Plan Review Details - Permit 03121472
Plan Review Stops For Permit 03121472
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-03-26 Cont ID  
Sent By jgomez Date 2004-03-26 Time 07:45 Rev Time 0.33
Received By jgomez Date 2004-03-26 Time 07:45 Sent To PC
Notes
2004-03-26 00:00:00ENGINEER LETTER TO CLARIFY ITEMS ON
 PROVISO.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-21 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:18 Rev Time 1.00
Received By jgomez Date 2004-01-21 Time 13:45 Sent To M
Notes
2004-01-21 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR ALL DOORS,WINDOWS
 ROOF TILE, MULLIONS, GLASS BLOCK AND
 STRUCTURAL CONNECTORS.
 2-REVISE DETAIL E/4. FASTENER SPECIFIED
 DOESN'T PROVIDE 2" MIN. EMBEDMENT.
 3-PROVIDE ENGINEERING FOR TRUSS ANCHOR
 FASTENERS OTHER THAN THOSE TESTED AND
 PUBLISHED BY USP TO COMPLY WITH SEC.
 1609.4.3 FBC 2001 REGARDING STEEL
 STRESS.
 4-REVISE DETAIL A/4. WHERE ARE TABLES 6
 AND 8 TAKEN FROM FOR ROOF TILE FASTE-
 NING. SEE ASCE 7-98 AND FBC 2001.
 5-SHEET #7: A)REVISE DESIGN PRESSURES AT
 EXTERIOR OPENINGS. SEE TABLES 1606.2B
 AND 1606.2E FBC 2001.
 B)DESIGN PRESSURES SHOWN DON'T MATCH
 THOSE SHOWN ON SHEET 3.
 C)REVISE ALL REAR PORCH FLOOR PLAN AND
 ROOF PLAN NOTES REGARDING WOOD BEAM.
 IT WAS CHANGED TO CONCRETE BEAM.
 D)WINDOWS SHOWN ON EXTERIOR ELEVATION
 DON'T MATCH WINDOW SCHEDULE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-09 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:52 Rev Time 3.00
Received By jgomez Date 2004-01-09 Time 10:23 Sent To PC
Notes
2004-01-09 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-STORM SHUTTERS: A)REVISE KEY PLAN AND
 INSTALLATION SCHEDULE. NEED EMERGENCY
 EGRESS THAT COMPLIES WITH SECTION
 1005.4.5 FBC 2001.
 B)CLEARLY MARK ON SHUTTERS DWGS SPECIFIC
 ANCHOR & SPACING TO BE USED ACCORDING
 TO MOUNTING CONDITIONS, EDGE DISTANCE,
 PANEL SPAN, CONNECTION TYPE AND THE
 STRUCTURE TO BE ATTACHED TO (MASONRY
 OR CONCRETE). SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 3-PROVIDE FLORIDA PRODUCT APPROVAL FOR:
 A)HORIZONTAL SLIDER WINDOW: NEED THE
 APPROVED DRAWINGS.
 B)GLASS BLOCK.
 C)ROOF TILE (FBC APPROVAL IS PENDING).
 D)SINGLE HUNG WINDOWS.
 E)ENTRY DOOR WITH SIDELITE ASSEMBLY.
 F)SLIDING GLASS DOORS.
 G)WINDOW MULLIONS.
  
 4-ARCHITECT TO HAVE ALL HIS INFORMATION
 ON TITLE BLOCK AS REQUIRED BY CHAPTER
 481 FL STATUTES. SEE FAC SECTION
 61G1-16.004.
 **NOTE: THIS COMMENT HAVE BEEN ADDRESSED
 BEFORE SEVERAL TIMES AND STILL IS
 NOT DONE.
 5- 1 HR. FIRE RATED GLASS BLOCK ASSEMBLY
 NEED SPECIFIC UL LISTED ASSEMBLY AND
 REVISE DETAIL TO MATCH SUCH ASSEMBLY.
 SPECIFY ALL COMPONENTS THAT MAKE THE
 ONE HR. FIRE RATED ASSEMBLY.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 6-CLARIFY GARAGE DOOR BUCK SPECS. DETAIL
 E/4 AND NOTES ON DWG #2 DON'T MATCH.
 CHECK SIZE OF FASTENER. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC 2001.
 B)SPECIFY USP RT SIZES TO VERIFY VALUE
 SPECIFIED ON CATALOGUE.
 NOTE: PROVIDE ENGINEERING CALCS FOR
 VALUES OTHER THAN THOSE PUBLISHED ON
 CATALOGUE. SECTION 104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001.
 8-ENGINEER TO SPECIFY ROOF TILE FASTENER
 AS REQ'D BY SEC. 104.2.1.1OF CITY
 AMENDMENTS TO FBC 2001.
 9-REVISE WINDOW/DOOR BUCK DETAIL. SEE
 SEC. 1707.4.4.2 FBC 2001 FOR PROPER
 BUCK INSTALLATION.
 10-CLARIFY WHERE IS CONNECTOR USP
 EHUH 28-3 TAKEN FROM?. INABLE TO FIND
 ON USP CATALOGUE. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 11-SHEET #7:A)MISSING CONNECTOR AT ONE
 END OF GIRDER TRUSS AT PORCH. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)REAR ELEVATION: CLARIFY WHY DESIGN
 PRESSURES ARE THE SAME, EVEN FOR OPG'S
 BIGGER THAN OTHERS. REVISE AS REQ'D.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096.
2003-12-24 00:00:00ENTERED IN ERROR

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-06 Cont ID  
Sent By jleech Date 2004-01-03 Time 11:50 Rev Time 0.33
Received By dpalmer Date 2004-01-06 Time 06:25 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:18 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 12:18 Sent To B
Notes
2004-02-27 00:00:00TO JG DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 16:03 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 16:03 Sent To B
Notes
2004-02-11 00:00:00TO JG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-16 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:52 Rev Time 0.00
Received By csiegber Date 2004-01-16 Time 16:52 Sent To B
Notes
2004-01-16 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-09 Cont ID  
Sent By mmclean Date 2004-01-09 Time 15:58 Rev Time 0.00
Received By jgomez Date 2003-12-24 Time 13:11 Sent To PC
Notes
2003-12-29 00:00:0012/24/03 TO Z
 12/29/03 TO E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-22 Cont ID  
Sent By pkrauss Date 2004-01-22 Time 14:39 Rev Time 0.25
Received By pkrauss Date 2004-01-22 Time 14:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-06 Cont ID  
Sent By jgomez Date 2004-01-21 Time 16:45 Rev Time 0.33
Received By pkrauss Date 2004-01-06 Time 12:21 Sent To B
Notes
2004-01-06 00:00:00DENIED:
 RETURN AIR JUMPER FROM THE MASTER
 BEDROOM IS NOT SIZED PROPERLY.ALL AIR
 TO THE MASTER SUITE IS TO BE INCLUDED IN
 THE CALCULATION FOR TOTAL SUPPLY AIR.
 RETURN AIR SHALL BE SIZED ACCORDING TO
 THE TOTAL OF SUPPLY AIR. SEE ATTACHED
 SCHEDULE & REVISE ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-03 Cont ID  
Sent By jleech Date 2004-01-03 Time 11:50 Rev Time 0.25
Received By jleech Date 2004-01-03 Time 11:50 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-01-06 Cont ID  
Sent By mmclean Date 2004-01-06 Time 11:44 Rev Time 0.00
Received By mmclean Date 2004-01-06 Time 11:43 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-12-24 Cont ID  
Sent By dpalmer Date 2004-01-06 Time 06:30 Rev Time 0.00
Received By mmclean Date 2003-12-24 Time 15:15 Sent To I
Notes
2003-12-24 00:00:00DENIED, MUST MEET FRONT SETBACK FOR
 FRONT LOAD GARAGE OF 20FT CALLED CONTR
 LEFT MSG