Plan Review Stops For Permit 03121424 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2004-02-02 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2004-02-02 |
Time |
14:04 |
Rev Time |
1.11 |
Received By |
jwitmer |
Date |
2004-02-02 |
Time |
14:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2004-01-14 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2004-01-14 |
Time |
16:20 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2004-01-14 |
Time |
16:20 |
Sent To |
|
|
Notes |
2004-01-14 00:00:00 | | | | | BUILDING PLAN REVIEW | | PERMIT: 03121424 | | ADD: 701 NORTHPOINTE CORP PARKWAY | | CONT: PASS INTERNATIONAL | | TEL: (561)239-0125 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | 1ST BUILDING REVIEW | | ACTION: DENIED | | | | 1) DOOR# 3 & 17 REQUIRE 18" ON THE PULL | | SIDE,11-4.13.6 MANEUVERING CLEARENCES | | AT DOORS. MINIMUM MANEUVERING CLEARENCES | | AT DOORS THAT ARE NOT AUTOMATIC OR | | POWER-ASSISTED SHALL BE AS SHOWN IN | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | IN THE REQUIRED CLEARENCES SHALL BE | | CLEAR & LEVEL. | | | | 2) PLANS INDICATE THE USE OF A FIRE | | ALARM AND FIRE SPRINKLERS ? | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2004-01-29 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-01-29 |
Time |
08:57 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2004-01-29 |
Time |
08:52 |
Sent To |
|
|
Notes |
2004-01-29 00:00:00 | **** REDLINED *** | | | | AS ON PREVIOUS REVIEW. WROTE ARCH'S | | LICENSE # ON TITLE BLOCK AS REQD' UNDER | | FS 481.219, 221 , FAC 61G1-16. 003.004 | | PLEASE INCLUDE ALL LICENSE #'S ON TITLE | | BLOCK IN THE FUTURE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2004-01-02 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-01-02 |
Time |
15:27 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2004-01-02 |
Time |
15:21 |
Sent To |
|
|
Notes |
2004-01-02 00:00:00 | WROTE ARCH'S LICENSE # ON TITLE BLOCK | | OF ELECTRICAL SHEETS. | | LICENSE # FOR ARCH ALONG WITH FIRM | | LICENSE # IS REQ'D ON TITLE BLOCK PER | | FAC 61G1-16.004 | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2004-01-29 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2004-01-29 |
Time |
07:09 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2004-01-29 |
Time |
07:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2004-01-02 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2004-01-02 |
Time |
15:00 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2004-01-02 |
Time |
15:00 |
Sent To |
|
|
Notes |
2004-01-02 00:00:00 | 1) COULD NOT LOCATE ANY NEW OR | | EXISTING FIRE ALARM EQUIPMENT ON | | PLANS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2004-01-23 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-01-23 |
Time |
14:33 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-01-23 |
Time |
14:33 |
Sent To |
|
|
Notes |
2004-01-23 00:00:00 | TO COMM BD#57 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-12-23 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-12-23 |
Time |
13:56 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-12-23 |
Time |
13:56 |
Sent To |
|
|
Notes |
2003-12-23 00:00:00 | TO COMM BD#29 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2004-01-29 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-01-29 |
Time |
17:17 |
Rev Time |
0.33 |
Received By |
pkrauss |
Date |
2004-01-29 |
Time |
17:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2004-01-07 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-01-07 |
Time |
06:58 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2004-01-07 |
Time |
06:48 |
Sent To |
|
|
Notes |
2004-01-07 00:00:00 | DENIED: | | 1.FIRE DAMPER IS NOT INDICATED ON THE | | EXISTING HIGH PRESSURE DUCT PENETRATING | | THE WALL IN OFFICE #100.PLEASE VERIFY | | EXISTING OR NEW FIRE DAMPER AS REQUIRED | | PER 2001 FBC(M) 607.1.2 & 607.6. | | | | 2.RETURN AIR GRILLES (NEW OR EXISTING) | | NOT SHOWN IN OFFICE AREAS. | | | | 3.PLEASE NOTE, NO COMBUSTIBLES ALLOWED | | ABOVE THE CEILING IN THE RETURN AIR | | PLENUM.2001 FBC(M) 602.2.1. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2004-01-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-01-14 |
Time |
11:07 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2004-01-14 |
Time |
11:07 |
Sent To |
|
|
Notes |
|
|