev Time 0.25
Received By hmoser Date 2004-01-26 Time 18:30 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-06 Cont ID  
Sent By csiegber Date 2004-01-20 Time 11:37 Rev Time 0.33
Received By pkrauss Date 2004-01-06 Time 13:45 Sent To B
Notes
2004-01-06 00:00:00DENIED:
 RETURN AIR JUMPER FROM THE MASTER
 BEDROOM IS NOT SIZED PROPERLY.ALL AIR
 TO THE MASTER SUITE IS TO BE INCLUDED
 IN THE CALCULATION FOR THE TOTAL SUPPLY
 AIR.RETURN AIR SHALL BE SIZED
 ACCORDING TO THE TOTAL OF SUPPLY AIR.
 PLEASE REVISE PLANS ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-03 Cont ID  
Sent By jleech Date 2004-01-03 Time 10:31 Rev Time 0.25
Received By jleech Date 2004-01-03 Time 10:31 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-01-06 Cont ID  
Sent By mmclean Date 2004-01-06 Time 12:05 Rev Time 0.00
Received By mmclean Date 2004-01-06 Time 12:05 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-12-24 Cont ID  
Sent By dpalmer Date 2004-01-06 Time 07:20 Rev Time 0.00
Received By mmclean Date 2003-12-24 Time 15:15 Sent To I
Notes
2003-12-24 00:00:00DENIED, MUST MEET FRONT SETBACK FOR
 FRONT LOAD GARAGE OF 20FT CALLED CONTR
 LEFT MSG