Plan Review Details - Permit 03121484
Plan Review Stops For Permit 03121484
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-23 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:25 Rev Time 1.00
Received By jgomez Date 2004-01-23 Time 11:58 Sent To PC
Notes
2004-01-23 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-ARCHITECT TO PROVIDE ALL DRAWINGS WITH
 INFORMATION AS REQ'D BY CHAPTER 481 FL
 STATUTES. SOME DWGS MISSING THIS INFO.
 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR WINDOWS, DOORS,
 GLASS BLOCK, ROOF TILE, MULLIONS AND
 STRUCTURAL CONNECTORS.
 3-GARAGE BUCK DETAIL AND NOTES ON DWG #2
 DON'T MATCH. CHECK FASTENER SIZE.
 4-TRUSS ANCHOR SCHEDULE: PROVIDE CALCS
 FOR TYPE/NUMBER OF FASTENERS OTHER
 THAN THOSE TESTED AND PUBLISHED BY USP
 TO COMPLY WITH SEC. 1609.4.3 FBC 2001.
 5-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENERS. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 6-REVISE WINDOW BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 7-SHEET #3: A)REVISE DESIGN PRESSURES.
 SEE TABLES 1606.2B & 1606.2E FBC 2001
 FOR PRESSURES ACCORDING TO SIZE AND
 LOCATION.
 B)PROVIDE ENGINEERING CALCS FOR SIMPSON
 EG7 FASTENERS, SINCE THEY DIFFER FROM
 THOSE TESTED AND PUBLISHED BY USP TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-14 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:42 Rev Time 2.00
Received By jgomez Date 2004-01-14 Time 17:35 Sent To PC
Notes
2004-01-14 00:00:00BUILDING REVIEW CHECKLIST:
 1-ARCHITECT TO COMPLY WITH ALL REQUIRE-
 MENTS OF CHAPTER 481 FLORIDA STATUTES
 WHEN SUBMITTING DRAWINGS FOR PUBLIC
 RECORDS.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR: ALL DOORS AND
 WINDOWS, ROOF TILE & TRUSS CONNECTORS.
 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY AND
 REVISE DETAIL TO SHOW ALL COMPONENTS
 LISTED ON THE ASSEMBLY. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2
 DON'T MATCH. CHECK SIZE OF FASTENER.
 6-TRUSS ANCHOR SCHEDULE: SPECIFY SIZE OF
 USP RT CONNECTORS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENERS. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-A)REVISE DESIGN PRESSURES FOR EXTERIOR
 OPENINGS. SEE TABLES 1606.2B AND
 1606.2E ACCORDING TO SIZE & LOCATION.
 PROVIDE CALCULATIONS FOR DESIGN
 PRESSURES OTHER THAN THOSE PUBLISHED
 ON ABOVE TABLES. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 B)SIMPSON EG7 CONNECTOR HAS DIFFERENT
 FASTENERS THAN THOSE PUBLISHED.PROVIDE
 ENGINEERING CALCS SHOWING COMPLIANCE
 WITH SEC. 1609.4.3 FBC 2001 WHICH DOES
 NOT ALLOW THE STEEL STRESS TO BE
 INCREASED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-02 Cont ID  
Sent By dpalmer Date 2004-01-02 Time 15:15 Rev Time 0.33
Received By dpalmer Date 2004-01-02 Time 15:15 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:25 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 12:25 Sent To B
Notes
2004-02-27 00:00:00TO JG DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 16:00 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 16:00 Sent To B
Notes
2004-02-11 00:00:00TO JG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-23 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:42 Rev Time 0.00
Received By jgomez Date 2004-01-16 Time 16:42 Sent To PC
Notes
2004-01-16 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-14 Cont ID  
Sent By mmclean Date 2004-01-14 Time 17:56 Rev Time 0.00
Received By jgomez Date 2003-12-24 Time 10:56 Sent To PC
Notes
2003-12-29 00:00:0012/24/03 TO Z
 12/29/03TO E

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-05 Cont ID  
Sent By dpalmer Date 2004-01-02 Time 15:15 Rev Time 0.33
Received By pkrauss Date 2004-01-05 Time 06:53 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-10 Cont ID  
Sent By pkrauss Date 2004-01-05 Time 07:01 Rev Time 0.33
Received By kstevens Date 2004-01-10 Time 06:43 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-24 Cont ID  
Sent By csiegber Date 2003-12-29 Time 10:56 Rev Time 0.00
Received By mmclean Date 2003-12-24 Time 14:50 Sent To I
Notes
***NONE***