Plan Review Details - Permit 03121444
Plan Review Stops For Permit 03121444
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-06-22 Cont ID  
Sent By jgomez Date 2004-06-22 Time 15:07 Rev Time 0.50
Received By jgomez Date 2004-06-22 Time 15:07 Sent To PC
Notes
2004-06-22 00:00:00PRODUCT APPROVAL SUBMITTAL CHECKLIST:
 1-PROVIDE DRAWINGS FOR GARAGE DOOORS
 THAT MATCH DRAWINGS SUBMITTED TO SBCCI
 FOR APPROVAL. NEED DRAWINGS THAT
 WERE SIGNED AND SEALED ON THE DATE
 NOTED ON SBCCI EVALUATION REPORT.
 2-PROVIDE FLORIDA PRODUCT APPROVAL COVER
 THAT MATCHES DADE COUNTY NOA DRAWINGS.
 THERMA-THRU AND BENCHMARK DOORS ARE
 2 DIFFERENT MODELS.
 3-SIMONTON DOORS/WINDOWS PACKAGE IS
 INCOMPLETE. NEED FLORIDA PRODUCT
 APPROVAL COVER PAGE FOR FIXED WINDOW
 AND SLIDING GLASS DOORS TO BE USED IN
 THIS PROJECT.
 4-PROVIDE INFORMATION REQUESTED ON
 PROVISO DATED 1-20-04. SEE ATTACHED
 COPY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-20 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:24 Rev Time 2.00
Received By jgomez Date 2004-01-20 Time 14:06 Sent To M
Notes
2004-01-20 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR ALL WINDOW/DOOR
 TYPE, GLASS BLOCK, MULLIONS,ROOF TILE,
 STRUCTURAL CONNECTORS.
 2-REVISE DETAIL E/4. FASTENER SPECIFIED
 DOESN'T PROVIDE 2" MIN. EMBEDMENT. SEC
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 3-PROVIDE ENGINEERING CALCS FOR TRUSS
 ANCHOR FASTENERS SINCE THEY ARE
 DIFFERENT FROM TESTED & PUBLISHED
 VALUES BY USP TO COMPLY WITH SECTION
 1609.4.3 FBC 2001 REGARDING THE STEEL
 STRESS INCREASE.SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 4-ROOF TILE FASTENERS ON DETAIL A/4 CALL
 FOR TABLES 6 AND 8. THESE TABLES ARE
 NOT IN FBC 2001 OR ASCE 7-98. CLARIFY.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 5-SHEET A-7: A)REVISE DESIGN PRESSURES @
 EXTERIOR OPENINGS. SEE TABLES 1606.2B
 AND 1606.2E FBC 2001.
 B)DESIGN PRESWSURES SHOWN ON THIS PAGE
 DON'T MATCH DESIGN PRESSURES SHOWN ON
 SHEET 3.
 C)REVISE REAR PORCH FLOOR PLAN AND ROOF
 PLAN. BEAM WAS CHANGED TO CONCRETE BM.
 THERE ARE SOME NOTES THAT STILL CALL
 FOR GIRDER TRUSS CONNECTORS AND
 BUILD-UP. REVISE AS REQUIRED. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 D)WINDOWS SHOWN ON EXTERIOR ELEVATION
 DON'T MATCH WINDOW SCHEDULE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-14 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:55 Rev Time 2.00
Received By jgomez Date 2004-01-14 Time 07:48 Sent To PC
Notes
2004-01-14 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR: SLIDER WINDOWS,
 GLASS BLOCK, ROOF TILE, SINGLE HUNG
 WINDOWS, ENTRY DOOR WITH SIDELITE,
 SLIDING GLASS DOORS, WINDOW MULLIONS
 AND TRUSS CONNECTORS.
 3-ARCHITECT TO PROVIDE ALL INFORMATION
 REQUIRED BY CHAPTER 481 FL. STATUTES.
 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY AND
 REVISE DETAIL TO MATCH ALL COMPONENTS
 REQUIRED ON LISTED ASSEMBLY. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-GARAGE BUCK DETAIL E/4 & NOTES ON DWG
 #2 DON'T MATCH. CHECK FASTENER SIZE.
 6-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC REGARDING STEEL STRESS.
 B)SPECIFY SIZE OF USP RT STRAPS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENER. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-SHEET #7: A)WHERE IS USP EHUH 28-3
 CONNECTOR TAKEN FROM?. UNABLE TO FIND
 IN USP 2003 CATALOGUE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 B)MISSING ONE CONNECTOR AT GIRDER TRUSS
 LOCATED IN REAR PORCH. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 C)WHY DESIGN PRESSURES SHOWN ON REAR
 ELEVATION ARE THE SAME FOR OPENINGS
 WITH DIFFERENT SIZE & LOCATION?. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 D)WINDOWS SHOWN ON REAR ELEVATION DON'T
 MATCH WINDOW SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-02 Cont ID  
Sent By dpalmer Date 2004-01-02 Time 07:18 Rev Time 0.00
Received By dpalmer Date 2004-01-02 Time 07:19 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:24 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 12:24 Sent To B
Notes
2004-02-27 00:00:00TO JG DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-16 Cont ID  
Sent By mmclean Date 2004-01-20 Time 14:50 Rev Time 0.00
Received By csiegber Date 2004-01-16 Time 16:55 Sent To B
Notes
2004-01-16 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-14 Cont ID  
Sent By mmclean Date 2004-01-14 Time 09:23 Rev Time 0.00
Received By jgomez Date 2003-12-24 Time 13:08 Sent To PC
Notes
2003-12-29 00:00:0012/24/03 TO Z
 12/29/03 TO E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-22 Cont ID  
Sent By pkrauss Date 2004-01-22 Time 14:07 Rev Time 0.25
Received By pkrauss Date 2004-01-22 Time 14:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-05 Cont ID  
Sent By jgomez Date 2004-01-20 Time 14:06 Rev Time 0.33
Received By pkrauss Date 2004-01-05 Time 07:17 Sent To P
Notes
2004-01-05 00:00:00DENIED:
 RETURN AIR FROM THE MASTER BEDROOM IS
 NOT SIZED PROPERLY.PER 2001 FBC(M)
 601.4 EXCEPTION #3, ALL SUPPLY AIR INTO
 THE MASTER SUITE SHALL BE INCLUDED IN
 THE CALCULATION FOR A TOTAL OF SUPPLY
 AIR TO THAT SPACE.RETURN SHALL BE
 SIZED ACCORDINGLY.PLEASE SEE THE
 ATTACHED SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-10 Cont ID  
Sent By pkrauss Date 2004-01-05 Time 07:27 Rev Time 0.33
Received By kstevens Date 2004-01-10 Time 06:30 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-01-20 Cont ID  
Sent By mmclean Date 2004-01-20 Time 14:50 Rev Time 0.00
Received By mmclean Date 2004-01-20 Time 14:50 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-12-24 Cont ID  
Sent By kmcvey Date 2003-12-24 Time 10:25 Rev Time 0.00
Received By mmclean Date 2003-12-24 Time 15:19 Sent To I
Notes
2003-12-24 00:00:00DENIED, MUST MEET FRONT SETBACK FOR
 FRONT LOAD GARAGE OF 20FT CALLED CONTR
 LEFT MSG