Plan Review Details - Permit 03121457
Plan Review Stops For Permit 03121457
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-22 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:06 Rev Time 2.00
Received By jgomez Date 2004-01-22 Time 17:36 Sent To PC
Notes
2004-01-22 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-SOME DRAWINGS ARE MISSING INFORMATION
 REQUIRED BY ARCHITECT TO BE INCLUDED
 IN ALL PLAN AS REQ'D BY CHAPTER 471
 FLORIDA STATUTES.
 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 INFORMATION FOR ALL DOORS, WINDOWS,
 GLASS BLOCK, ROOF TILE, MULLIONS AND
 STRUCTURAL CONNECTORS PRIOR TO INSTA-
 LLATION.
 3-GARAGE BUCK DETAIL AND NOTES ON DWG #2
 DON'T MATCH. CHECK FASTENER SIZE.
 4-TRUSS ANCHOR SCHEDULE: PROVIDE CALCS
 FOR TYPE/NUMBER OF FASTENERS OTHER
 THAN THOSE TESTED AND PUBLISHED BY USP
 TO COMPLY WITH SEC. 1609.4.3 FBC 2001
 REGARDING STEEL STRESS INCREASE.
 5-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENERS AS REQ'D BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
 6-REVISE WINDOW BUCK DETAIL. SEE SECTION
 1707.4.42 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 7-SHEET #3: A)REVISE DESIGN PRESSURES.
 SEE TABLES 1606.2B AND 1606.2E FOR
 DESIGN PRESSURES ACCORDING TO SIZE AND
 LOCATION.
 B)PROVIDE ENGINEERING CALCULATIONS FOR
 SIMPSON EG7 FASTENERS, SINCE THEY ARE
 DIFFERENT THAN THOSE TESTED AND
 PUBLISHED BY USP TO COMPLY WITH SEC.
 1609.4.3 FBC 2001 REGARDING THE STEEL
 STRESS INCREASE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-14 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:42 Rev Time 3.00
Received By jgomez Date 2004-01-14 Time 15:08 Sent To PC
Notes
2004-01-14 00:00:00BUILDING REVIEW CHECKLIST:
 1-ARCHITECT TO COMPLY WITH ALL REQUIRE-
 MENTS OF CHAPTER 481 FLORIDA STATUTES
 WHEN SUBMITTING DWGS FOR PUBLIC RECORD
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR: SLIDER WINDOWS,
 GLASS BLOCK, ROOF TILE, SINGLE HUNG
 WINDOWS, ENTRY DOOR WITH SIDELITE,
 FIXED WINDOWS, SLIDING GLASS DOORS,
 TRUSS CONNECTORS.
 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY AND
 REVISE DETAIL TO MATCH ALL COMPONENTS
 SPECIFIED ON THE LISTING. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-GARAGE BUCK DETAIL DOESN'T MATCH NOTE
 ON DWG #2. SEE FASTENER SIZE. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 6-A)UPDATE TRUSS ANCHOR SCHEDULE AND
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC REGARDING STEEL STRESS.
 B)SPECIFY SIZE OF USP RT STRAP. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENER AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-SHEET #3B: A)CLARIFY DESIGN PRESSURES
 CALCULATED FO EXTERIOR OPENINGS. THEY
 DEVIATE FROM TABLES 1606.2B & 1606.2E
 ACCORDING TO SIZE/LOCATION. PROVIDE
 CALCULATIONS FOR DESIGN PRESSURES THAT
 ARE DIFFERENT FROM ABOVE MENTIONED
 TABLES. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
 B)CONNECTOR SIMPSON EG7 SHOWS DIFFERENT
 FASTENERS AS PUBLISHED ON CATALOGUE.
 PROVIDE ENGINEERING SHOWING HOW THIS
 CONNECTOR COMPLIES WITH SEC. 1609.4.3
 FBC 2001 WHICH DOESN'T ALLOW THE STEEL
 STRESS TO BE INCREASED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-02 Cont ID  
Sent By dpalmer Date 2004-01-02 Time 13:12 Rev Time 0.33
Received By dpalmer Date 2004-01-02 Time 13:12 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:06 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 12:06 Sent To B
Notes
2004-02-27 00:00:00TO JG DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 15:58 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 15:57 Sent To B
Notes
2004-02-11 00:00:00TO JG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-22 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:42 Rev Time 0.00
Received By jgomez Date 2004-01-16 Time 16:42 Sent To PC
Notes
2004-01-16 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-14 Cont ID  
Sent By mmclean Date 2004-01-14 Time 15:42 Rev Time 0.00
Received By jgomez Date 2003-12-24 Time 10:55 Sent To PC
Notes
2003-12-29 00:00:0012/24/03 TO Z
 12/29/03 TO E

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-05 Cont ID  
Sent By dpalmer Date 2004-01-02 Time 13:13 Rev Time 0.33
Received By pkrauss Date 2004-01-05 Time 07:50 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-10 Cont ID  
Sent By pkrauss Date 2004-01-05 Time 07:50 Rev Time 0.33
Received By kstevens Date 2004-01-10 Time 07:01 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-24 Cont ID  
Sent By msmith Date 2003-12-24 Time 10:31 Rev Time 0.00
Received By mmclean Date 2003-12-24 Time 14:49 Sent To I
Notes
***NONE***