2004-01-09 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 2-STORM SHUTTERS: A)REVISE KEY PLAN AND |
| INSTALLATION SCHEDULE. NEED EMERGENCY |
| EGRESS THAT COMPLIES WITH SECTION |
| 1005.4.5 FBC 2001. MAKE SURE KEY PLAN |
| MATCHES FLOOR PLAN SUBMITTED. |
| B)CLEARLY INDICATE ANCHOR TYPE & SPACING |
| TO BE USED ACCORDING TO EDGE DISTANCE, |
| PANEL SPAN, CONNECTION TYPE, DESIGN |
| PRESSURES & STRUCTURE TO BE ATTACHED |
| TO (MASONRY OR CONCRETE). |
| 3-PROVIDE FLORIDA PRODUCT APPROVAL FOR: |
| A)HORIZONTAL SLIDER WINDOW: NEED THE |
| APPROVED DRAWINGS. |
| B)GLASS BLOCK. |
| C)ROOF TILE(FBC APPROVAL IS PENDING) |
| D)SINGLE HUNG WINDOWS. |
| E)ENTRY DOOR WITH SIDELITE ASSEMBLY. |
| F)SLIDING GLASS DOORS. |
| G)WINDOW MULLIONS. |
| H)TRUSS CONNECTORS. |
| |
| 4-ARCHITECT TO HAVE ALL HIS INFORMATION |
| ON TITLE BLOCK AS REQUIRED BY CHAAPTER |
| 481 FLORIDA STATUTES. SEE FAC SECTION |
| 61G1-16004. |
| **THIS COMMENT HAS BEEN ADDRESSED ON |
| PREVIOUS REVIEWS. |
| 5-1 HR FIRE RATED GLASS BLOCK ASSEMBLY |
| NEED SPECIFIC UL LISTED ASSEMBLY AND |
| REVISE DETAIL TO MATCH SUCH ASSEMBLY. |
| SPECIFY ALL COMPONENTS REQUIRED TO |
| MEET THE ONE HR FIRE RATED ASSEMBLY. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 6-CLARIFY GARAGE DOOR BUCK SPECS. DETAIL |
| E/4 AND NOTES ON DWG #2 DON'T MATCH. |
| CHECK SIZE OF FASTENER. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 7-REVISE/UPDATE TRUSS ANCHOR SCHEDULE & |
| ALL DETAILS THAT ARE AFFECTED BY SEC. |
| 1609.4.3 FBC 2001. |
| B)SPECIFY USP RT SIZES TO VERIFY VALUE |
| SPECIFIED ON CATALOGUE. |
| 8-ENGINEER TO SPECIFY ROOF TILE FASTENER |
| AS REQ'D BY SEC. 104.2.1.1 OF CITY |
| AMENDMENTS TO FBC 2001. |
| 9-REVISE WINDOW BUCK DETAIL. SEE SECTION |
| 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| INSTALLATION. |
| 10-SHEET #7: A)CLARIFY WHERE IS USP |
| EHUH 28-3 TAKEN FROM?. UNABLE TO FIND |
| IN 2003 CATALOGUE. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| B)MISSING SPECIFICATIONS FOR CONNECTOR |
| AT ONE END OF GIRDER TRUSS AT REAR |
| PORCH. SEC. 104.2.1.2 CITY AMENDMENTS. |
| C)REAR ELEVATION: CLARIFY CALCULATED |
| DESIGN PRESSURES. WHY SAME PRESSURES |
| FOR DIFFERENT SIZE/LOCATION OF OPG'S? |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT (561)805-6712. |