Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-26 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:31 Rev Time 1.00
Received By jgomez Date 2004-01-26 Time 08:55 Sent To PC
Notes
2004-01-26 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-SOME DRAWINGS NEED TO HAVE ALL INFO.
 REQUIRED BY THE ARCHITECT AS REQ'D
 BY CHAPTER 481 FLORIDA STATUTES.
 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR DOORS, WINDOWS,
 ROOF TILE, GLASS BLOCK, MULLIONS AND
 STRUCTURAL CONNECTORS.
 3-GARAGE BUCK DETAIL AND NOTES ON DWG #2
 DON'T MATCH. CHECK FASTENER SIZE.
 4-TRUSS ANCHOR SCHEDULE: PROVIDE CALCS
 FOR TYPE/NUMBER OF FASTENERS WHEN THEY
 ARE DIFFERENT THAN THOSE TESTED AND
 PUBLISHED ON CATALOGUE TO COMPLY WITH
 SEC. 1609.4.3 FBC 2001.
 5-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENERS. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 6-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.42 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 7-SHEET #3: A)REVISE/CLARIFY EXTERIOR
 OPENINGS DESIGN PRESSURES ACCORDING
 TO SIZE AND LOCATION. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 B)PROVIDE ENGINEERING CALCS FOR SYMPSON
 EG7 FASTENERS, SINCE THEY ARE DIFFEENT
 FROM THOSE TESTED AND PUBLISHED TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-14 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:40 Rev Time 2.00
Received By jgomez Date 2004-01-14 Time 16:56 Sent To PC
Notes
2004-01-14 00:00:00BUILDING REVIEW CHECKLIST:
 1-ARCHITECT TO COMPLY WITH ALL REQUIRE-
 MENTS OF CHAPTER 481 WHEN SUBMITTING
 DRAWINGS FOR PUBLIC RECORD.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR EXTERIOR DOOR AND
 WINDOWS, ROOF TILE AND TRUSS ANCHORS.
 4-PROVIDE SPECIFIC UL LISTING FOR GLASS
 BLOCK RATED 1HR RATED ASSEMBLY AND
 REVISE DETAIL TO MATCH LISTED ASSEMBLY
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2
 DON'T MATCH. CHECK FASTENER SIZE.
 6-TRUSS ANCHOR SCHEDULE: SPECIFY SIZE OF
 USP RT STRAP USED. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENERS. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-A)REVISE DESIGN PRESSURES FOR EXTERIOR
 OPENINGS. SEE TABLES 1606.2B AND
 1606.2E ACCORDING TO SIZE & LOCATION.
 PROVIDE CALCULATIONS FOR DESIGN PRESSU
 RES THAT DIFFER FROM ABOVE TABLES. SEC
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)SIMPSON EG7 CONNECTOR HAS DIFFERENT
 FASTENERS THAN SHOWN ON CATALOGUE.
 PROVIDE ENGINEERING CALCS SHOWING
 COMPLIANCE WITH SEC. 1609.4.3 FBC 2001
 REGARDING STEEL STRESS INCREASE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-02 Cont ID  
Sent By dpalmer Date 2004-01-02 Time 12:55 Rev Time 0.33
Received By dpalmer Date 2004-01-02 Time 12:55 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:30 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 12:30 Sent To B
Notes
2004-02-27 00:00:00TO JG DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 16:00 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 16:00 Sent To B
Notes
2004-02-11 00:00:00TO JG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-16 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:40 Rev Time 0.00
Received By csiegber Date 2004-01-16 Time 16:40 Sent To B
Notes
2004-01-16 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-14 Cont ID  
Sent By mmclean Date 2004-01-14 Time 17:28 Rev Time 0.00
Received By jgomez Date 2003-12-24 Time 10:22 Sent To PC
Notes
2003-12-29 00:00:0012/24/03TO Z
 12/29/03 TO E

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-05 Cont ID  
Sent By dpalmer Date 2004-01-02 Time 12:55 Rev Time 0.33
Received By pkrauss Date 2004-01-05 Time 08:14 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-10 Cont ID  
Sent By pkrauss Date 2004-01-05 Time 08:18 Rev Time 0.33
Received By kstevens Date 2004-01-10 Time 07:33 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-24 Cont ID  
Sent By ptjomsto Date 2003-12-24 Time 10:23 Rev Time 0.00
Received By mmclean Date 2003-12-24 Time 14:51 Sent To I
Notes
***NONE***