Plan Review Details - Permit 03121454
Plan Review Stops For Permit 03121454
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-06-22 Cont ID  
Sent By jgomez Date 2004-06-22 Time 17:10 Rev Time 0.50
Received By jgomez Date 2004-06-22 Time 17:10 Sent To PC
Notes
2004-06-22 00:00:00PRODUCT APPROVAL SUBMITTAL CHECKLIST:
 1-PROVIDE COPIES OF DRAWINGS FOR GARAGE
 THAT WERE SUBMITTED TO SBCCI FOR
 APPROVAL. NEED DWGS THAT WERE SIGNED
 AND SEALED ON THE DATE NOTED ON SBCCI
 EVALUATION REPORT.
 2-PROVIDE FLORIDA PRODUCT APPROVAL COVER
 PAGE THAT MATCHES DADE COUNTY NOA
 SUBMITTED. BENCHMARK AND THERMA-TRU
 DOORS ARE 2 DIFFERENT MODELS.
 3-SIMONTON DOORS/WINDOWS PACKAGE IS
 INCOMPLETE. NEED FLORIDA PRODUCT
 APPROVAL COVER PAGE FOR FIXED WINDOWS
 AND SLIDING GLASS DOORS USED.
 4-WINDOW MULLIONS: PROVIDE NOA REPORT
 AND DWGS THAT MATCH THOSE SUBMITTED
 FOR FLORIDA PRODUCT APPROVAL.
 5-PROVIDE ALL INFORMATION REQUESTED ON
 PROVISO DATED 1-20-04. SEE ATTACHED
 COPY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-20 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:32 Rev Time 2.00
Received By jgomez Date 2004-01-20 Time 16:37 Sent To M
Notes
2004-01-20 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR ALL WINDOWS AND
 DOORS, GLASS BLOCK, MULLIONS, ROOF
 TILE AND STRUCTURAL CONNECTORS.
 2-REVISE DETAIL E/4. FASTENER SPECIFIED
 DOESN'T PROVIDE 2" MIN. EMBEDMENT. SEC
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 3-PROVIDE ENGINEERING CALCULATIONS FOR
 NUMBER OF FASTENERS SPECIFIED ON TRUSS
 ANCHOR SCHEDULE SINCE THEY DIFFER FROM
 TESTED AND PUBLISHED VALUES BY USP TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001
 REGARDING THE STEEL STRESS LIMITATION.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 4-CLARIFY WHERE ARE TABLES 6 AND 8 NOTED
 ON DETAIL A/4 FOR ROOF TILE FASTENING
 TAKEN FROM?. WEE FOLLOW FBC 2001 AND
 ASCE 7-98 AND THEY DON'T HAVE THOSE
 TABLES. SEC. 104.2.1.2 CITY AMENDMENTS
 5-SHEET A7: A)REVISE DESIGN PRESSURES.
 SEE TABLES 1606.2B AND 1606.2E FBC.
 B)DESIGN PRESSURES SHOWN ON THIS SHEET
 AND SHEET 3 DON'T MATCH.
 C)REVISE SPECS ON FLOOR PLAN & ROOF PLAN
 TO REFLECT CHANGE OF BEAM FROM WOOD TO
 CONCRETE BEAM. REVISE TRUSS ANCHOR AND
 NOTES FOR WOOD BEAM. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 D)WINDOWS SHOWN ON ELEVATION DON'T MATCH
 THOSE ON WINDOW SCHEDULE. REVISE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-09 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:54 Rev Time 2.00
Received By jgomez Date 2004-01-09 Time 15:59 Sent To PC
Notes
2004-01-09 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-STORM SHUTTERS: A)REVISE KEY PLAN AND
 INSTALLATION SCHEDULE. NEED EMERGENCY
 EGRESS THAT COMPLIES WITH SECTION
 1005.4.5 FBC 2001. MAKE SURE KEY PLAN
 MATCHES FLOOR PLAN SUBMITTED.
 B)CLEARLY INDICATE ANCHOR TYPE & SPACING
 TO BE USED ACCORDING TO EDGE DISTANCE,
 PANEL SPAN, CONNECTION TYPE, DESIGN
 PRESSURES & STRUCTURE TO BE ATTACHED
 TO (MASONRY OR CONCRETE).
 3-PROVIDE FLORIDA PRODUCT APPROVAL FOR:
 A)HORIZONTAL SLIDER WINDOW: NEED THE
 APPROVED DRAWINGS.
 B)GLASS BLOCK.
 C)ROOF TILE(FBC APPROVAL IS PENDING)
 D)SINGLE HUNG WINDOWS.
 E)ENTRY DOOR WITH SIDELITE ASSEMBLY.
 F)SLIDING GLASS DOORS.
 G)WINDOW MULLIONS.
 H)TRUSS CONNECTORS.
  
 4-ARCHITECT TO HAVE ALL HIS INFORMATION
 ON TITLE BLOCK AS REQUIRED BY CHAAPTER
 481 FLORIDA STATUTES. SEE FAC SECTION
 61G1-16004.
 **THIS COMMENT HAS BEEN ADDRESSED ON
 PREVIOUS REVIEWS.
 5-1 HR FIRE RATED GLASS BLOCK ASSEMBLY
 NEED SPECIFIC UL LISTED ASSEMBLY AND
 REVISE DETAIL TO MATCH SUCH ASSEMBLY.
 SPECIFY ALL COMPONENTS REQUIRED TO
 MEET THE ONE HR FIRE RATED ASSEMBLY.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-CLARIFY GARAGE DOOR BUCK SPECS. DETAIL
 E/4 AND NOTES ON DWG #2 DON'T MATCH.
 CHECK SIZE OF FASTENER. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 7-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC 2001.
 B)SPECIFY USP RT SIZES TO VERIFY VALUE
 SPECIFIED ON CATALOGUE.
 8-ENGINEER TO SPECIFY ROOF TILE FASTENER
 AS REQ'D BY SEC. 104.2.1.1 OF CITY
 AMENDMENTS TO FBC 2001.
 9-REVISE WINDOW BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 10-SHEET #7: A)CLARIFY WHERE IS USP
 EHUH 28-3 TAKEN FROM?. UNABLE TO FIND
 IN 2003 CATALOGUE. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 B)MISSING SPECIFICATIONS FOR CONNECTOR
 AT ONE END OF GIRDER TRUSS AT REAR
 PORCH. SEC. 104.2.1.2 CITY AMENDMENTS.
 C)REAR ELEVATION: CLARIFY CALCULATED
 DESIGN PRESSURES. WHY SAME PRESSURES
 FOR DIFFERENT SIZE/LOCATION OF OPG'S?
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-06 Cont ID  
Sent By jleech Date 2004-01-03 Time 11:47 Rev Time 0.33
Received By dpalmer Date 2004-01-06 Time 06:29 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:32 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 12:32 Sent To B
Notes
2004-02-27 00:00:00TO JG DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-16 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:54 Rev Time 0.00
Received By csiegber Date 2004-01-16 Time 16:54 Sent To B
Notes
2004-01-16 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-09 Cont ID  
Sent By mmclean Date 2004-01-09 Time 17:06 Rev Time 0.00
Received By jgomez Date 2003-12-24 Time 13:10 Sent To PC
Notes
2003-12-29 00:00:0012/24/03 TO Z
 12/29/03 TO E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-22 Cont ID  
Sent By pkrauss Date 2004-01-22 Time 13:42 Rev Time 0.25
Received By pkrauss Date 2004-01-22 Time 13:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-06 Cont ID  
Sent By jgomez Date 2004-01-20 Time 16:38 Rev Time 0.33
Received By pkrauss Date 2004-01-06 Time 12:38 Sent To B
Notes
2004-01-06 00:00:00DENIED:
 RETURN AIR JUMPER FROM THE MASTER
 BEDROOM IS NOT SIZED PROPERLY.ALL AIR
 TO THE MASTER SUITE IS TO BE INCLUDED
 IN THE CALCULATION FOR TOTAL SUPPLY
 AIR.RETURN AIR SHALL BE SIZED
 ACCORDING TO THE TOTAL OF SUPPLY AIR.
 SEE THE ATTACHED SCHEDULE & REVISE
 ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-03 Cont ID  
Sent By jleech Date 2004-01-03 Time 11:47 Rev Time 0.25
Received By jleech Date 2004-01-03 Time 11:47 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-01-06 Cont ID  
Sent By mmclean Date 2004-01-06 Time 11:49 Rev Time 0.00
Received By mmclean Date 2004-01-06 Time 11:49 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-12-24 Cont ID  
Sent By dpalmer Date 2004-01-06 Time 06:30 Rev Time 0.00
Received By mmclean Date 2003-12-24 Time 15:09 Sent To I
Notes
2003-12-24 00:00:00DENIED, MUST MEET FRONT SETBACK FOR
 FRONT LOAD GARAGE OF 20FT CALLED CONTR
 LEFT MSG