Plan Review Details - Permit 03121445
Plan Review Stops For Permit 03121445
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-06-22 Cont ID  
Sent By jgomez Date 2004-06-22 Time 15:36 Rev Time 0.50
Received By jgomez Date 2004-06-22 Time 15:36 Sent To PC
Notes
2004-06-22 00:00:00PRODUCT APPROVAL SUBMITTAL CHECKLIST:
 1-PROVIDE DRAWINGS FOR GARAGE DOOR THAT
 MATCHES DRAWINGS SUBMITTED TO SBCCI
 FOR APPROVAL. NEED DRAWINGS THAT WERE
 SIGNED AND SEALED ON THE DATE NOTED ON
 THE SBCCI EVALUATION REPORT.
 2-PROVIDE FLORIDA PRODUCT APPROVAL COVER
 PAGE FOR ENTRY DOOR THAT MATCHES DADE
 COUNTY NOA SUBMITTED. BENCHMARK AND
 THERMA-TRU ARE 2 DIFFERENT MODELS.
 3-SIMONTON WINDOWS/DOORS PACKAGE IS
 INCOMPLETE. NEED FLORIDA PRODUCT
 APPROVAL COVER PAGE FOR FIXED WINDOWS
 AND SLIDING GLASS DOORS TO BE USED.
 4-WINDOW MULLIONS: PROVIDE DADE COUNTY
 NOA DWGS THAT MATCH FLORIDA PRODUCT
 APPROVAL. NOA SUBMITTED IS NOT THE
 SAME REPORT SUBMITTED FOR APPROVAL.
 5-PROVIDE ALL INFORMATION REQUESTED ON
 PROVISO DATED 1-23-04. SEE ATTACHED
 COPY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-23 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:32 Rev Time 1.00
Received By jgomez Date 2004-01-23 Time 11:07 Sent To PC
Notes
2004-01-23 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-SOME DRAWINGS ARE MISSING INFORMATION
 REQUIRED BY ARCHITECT TO BE INCLUDED
 IN ALL PLANS AS REQ'D BY CHAPTER 471
 FLORIDA STATUTES.
 2-PROVIDE COMLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR DOORS, WINDOWS,
 GLASS BLOCK, MULLIONS, ROOF TILE AND
 STRUCTURAL CONNECTORS.
 3-GARAGE BUCK DETAIL AND NOTES ON DWG #2
 DON'T MATCH. CHECK FASTENER SIZE.
 4-TRUSS ANCHOR SCHEUDLE: PROVIDE CALCS
 FOR TYPE/NUMBER OF FASTENERS OTHER
 THAN THOSE TESTED AND PUBLISHED BY USP
 TO COMPLY WITH SEC. 1609.4.3 FBC 2001.
 5-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENERS AS REQUIRED BY SEC.
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
 6-REVISE WINDOW BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 7-SHEET #3: A)REVISE DESIGN PRESSURES.
 SEE TABLES 1606.2B AND 1606.2E FBC FOR
 MIN. PRESSURES ACCORDING TO SIZE AND
 LOCATION OF OPENING.
 B)PROVIDE ENGINEERING CALCS FOR SIMPSON
 EG7 FASTENERS,SINCE THEY ARE DIFFERENT
 THAN THOSE TESTED AND PUBLISHED BY USP
 TO COMPLY WITH SEC. 1609.4.3 FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-15 Cont ID  
Sent By kstevens Date 2004-01-10 Time 06:24 Rev Time 2.00
Received By jgomez Date 2004-01-15 Time 14:27 Sent To PC
Notes
2004-01-15 00:00:00BUILDING REVIEW CHECKLIST:
 1-ARCHITECT TO COMPLY WITH CHAPTER 481
 FLORIDA STATUTES WHEN SUBMITTING DWGS
 FOR PUBLIC RECORDS.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR ALL DOORS/WINDOWS
 TYPE, MULLIONS, GLASS BLOCK, ROOF TILE
 AND ALL STRUCTURAL CONNECTORS.
 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY AND
 REVISE DETAIL ACCORDINGLY. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2
 DON'T MATCH. CHECK FASTENERS.
 6-UPDATE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS TO COMPLY WITH SEC. 1609.4.3
 FBC 2001.PROVIDE ENGINEERING CALCS
 FOR DIFFERENT VALUES AND FASTENERS.
 SEE REVISE CATALOGUES.
 B)SPECIFY SIZE FOR RT USP STRAPS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENER. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-REVISE DESIGN PRESSURES FOR EXTERIOR
 OPENINGS. SEE TABLES 1606.2B AND
 1606.2E FOR PRESSURES ACCORDING TO
 SIZE AND LOCATION. PROVIDE ENGINEERING
 CALCS FOR DIFFERENT VALUES.
 10-PROVIDE ENGINEERING CALCS FOR SIMPSON
 EG-7 CONNECTOR SHOWING COMPLIANCE WITH
 SEC. 1609.4.3 FBC REGARDING THE STEEL
 STRESS SINCE FASTENERS AREN'T THE SAME
 AS TESTED AND PUBLISHED BY SIMPSON.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-02 Cont ID  
Sent By dpalmer Date 2004-01-02 Time 12:46 Rev Time 0.33
Received By dpalmer Date 2004-01-02 Time 12:45 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:32 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 12:32 Sent To B
Notes
2004-02-27 00:00:00TO JG DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-15 Cont ID  
Sent By mmclean Date 2004-01-15 Time 14:38 Rev Time 0.00
Received By jgomez Date 2003-12-24 Time 10:58 Sent To PC
Notes
2003-12-29 00:00:0012/24/03 TO Z
 12/29/03 TO E

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-23 Cont ID  
Sent By dpalmer Date 2004-01-02 Time 12:46 Rev Time 0.25
Received By pkrauss Date 2004-01-23 Time 09:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-10 Cont ID  
Sent By kstevens Date 2004-01-10 Time 06:24 Rev Time 0.33
Received By kstevens Date 2004-01-10 Time 06:24 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-24 Cont ID  
Sent By wlehnhar Date 2003-12-24 Time 10:28 Rev Time 0.00
Received By mmclean Date 2003-12-24 Time 14:50 Sent To I
Notes
***NONE***