Plan Review Details - Permit 03121466
Plan Review Stops For Permit 03121466
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-03-19 Cont ID  
Sent By jgomez Date 2004-03-19 Time 12:09 Rev Time 0.33
Received By jgomez Date 2004-03-19 Time 12:09 Sent To PC
Notes
2004-03-19 00:00:00ENGINEER LETTER TO CLARIFY ITEMS
 REQUESTED ON PROVISO DATED 1-23-04.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-23 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:19 Rev Time 1.00
Received By jgomez Date 2004-01-23 Time 18:41 Sent To PC
Notes
2004-01-23 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-REVISE ADDRESS ON NOTICE OF COMMENCE-
 MENT. LOT 10 IS 2254 EGRET COVE DR.
 NOT 2454 EGRET COVE DR.
 2-ARCHITECT IS MISSING SOMEINFORMATION
 ON SOME DRAWINGS AS REQ'D BY CHAPTER
 481 FL ST. NEED NAME AND DATE.
 3-GARAGE BUCK DETAIL AND NOTES ON DWG #2
 DON'T MATCH. CHECK SIZE OF FASTENER.
 4-TRUSS ANCHOR SCHEDULE: PROVIDE CALCS
 FOR FASTENERS TYPE/NUMBER DIFFERENT
 THAN THOSE TESTED AND PUBLISHED BY
 USP TO SATISFY SEC. 1609.4.3 FBC 2001.
 5-SPECIFY ROOF TILE FASTENERS AS REQ'D
 BY SEC. 104.2.1.1 CITY AMENDMENTS TO
 FBC 2001 AND SEC. 1606.3 FBC 2001.
 6-REVISE WINDOW BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 7-SHEET #3: A)REVISE/CLARIFY EXTERIOR
 OPENINGS DESIGN PRESSURES ACCORDING TO
 SIZE AND LOCATION IN WALL. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)PROVIDE CALCS FOR FASTENERS USED FOR
 EG7 CONNECTOR, SINCE THEY DIFFER FROM
 THOSE TESTED AND PUBLISHED BY SIMPSON
 TO SATISFY SEC. 1609.4.3 FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-15 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:40 Rev Time 2.00
Received By jgomez Date 2004-01-15 Time 10:41 Sent To PC
Notes
2004-01-15 00:00:00BUILDING REVIEW CHECKLIST:
 1-ARCHITECT TO COMPLY WITH ALL REQUIRE-
 MENTS OF CHAPTER 481 FLORIDA STATUTES.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR: ALL WINDOW/DOOR
 TYPES, ROOF TILE, MULLIONS, GLASS
 BLOCK AND ALL STRUCTURAL COMPONENTS.
 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY AND
 REVISE DETAIL TO SHOW ALL COMPONENTS
 REQUIRED ON THE LISTED ASSEMBLY.
 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2
 DON'T MATCH. CHECK FASTENER SIZE.
 6-TRUSS ANCHOR SCHEDULE: A)UPDATE TRUSS
 ANCHOR SCHEDULE TO COMPLY WITH SECTION
 1609.4.3 FBC REGARDING STEEL STRESS.
 PROVIDE ENGINEERING CALCS FOR VALUES
 OTHER THAN THOSE PUBLISHED. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)SPECIFY SIZE OF USP RT STRAPS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENER. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-DESIGN PRESSURES AT EXTERIOR OPENINGS
 DIFFER THOSE SHOWN ON TABLES 1606.2B
 AND 1606.2E FBC 2001 ACCORDING TO SIZE
 & LOCATION. PROVIDE ENGINEERING CALCS
 FOR DIFFERENT DESIGN PRESSURES. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 10-PROVIDE ENGINEERING CALCS FOR SIMPSON
 EG7 CONNECTOR SHOWING COMPLIANCE WITH
 SEC. 1609.4.3 FBC 2001. FASTENERS ARE
 DIFFERENT FROM THOSE PUBLISHED ON
 CATALOGUE. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-02 Cont ID  
Sent By dpalmer Date 2004-01-02 Time 13:22 Rev Time 0.33
Received By dpalmer Date 2004-01-02 Time 13:22 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:19 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 12:19 Sent To B
Notes
2004-02-27 00:00:00TO JG DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 16:01 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 16:01 Sent To B
Notes
2004-02-11 00:00:00TO JG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-23 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:40 Rev Time 0.00
Received By jgomez Date 2004-01-16 Time 16:40 Sent To PC
Notes
2004-01-16 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-15 Cont ID  
Sent By mmclean Date 2004-01-15 Time 11:09 Rev Time 0.00
Received By jgomez Date 2003-12-24 Time 10:30 Sent To PC
Notes
2003-12-29 00:00:0012/24/03TO Z
 TO E

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-05 Cont ID  
Sent By dpalmer Date 2004-01-02 Time 13:22 Rev Time 0.33
Received By pkrauss Date 2004-01-05 Time 07:47 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-10 Cont ID  
Sent By pkrauss Date 2004-01-05 Time 07:47 Rev Time 0.33
Received By kstevens Date 2004-01-10 Time 06:49 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-24 Cont ID  
Sent By ptjomsto Date 2003-12-24 Time 10:28 Rev Time 0.00
Received By mmclean Date 2003-12-24 Time 14:49 Sent To I
Notes
***NONE***