Plan Review Details - Permit 03121432
Plan Review Stops For Permit 03121432
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-05-23 Cont ID  
Sent By jwitmer Date 2005-05-23 Time 12:32 Rev Time 0.55
Received By jwitmer Date 2005-05-23 Time 12:32 Sent To PC
Notes
2005-05-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03121432
 ADD: 1500 S. OLIVE AVE
 CONT: BATTEN
 TEL: (561)662-0309
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 ?1016.1 MEANS OF EGRESS ILLUMINATION
  
 ?1016.1.1 ILLUMINATION OF MEANS OF
 EGRESS SHALL BE PROVIDED IN
 ACCORDANCE WITH THIS SECTION FOR EVERY
 BUILDING AND STRUCTURE.FOR THE
 PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS AND PASSAGEWAYS LEADING TO
 AN EXIT.FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT DISCHARGE SHALL
 INCLUDE ONLY DESIGNATED STAIRS,
 AISLES, CORRIDORS, RAMPS, ESCALATORS,
 WALKWAYS AND EXIT PASSAGEWAY LEADING
 TO A PUBLIC WAY.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-03-02 Cont ID  
Sent By jwitmer Date 2004-03-02 Time 16:01 Rev Time 1.22
Received By jwitmer Date 2004-03-02 Time 15:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-15 Cont ID  
Sent By jwitmer Date 2004-01-15 Time 13:00 Rev Time 2.00
Received By jwitmer Date 2004-01-15 Time 13:00 Sent To  
Notes
2004-01-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03121432
 ADD: 1500 S OLIVE AVE
 CONT: BATTEN
 TEL: (561)662-0309
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) CUT SECTION 1/A-7FRONT ENTRY DOES
 NOT INDICATE THE GRADE OR ENTRY, STEPS
 OR RAMPS ETC 11-4.1.6 IF EXISTING ELE-
 MENTS, SPACES, OR COMMON AREAS ARE ALTER
 ED, THEN EACH SUCH ALTERED ELEMENT,
 SPACE, FEATURE OR AREA SHALL COMPLY WITH
 THE APPLICABLE PROVISIONS OF 11-4.1.1
 TO 11-4.1.3 MINIMUIM REQUIREMENTS FOR
 NEW CONSTRUCTION.
  
 2) DOOR# 1&2 BOTH SHOW INFILL BLOCK THAT
 THE DOOR OPENINGS ARE NEXT TO, ARE THE
 END CELLS GROUTED, IS THERE ANY VERTICAL
 STEEL?
  
 3) CLEARSTORY, SHEET A-6 INDICATES ON
 THE WEST SIDE REBARS BEING WELDED TO THE
 BAR JOIST, NO INFORMATION ON TYPE OF
 WELD OR THICKNESS.
  
 4) SAME DETAIL EAST SIDE THE DEPTH OF
 THE HOLE FOR THE EPOXIED REBAR IS NOT
 GIVEN.
  
 5) SAME DETAIL THE METAL STUD FRAMING
 THAT IS FASTENED TO THE BOTTOM OF THE
 ROOF SLAB, TYPE OF FASTENER & SPACING?
  
 6) THIS ALSO HOLDS TRUE FOR THE METAL
 FRAMING EAST OF THE CLEARSTORY.
  
 7)THE METAL FRAMING ON THE EAST SIDE OF
 THE CLEARSTORY HAS A STUUCO FINISH ON
 WIRE LATH MISSING IS EITHER PAPER BACK
 LATH OR MOISTURE PROTECTION, 2303.3.
  
 8) FLORIDA ENERGY CODE FORM 400 D FOR
 RENTOVATIONS OF BUILDINGS, MISSING.
  
 9) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS BOTH STOREFRONT AND
 AWNING UNIT
 B) MULLIONS
 C) SWING DOORS BOTH GLAZED AND NON
 D) ROOFING ASSEMLIES, ROOFING REPORT
 INDICATE USE OF STANDING SEAM FAST-
 ENED TO CONCRETE OR GUNITE DECK
 E) STORM SHUTTERS IF DECISION NOT TO
 USE LARGE MISSLE GLAZING
  
 10) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-04-20 Cont ID  
Sent By dpalmer Date 2005-04-20 Time 16:58 Rev Time 0.10
Received By dpalmer Date 2005-04-20 Time 16:58 Sent To  
Notes
2005-04-20 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE PLANS NOW APPEAR TO
 BE REMOVING ALL LIGHTING IN EGRESS
 HALLWAY ARA.
 PLEASE SEE FIRE REVIEW COMMENTS TO MIN
 LIGHT REQUIRED FOR EGRESS.
 PLEASE SEE LS 101 5-8.
  
 2)NOTE: PLEASE INCLUDE ALL INFORMATION
 ON TITLE BLOCK FOR FIRM: ADDRESS ETC.
 PLEASE SEE FAC 61G1-16.004
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-02-09 Cont ID  
Sent By dpalmer Date 2004-02-09 Time 09:51 Rev Time 0.50
Received By dpalmer Date 2004-02-09 Time 09:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-02 Cont ID  
Sent By dpalmer Date 2004-01-02 Time 17:05 Rev Time 0.33
Received By dpalmer Date 2004-01-02 Time 17:05 Sent To  
Notes
2004-01-02 00:00:00PLEASE SEE FIRE REVIEW COMMENTS THAT
 WILL AFFECT ELECTRICAL PLANS.
 ELECTRICAL OK, PENDING FIRE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2005-04-27 Cont ID  
Sent By mwennerg Date 2005-04-27 Time 11:04 Rev Time 0.00
Received By mwennerg Date 2005-04-27 Time 11:04 Sent To  
Notes
2005-04-27 00:00:001) EXIT LIGHTS AND EMERGENCY LIGHTING
 FACILITIES SHALL BE ARRANGED IN ALL
 REQUIRED MEANS OF EGRESS.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-02-10 Cont ID  
Sent By mcarsill Date 2004-02-10 Time 14:27 Rev Time 0.00
Received By mcarsill Date 2004-02-10 Time 14:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-01-02 Cont ID  
Sent By mcarsill Date 2004-01-02 Time 07:35 Rev Time 0.00
Received By mcarsill Date 2004-01-02 Time 07:35 Sent To  
Notes
2004-01-02 00:00:001) PLANS DO NOT INDICATE TYPE OF
 OCCUPANCY.
  
 2) PLANS DO NOT INDICATE CONSTRUCTION
 TYPE.
  
 3) NO EMERGENCY LIGHTS OR EXIT SIGNS
 SHOWN.
  
 4) ELEVATION DOES NOT DISPLAY BUILDING
 ADDRESS. A MINIMUM OF 6" HIGH NUMBERS
 ARE REQUIRED.
  
 5) MORE DETAILS REQUIRED ON THE PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-23 Cont ID  
Sent By adarroug Date 2005-05-23 Time 09:01 Rev Time 0.00
Received By adarroug Date 2005-05-23 Time 09:01 Sent To B
Notes
2005-05-23 00:00:00TAKEN OFF BD#24 TO "JWITMER" DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-12 Cont ID  
Sent By adarroug Date 2005-04-12 Time 14:56 Rev Time 0.00
Received By adarroug Date 2005-04-12 Time 14:56 Sent To  
Notes
2005-04-12 00:00:00TO "COMM" BD#24

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-04 Cont ID  
Sent By csiegber Date 2004-02-04 Time 11:45 Rev Time 0.00
Received By csiegber Date 2004-02-04 Time 11:45 Sent To  
Notes
2004-02-04 00:00:00TO COMM BD#56

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-23 Cont ID  
Sent By csiegber Date 2003-12-23 Time 16:00 Rev Time 0.00
Received By csiegber Date 2003-12-23 Time 16:00 Sent To  
Notes
2003-12-23 00:00:00TO COMM BD#47

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-06 Cont ID  
Sent By pkrauss Date 2004-01-06 Time 16:35 Rev Time 0.33
Received By pkrauss Date 2004-01-06 Time 16:35 Sent To  
Notes
***NONE***