Plan Review Details - Permit 03121481
Plan Review Stops For Permit 03121481
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-06-22 Cont ID  
Sent By jgomez Date 2004-06-22 Time 17:41 Rev Time 0.50
Received By jgomez Date 2004-06-22 Time 17:41 Sent To PC
Notes
2004-06-22 00:00:00PRODUCT APPROVAL SUBMITTAL CHECKLIST:
 1-PROVIDE COPIES OF GARAGE DOOR DRAWINGS
 THAT MATCH DRAWINGS SUBMITTED TO SBCCI
 FOR APPROVAL. NEED COPIES OF DRAWINGS
 THAT WERE SIGNED AND SEALED ON DATE
 NOTED ON SBCCI EVALUATION REPORT.
 2-PROVIDE FLORIDA PRODUCT APPROVAL COVER
 PAGE FOR ENTRY DOOR THAT MATCHES DADE
 COUNTY NOA SUBMITTED. THERMA-TRU AND
 BENCHMARK ARE 2 DIFFERENT MODELS.
 3-SIMONTON DOORS/WINDOWS PACKAGE IS
 INCOMPLETE. NEED FLORIDA PRODUCT
 APPROVAL COVER PAGE FOR FIXED WINDOWS
 AND SLIDING GLASS DOORS USED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-03-29 Cont ID  
Sent By jgomez Date 2004-03-29 Time 12:15 Rev Time 0.33
Received By jgomez Date 2004-03-29 Time 12:15 Sent To PC
Notes
2004-03-29 00:00:00ENGINEER LETTER TO CLARIFY ITEMS
 REQUESTED ON PROVISO.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-02-04 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:21 Rev Time 1.00
Received By jgomez Date 2004-02-04 Time 14:20 Sent To PC
Notes
2004-02-04 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-SOME DRAWINGS ARE MISSING INFORMATION
 REQUIRED BY ARCHITECT TO BE INCLUDED
 AS REQ'D BY CHAPTER 481 FL. STATUTES.
 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL UNDER A SEPARATE
 PERMIT FOR ALL DOORS AND WINDOWS TO BE
 USED, GLASS BLOCK, ROOF TILE MULLIONS
 AND ALL STRUCTURAL CONNECTORS.
 3-DETAIL E/4 AND RESIDENTIAL NOTES ON
 DWG #2 DON'T MATCH. REVISE AS REQUIRED
 4-REVISE WINDOW BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001.
 5-DWG #2: A)CLARIFY/REVISE TRUSS ANCHOR
 SCHEDULE. SEC. 104.2.1.2 CITY AMENDM.
 B)PROVIDE ENGINEER CALCS AND DETAILS AS
 SPECIFIED ON NOTE BELOW TRUSS ANCHOR
 SCHEDULE.
 6-SPECIFY ROOF TILE FASTENERS. SECTION
 104.2.1.1. CITY AMENDMENTS TO FBC 2001
 7-PROVIDE REVISED FRAMING AT REAR PORCH.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 8-CLARIFY NOTE ONSHEET 3A REGARDING
 MAXIMUM UPLIFT VALUES & CONNECTORS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-15 Cont ID  
Sent By csiegber Date 2004-01-20 Time 11:29 Rev Time 2.00
Received By jgomez Date 2004-01-15 Time 09:07 Sent To PC
Notes
2004-01-15 00:00:00BUILDING REVIEW CHECKLIST:
 1-ARCHITECT TO COMPLY WITH ALL REQUIRE-
 MENTS OF CHAPTER 481 FLORIDA STATUTES.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR ALL DOORS/WINDOWS
 TYPE, ROOF TILE, GLASS BLOCK AND ALL
 STRUCTURAL COMPONENTS.
 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY AND
 REVISE DETAIL TO SHOW ALL COMPONENTS
 SPECIFIED ON SUCH ASEMBLY. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2
 DON'T MATCH CHECK FASTENER SIZE.
 6-TRUSS ANCHOR SCHEDULE: A)CONNECTORS TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001 FOR
 STEEL STRESS. REVISE FASTENER TYPE AND
 NUMBER AS SHOWN ON REVISED CATALOGUE.
 PROVIDE ENGINEERING CALCS FOR VALUES
 OTHER THAN THOSE PUBLISHED.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)SPECIFY SIZE OF USP RT STRAPS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENER. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-REVISE DESIGN PRESSURES FOR EXTERIOR
 OPENINGS. SEE TABLES 1606.2B AND
 1606.2E ACCORDING TO SIZE & LOCATION.
 PROVIDE CALCS FOR DESIGN PRESSURES
 THAT SIGNIFICANTLY DIFFER FROM ABOVE
 TABLES. SEC. 104.2.1.2 CITY AMENDMENTS
 10-SIMPSON EG7 CONNECTOR SPECIFIED ON
 ROOF FRAMING PLAN SHOW DIFFERENT
 FASTENERS THAN SHOWN ON CATALOGUE.
 PROVIDE CALCS SHOWING COMPLIANCE WITH
 SEC. 1609.4.3 FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-02 Cont ID  
Sent By dpalmer Date 2004-01-02 Time 15:04 Rev Time 0.33
Received By dpalmer Date 2004-01-02 Time 15:04 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:20 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 12:20 Sent To B
Notes
2004-02-27 00:00:00TO JG DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 16:03 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 16:03 Sent To B
Notes
2004-02-11 00:00:00TO JG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-20 Cont ID  
Sent By csiegber Date 2004-01-20 Time 11:29 Rev Time 0.00
Received By csiegber Date 2004-01-20 Time 11:29 Sent To B
Notes
2004-01-20 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-16 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:53 Rev Time 0.00
Received By csiegber Date 2004-01-16 Time 16:53 Sent To B
Notes
2004-01-16 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-15 Cont ID  
Sent By mmclean Date 2004-01-15 Time 09:30 Rev Time 0.00
Received By jgomez Date 2003-12-24 Time 10:57 Sent To PC
Notes
2003-12-29 00:00:0012/24/03TO Z
 12/29/03 TO E

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-05 Cont ID  
Sent By dpalmer Date 2004-01-02 Time 15:04 Rev Time 0.33
Received By pkrauss Date 2004-01-05 Time 07:56 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-10 Cont ID  
Sent By pkrauss Date 2004-01-05 Time 07:56 Rev Time 0.33
Received By kstevens Date 2004-01-10 Time 07:07 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-24 Cont ID  
Sent By wlehnhar Date 2003-12-24 Time 10:29 Rev Time 0.00
Received By mmclean Date 2003-12-24 Time 14:50 Sent To I
Notes
***NONE***