Plan Review Details - Permit 03121448
Plan Review Stops For Permit 03121448
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-20 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:12 Rev Time 2.00
Received By jgomez Date 2004-01-20 Time 11:29 Sent To M
Notes
2004-01-20 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR ALL DOORS/WINDOWS
 TYPE, GLASS BLOCK, MULLIONS, ROOF TILE
 AND STRUCTURAL CONNECTORS.
 2-DETAIL E/4: REVISEFASTENER SIZE TO
 ACHIEVE 2" MIN. EMBEDMENT. REVISE NOTE
 ON DWG #2 TO MATCH. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 3-PROVIDE ENGINEERING CALCS FOR FASTENER
 SPECIFIED ON TRUSS ANCHORS TO COMPLY
 WITH SEC. 1609.4.3 FBC 2001 REGARDING
 STEEL STRESS WHEN USING DIFFERENT
 NUMBER OF FASTENERS THAN THOSE TESTED
 AND PUBLISHED ON CATALOGUE.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 4-DETAIL A/4: WHERE ARE TABLES 6 AND 8
 FOR ROOF TILE FASTENER TAKEN FROM?.
 WE USE FBC 2001 OR ASCE 7-98.
 5-SHEET A-7: A)REVISE DESIGN PRESSURES @
 EXTERIOR OPENINGS. SEE TABLES 1606.2B
 AND 1606.2E FBC 2001.
 B)DESIGN PRESSURES SHOWN ON SHEET 3B AND
 SHEET 7 DON'T MATCH.
 C)REVISE REAR PORCH FLOOR PLAN AND ROOF
 FRAMING PLAN TO REFLECT CHANGE FROM
 GIRDER TRUSS TO CONCRETE BEAM. SOME
 NOTES STILL REFER TO GIRDER TRUSS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 D)WINDOWS SHOWN ON EXTERIOR ELEVATION
 DON'T MATCH THOSE SHOWN ON WINDOW
 SCHEDULE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-14 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:55 Rev Time 2.00
Received By jgomez Date 2004-01-14 Time 09:55 Sent To PC
Notes
2004-01-14 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR: SLIDER WINDOWS,
 GLASS BLOCK, ROOF TILE, SINGLE HUNG
 WINDOWS, ENTRY DOOR WITH SIDELITE,
 SLIDING GLASS DOORS, WINDOW MULLIONS
 AND TRUSS CONNECTORS.
 3-ARCHITECT TO PROVIDE AND FOLLOW ALL
 REQUIREMENTS OF CHAPTER 481 FLORIDA
 STATUTES WHEN SUBMITTING DRAWINGS FOR
 PUBLIC RECORDS.
 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY AND
 REVISE DETAIL TO MATCH ALL COMPONENTS
 LISTED ON THE LISTED ASSEMBLY. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-GARAGE BUCK DETAIL E/4 DON'T MATCH
 NOTES ON DWG #2. SEE FASTENER SIZE.
 6-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC REGARDING STEEL STRESS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 B)SPECIFY SIZE OF USP RT STRAPS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENER. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-SHEET #7: A)WHERE IS USP EHUH 28-3
 CONNECTOR TAKEN FROM?. UNABLE TO FIND
 IN 2003 USP CATALOGUE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 B)MISSING ONE CONNECTOR AT GIRDER TRUSS
 AT REAR PORCH. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 C)DESIGN PRESSURES FOR OPENINGS WITH
 DIFFERENT SIZE ARE THE SAME. WHY?. SEC
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 D)WINDOWS SHOWN ON EXTERIOR ELEVATION
 DON'T MATCH WINDOW SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-02 Cont ID  
Sent By dpalmer Date 2004-01-02 Time 13:38 Rev Time 0.33
Received By dpalmer Date 2004-01-02 Time 13:38 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:12 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 12:12 Sent To B
Notes
2004-02-27 00:00:00TO JG DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 15:57 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 15:57 Sent To B
Notes
2004-02-11 00:00:00TO JG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-16 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:55 Rev Time 0.00
Received By csiegber Date 2004-01-16 Time 16:55 Sent To B
Notes
2004-01-16 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-14 Cont ID  
Sent By mmclean Date 2004-01-14 Time 10:42 Rev Time 0.00
Received By jgomez Date 2003-12-24 Time 13:09 Sent To PC
Notes
2003-12-29 00:00:0012/24/03 TO Z
 12/29/03 TO E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-22 Cont ID  
Sent By pkrauss Date 2004-01-22 Time 14:18 Rev Time 0.25
Received By pkrauss Date 2004-01-22 Time 14:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-05 Cont ID  
Sent By jgomez Date 2004-01-20 Time 11:29 Rev Time 0.33
Received By pkrauss Date 2004-01-05 Time 07:11 Sent To P
Notes
2004-01-05 00:00:00DENIED:
 RETURN AIR FROM THE MASTER BEDROOM IS
 NOT SIZED PROPERLY.PER 2001 FBC(M)
 601.4 EXECPTION #3, ALL SUPPLY AIR INTO
 THE MASTER SUITE SHALL BE INCLUDED FOR
 THE PROPER SIZING OF THE RETURN AIR TO
 THAT SPACE. PLEASE SEE ATTACHED SCHEDULE
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-10 Cont ID  
Sent By pkrauss Date 2004-01-05 Time 07:14 Rev Time 0.33
Received By kstevens Date 2004-01-10 Time 06:38 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-24 Cont ID  
Sent By kmcvey Date 2003-12-24 Time 10:33 Rev Time 0.00
Received By mmclean Date 2003-12-24 Time 15:01 Sent To I
Notes
***NONE***