Plan Review Details - Permit 03121436
Plan Review Stops For Permit 03121436
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-03-03 Cont ID  
Sent By jgomez Date 2004-03-03 Time 09:28 Rev Time 3.00
Received By jgomez Date 2004-03-03 Time 09:28 Sent To PC
Notes
2004-03-03 00:00:00BUILDING REVIEW PROVISO:
 1-REVISE SPECIFICATIONS FOR INSTALLATION
 OF CEILING AT REAR ENTRY & REAR PORCH.
 FASTENER NEED TO HAVE 1 3/4" MINIMUM
 PENETRATION INTO HORIZONTAL MEMBER.
 SEE ASTM C-1063. SEC. 2504.2 FBC 2001.
 2-REVISE WINDOW BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-11 Cont ID  
Sent By mmclean Date 2004-03-02 Time 16:14 Rev Time 3.50
Received By jgomez Date 2004-02-11 Time 14:59 Sent To PC
Notes
2004-02-11 00:00:00BUILDING REVIEW CHECKLIST:
 1-PROVIDE IMPACT FEES PAID RECEIPT.
 2-SURVEY SAYS FLOOD ZONE A8. FLOOD ZONE
 WAS CHANGED TO B PER LETTER OF MAP
 REVISION DATED DEC 3 1985. REVISE INFO
 ON SURVEY AS REQUIRED.
 3-AS OF OCT. 1ST 2003 NEED TO PROVIDE
 FLORIDA OR LOCAL PRODUCT APPROVAL FOR
 ALL TYPES OF DOORS, WINDOWS, MULLIONS
 (AS SHOWN ON PLANS), ROOF TILE AND ALL
 STRUCTURAL CONNECTORS AS REQUIRED BY
 RULE 9B-72.
 4-NEED RECORDED NOTICE OF COMMENCEMENT.
 5-DRAWING #3 IS MISSING ENGINEER'S LOGO
 AND SEAL, SIGNATURE AND DATE.
 6-SPECIFY ROOF TILE FASTENERS. SEE SEC.
 1606.3 FBC 2001 AND SECTION 104.2.1.1
 CITY AMENDMENTS TO FBC 2001.
 7-PROVIDE COMPLETE SECTION/DETAIL THRU
 MASONRY COLUMNS @ ENTRY AND REAR PORCH
 SHOWING FOOTING LOCATION IN RELATION
 TO FINISH GRADE. ALSO, NEED TO SHOW
 COMPLETE SPECS FOR VERTICAL REINFORCE-
 MENT. PROVIDE CALCULATIONS TO SHOW HOW
 THESE COLUMNS (FRONT AND REAR WILL
 PROVIDE SUPPORT FOR UPLIFT LOADS).
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 8-SPECIFY SIZE OF ATTIC ACCESS. SEE SEC.
 2309.6 FBC 2001.
 9-PROVIDE COMPLETE DETAIL AND SPECS FOR
 HANGING OF AHU. SPECIFY ALL FASTENERS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 10-SHEET #5B: A)SPECIFY TRUSS CONNECTORS
 FOR ALL TRUSSES.
 B)PROVIDE DETAILS FOR INSTALLATION OF #
 OF ANCHORS AT UNION OF TRUSSES TO COLS
 AS SPECIFIED ON TRUSS ANCHOR SCHEDULE.
 SEE ROOF FRAMING PLAN FOR COMMENTS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 11-REVISE DETAIL 28/4S2. SEE ZONE 3 ON
 FIGURE 1606.2(C) FBC 2001.
 12-PROVIDE DETAIL/SPECS FOR INSTALLATION
 OF CEILING AT ENTRY AND REAR PORCH.
 SEE ASTM C-926 & ASTM C-1063. SPECIFY
 STUCCO THICKNESS AND FASTENER SIZE AND
 SPACING. SEC. 2504.2 FBC 2001.
 13-SHOW ONLY DETAILS THAT APPLY TO THIS
 PROJECT.
 14-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 15-GARAGE BUCK DETAIL 3/4S1 AND DETAIL
 3/4S4 DON'T MATCH. CHECK SIZE AND MIN.
 NUMBER OF ANCHORS. ALSO,SPECIFY ANCHOR
 SPACING AT THE END OF BUCK AND SPECIFY
 SIZE OF WASHERS. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 16-DWG #4S4: CLARIFY BUTT GLAZING NOTE:
 IS THERE ANY BUTT GLAZING IN MORNING
 AREA OR THERE ARE FIXED WINDOWS WITH
 STOREFRONT SYSTEM? EITHER WAY NEED
 PRODUCT APPROVAL. SEE SEC. 2406.2 FBC.
 17-PROVIDE AREA TABULATIONS INCLUDING
 A/C AREAS, PORCHES, GARAGE ETC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-08-09 Cont ID  
Sent By dpalmer Date 2005-08-09 Time 19:41 Rev Time 0.30
Received By dpalmer Date 2005-08-09 Time 19:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-08-01 Cont ID  
Sent By dpalmer Date 2005-08-01 Time 20:01 Rev Time 0.20
Received By dpalmer Date 2005-08-01 Time 20:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-07-21 Cont ID  
Sent By dpalmer Date 2005-07-21 Time 14:23 Rev Time  
Received By dpalmer Date 2005-07-21 Time 14:23 Sent To  
Notes
2005-07-21 00:00:00** UNSAT **
  
 1)NOTE: PLEASE SHOW PANEL "C" ON PLANS.
  
  
  
 2)NOTE: PLEASE SEE REDTAG ISSUE BY
 ELECTRICAL INSPECTOR FOR LANDSCAPE
 LIGHTING NOT PERMITTED. PLEASE ALSO SEE
 CORRECTION NOTICE FOR INSTALLATION WHICH
 DOES NOT MEET CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-06-28 Cont ID  
Sent By dpalmer Date 2005-06-28 Time 06:57 Rev Time 0.50
Received By dpalmer Date 2005-06-28 Time 06:45 Sent To  
Notes
2005-06-28 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE PLANS MUST CONTAIN
 THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR PLANS AND /OR
 DESIGN.
 FBC 104.2.1
  
 2)NOTE: PLEASE SEE ONLY ONE SM APPL
 CIRCUIT IS INDICATED IN LOAD
 CALCULATIONS AND "KITCHEN OUTLETS" ARE
 SHOWN ON PANEL SCHEDULE. PLEASE SEE
 210.52B1, 220.16,210.11C1, A MIN OF TWO
 "SMALL APPLIANCE" CIRCUITS ARE REQUIRED
 ON PANEL SCHEDULE AND LOAD CALCULATIONS.
  
 3)NOTE: PLEASE SEE RECEPT/CONN FOR
 JACUZZI TUB IS BE SHOWN AS GFI/ GFI
 PROTECTED. 680.71
  
 4)NOTE: PLEASE SEE MISSING GROUNDING
 ELECTRODE CONDUCTOR PER 250.50, 250.66
 #2 MIN.
  
 5)NOTE: PLEASE SEE MISSING RECEPT IN
 LEISURE RM. 210.52
  
 6)NOTE: PLEASE INDICATE LOADS FOR
 PANELS.
 PLEASE SEE ALL CONTINUOUS LOADS ARE TO
 BE SHOWN @125%.(POOL PUMP, POOL HEAT
 PUMP).
 215.5,220.31,680.9 ETC.215.3,230.42, 100
 ETC.
  
 7)NOTE: PLEASE SEE PANEL "C" IS MISSING
 FROM PLANS? PLEASE ALSO SEEE PANEL "C"
 IS SHOWN ASMBP? THIS IS ONLY A NOTE
 ABOUT THE MB INDICATED. IF SHOWN AS MCB
 THEN A MCB WILL BE REQUIRED.
 PLEASE SEE "TAN" SHOWN FOR COLOR OF
 CONDUCTORS??
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-02-27 Cont ID  
Sent By dpalmer Date 2004-02-27 Time 06:16 Rev Time 0.33
Received By dpalmer Date 2004-02-27 Time 06:10 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-31 Cont ID  
Sent By csiegber Date 2004-02-17 Time 16:22 Rev Time 0.75
Received By dpalmer Date 2003-12-31 Time 14:51 Sent To M
Notes
2003-12-31 00:00:00*********** UNSAT *************
  
  
 *** NOTE*** UNABLE TO DUE COMPLETE
 REVIEW AT THIS TIME DUE TO PLANS MISSING
 RISER DIAGRAM FOR SERVICE.
  
  
 1)NOTE: PLEASE SUBMIT COMPLETE RISER
 DIAGRAM. 215.5,250.50,110.9, 310.15B6
 250.66 ETC
  
 2)NOTE: PLEASE CLARIFY MASTER BATH NOT
 SHOWN ON PANEL SCHEDULE? OTHER BATHS
 SHOWN AND PER 210.52D,210.11C3 OTHER
 BATHS MAY NOT BE ON EITHER OF THESE.
  
 3)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. PER 210.8A6
  
 4)NOTE: PLEASE SEE 210.52C1 FOR RECEPT
 SPACING ALONG KITCHEN COUNTERSPACE.
 MISSING A FEW.
  
 5)NOTE: PLEASE SHOW /NOTE ALL OUTSIDE/
 GARAGE RECEPTS AS GFI. 210.8
  
 6)NOTE: PLEASE SEE MISSING RECEPT FOR
 LIVING RM PER 210.52/ 2' WALL.
  
 7)NOTE: PLEASE SEE THAT NOTE ON PLAN
 MENTIONS SD TO BE 3' FROM RETURN.
 PLEASE SEE NFPA-72, STATES TO BE 3' FROM
 SUPPLY GRILLES. NFPA DOES NOT STATE R/A
 TYP PER MANF SPECS AND CITY OF WPB SD'S
 ARE TO BE 5' FROM RETURN AIR.
  
 8)NOTE: PLEASE SEE THAT PLANS ONLY
 SHOW ONEA/C CONDENSER UNIT?
 PLEASE SHOW ADDITIONAL UNIT AS SHOWN
 ON PANEL SCHEDULE.
 PLEASE ALSO SHOW/CLARIFY LOCATION OF
 AHU #2? ALSO 210.70/210.63 LOCATIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-08 Cont ID  
Sent By adarroug Date 2005-08-08 Time 14:55 Rev Time 0.00
Received By adarroug Date 2005-08-08 Time 14:55 Sent To E
Notes
2005-08-08 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-29 Cont ID  
Sent By adarroug Date 2005-07-29 Time 15:41 Rev Time 0.00
Received By adarroug Date 2005-07-29 Time 15:41 Sent To E
Notes
2005-07-29 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-20 Cont ID  
Sent By adarroug Date 2005-07-20 Time 14:08 Rev Time 0.00
Received By adarroug Date 2005-07-20 Time 14:08 Sent To E
Notes
2005-07-20 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-24 Cont ID  
Sent By adarroug Date 2005-06-24 Time 11:15 Rev Time 0.00
Received By adarroug Date 2005-06-24 Time 11:15 Sent To E
Notes
2005-06-24 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-17 Cont ID  
Sent By csiegber Date 2004-02-17 Time 16:22 Rev Time 0.00
Received By csiegber Date 2004-02-17 Time 16:22 Sent To E
Notes
2004-02-17 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-11 Cont ID  
Sent By mmclean Date 2004-02-05 Time 15:30 Rev Time 0.00
Received By csiegber Date 2003-12-23 Time 16:54 Sent To  
Notes
2003-12-29 00:00:0012/23/03TO Z
 12/29/03 Z PASSED BUT DID NOT ENTER-
 PASSING TO SFD RACK/E DEE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-02-27 Cont ID  
Sent By pkrauss Date 2004-02-27 Time 06:47 Rev Time 0.30
Received By pkrauss Date 2004-02-27 Time 06:33 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-05 Cont ID  
Sent By dpalmer Date 2004-02-27 Time 06:16 Rev Time 0.35
Received By pkrauss Date 2004-01-05 Time 10:02 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-01-10 Cont ID  
Sent By pkrauss Date 2004-01-05 Time 10:13 Rev Time 0.25
Received By kstevens Date 2004-01-10 Time 07:59 Sent To B
Notes
2004-01-10 00:00:00NO PLUMBING PLANS SUBMITTED - PLUMING
 PERMIT REQUIRED.

Review Stop Z ZONING
Rev No 2 Status P Date 2004-03-02 Cont ID  
Sent By mmclean Date 2004-03-02 Time 16:14 Rev Time 0.00
Received By mmclean Date 2004-03-02 Time 16:14 Sent To B
Notes
2004-03-02 00:00:00RE-STAMP PLANS GIVEN TO JULIO MM

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-24 Cont ID  
Sent By csiegber Date 2003-12-23 Time 16:54 Rev Time 0.00
Received By mmclean Date 2003-12-24 Time 15:30 Sent To I
Notes
***NONE***