2004-01-14 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1-ARCHITECT TO COMPLY WITH ALL REQUIRE- |
| MENTS OF CHAPTER 481 FLORIDA STATUTES |
| WHEN SUBMITTING DRAWINGS FOR PUBLIC |
| RECORDS. |
| 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| PRODUCT APPROVAL FOR: ALL DOORS AND |
| WINDOWS, ROOF TILE & TRUSS CONNECTORS. |
| 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR |
| FIRE RATED GLASS BLOCK ASSEMBLY AND |
| REVISE DETAIL TO SHOW ALL COMPONENTS |
| LISTED ON THE ASSEMBLY. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2 |
| DON'T MATCH. CHECK SIZE OF FASTENER. |
| 6-TRUSS ANCHOR SCHEDULE: SPECIFY SIZE OF |
| USP RT CONNECTORS. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 7-DESIGNER OF RECORD TO SPECIFY ROOF |
| TILE FASTENERS. SEC. 104.2.1.1 CITY |
| AMENDMENTS TO FBC 2001. |
| 8-REVISE WINDOW BUCK DETAIL. SEE SEC. |
| 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| INSTALLATION. |
| 9-A)REVISE DESIGN PRESSURES FOR EXTERIOR |
| OPENINGS. SEE TABLES 1606.2B AND |
| 1606.2E ACCORDING TO SIZE & LOCATION. |
| PROVIDE CALCULATIONS FOR DESIGN |
| PRESSURES OTHER THAN THOSE PUBLISHED |
| ON ABOVE TABLES. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| B)SIMPSON EG7 CONNECTOR HAS DIFFERENT |
| FASTENERS THAN THOSE PUBLISHED.PROVIDE |
| ENGINEERING CALCS SHOWING COMPLIANCE |
| WITH SEC. 1609.4.3 FBC 2001 WHICH DOES |
| NOT ALLOW THE STEEL STRESS TO BE |
| INCREASED. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT 805-6712. |