2004-01-15 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 03121432 |
| ADD: 1500 S OLIVE AVE |
| CONT: BATTEN |
| TEL: (561)662-0309 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) CUT SECTION 1/A-7FRONT ENTRY DOES |
| NOT INDICATE THE GRADE OR ENTRY, STEPS |
| OR RAMPS ETC 11-4.1.6 IF EXISTING ELE- |
| MENTS, SPACES, OR COMMON AREAS ARE ALTER |
| ED, THEN EACH SUCH ALTERED ELEMENT, |
| SPACE, FEATURE OR AREA SHALL COMPLY WITH |
| THE APPLICABLE PROVISIONS OF 11-4.1.1 |
| TO 11-4.1.3 MINIMUIM REQUIREMENTS FOR |
| NEW CONSTRUCTION. |
| |
| 2) DOOR# 1&2 BOTH SHOW INFILL BLOCK THAT |
| THE DOOR OPENINGS ARE NEXT TO, ARE THE |
| END CELLS GROUTED, IS THERE ANY VERTICAL |
| STEEL? |
| |
| 3) CLEARSTORY, SHEET A-6 INDICATES ON |
| THE WEST SIDE REBARS BEING WELDED TO THE |
| BAR JOIST, NO INFORMATION ON TYPE OF |
| WELD OR THICKNESS. |
| |
| 4) SAME DETAIL EAST SIDE THE DEPTH OF |
| THE HOLE FOR THE EPOXIED REBAR IS NOT |
| GIVEN. |
| |
| 5) SAME DETAIL THE METAL STUD FRAMING |
| THAT IS FASTENED TO THE BOTTOM OF THE |
| ROOF SLAB, TYPE OF FASTENER & SPACING? |
| |
| 6) THIS ALSO HOLDS TRUE FOR THE METAL |
| FRAMING EAST OF THE CLEARSTORY. |
| |
| 7)THE METAL FRAMING ON THE EAST SIDE OF |
| THE CLEARSTORY HAS A STUUCO FINISH ON |
| WIRE LATH MISSING IS EITHER PAPER BACK |
| LATH OR MOISTURE PROTECTION, 2303.3. |
| |
| 8) FLORIDA ENERGY CODE FORM 400 D FOR |
| RENTOVATIONS OF BUILDINGS, MISSING. |
| |
| 9) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) WINDOWS BOTH STOREFRONT AND |
| AWNING UNIT |
| B) MULLIONS |
| C) SWING DOORS BOTH GLAZED AND NON |
| D) ROOFING ASSEMLIES, ROOFING REPORT |
| INDICATE USE OF STANDING SEAM FAST- |
| ENED TO CONCRETE OR GUNITE DECK |
| E) STORM SHUTTERS IF DECISION NOT TO |
| USE LARGE MISSLE GLAZING |
| |
| 10) PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |