Plan Review Details - Permit 03121403
Plan Review Stops For Permit 03121403
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-10-19 Cont ID  
Sent By rmcdouga Date 2004-10-19 Time 15:46 Rev Time 0.00
Received By rmcdouga Date 2004-10-19 Time 15:46 Sent To  
Notes
2004-10-19 00:00:00REVISION TO SHEET 4/7 IS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-08-24 Cont ID  
Sent By csiegber Date 2004-10-15 Time 09:50 Rev Time 0.00
Received By rmcdouga Date 2004-08-24 Time 15:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-07-23 Cont ID  
Sent By dpalmer Date 2004-08-23 Time 15:11 Rev Time 2.00
Received By rmcdouga Date 2004-07-23 Time 15:39 Sent To  
Notes
2004-07-23 00:00:00DENIED
  
 1) SUBMIT A COPY OF THE RECORDED UNITY
 OF TITLE FOR THE TWO LOTS.
  
 2) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL. THE REPORT SUBMITTED DOES NOT
 MEET THE REQUIREMENTS OF FBC 1804.2.2.
 THE REPORT IS ALSO REQUIRED TO BE SIGNED
 AND SEALED BY THE SOIL ENGINEER.
  
 3) SPECIFY THE LENGTH/EMBED DEPTH OF THE
 5/8" J-BOLT FOR THE SIMPSON MGT TRUSS
 ANCHOR.
  
 4)FBC 1005.4.5 (GLITCH AMENDMENTS
 JULY 1, 2003) REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-25 Cont ID  
Sent By dpalmer Date 2004-07-20 Time 13:57 Rev Time 2.50
Received By rmcdouga Date 2004-06-25 Time 07:23 Sent To  
Notes
2004-06-25 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SUBMIT A COPY OF THE PAID RECEIPT FOR
 THE COUNTY IMPACT FEES.
  
 3) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 4)ON SHEET 3 STRUCTURAL NOTE 6 SPECIFIES
 THAT REINFORCING STEEL BE LAPPED 48 BAR
 DIAMETERS. THE FILLED CELL DETAIL ON
 SHEET 1 AND COLUMN NOTE 1 ON 3 SPECIFY
 SPECIFY 30 BAR DIAMETERS. PLEASE CORRECT
  
 5) THE UPLIFTS FOR THE 2 MEMBER GIRDER
 ARE 2852PSF AND 2808PSF EXCEED THE
 UPLIFT CAPACITY OF 1215# SPECIFIED FOR
 THE HUS 26-2 IN DETAIL A ON SHEET 4.
  
 6)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT
 PRODUCT APPROVALS FOR THE FOLLOWING:
 - STRUCTURAL MULLIONS
 - OUTSWING GLAZED DOOR (FL PRODUCT
 APPROVAL DOES NOT MATCH NOA SUBMITTED)
 - OVERHEAD GARAGE DOOR (FL# IS NOT
 CORRECT, PARTS OF REPORT SUBMITTED ARE
 ILLEGIBLE)
  
 IF YOU HAVE QUESTIONS CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-08-23 Cont ID  
Sent By dpalmer Date 2004-08-23 Time 15:11 Rev Time 0.33
Received By dpalmer Date 2004-08-23 Time 15:11 Sent To B
Notes
2004-08-23 00:00:00REDLINED
 210.8A6
 210.12
  
  
 **2002 NEC

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-07-20 Cont ID  
Sent By csiegber Date 2004-08-20 Time 14:54 Rev Time 0.33
Received By dpalmer Date 2004-07-20 Time 13:37 Sent To B
Notes
2004-07-20 00:00:00*** UNSAT ***
  
 1)NOTE: ELECTRICAL PLANS OK,
 PLEASE SEE FBC 104.2.1, PLANS ARE
 REQUIRED TO HAVE PRINTED NAME AND
 SIGNATURE OF PERSON RESPONSIBLE FOR
 PLANS.
 PLEASE HAVE PLANS SIGNED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-06-11 Cont ID  
Sent By csiegber Date 2004-07-16 Time 16:45 Rev Time 0.50
Received By dpalmer Date 2004-06-11 Time 07:59 Sent To M
Notes
2004-06-11 00:00:00*********** UNSAT *************
  
 PLANS WENT OUT W/OUT ALL REVIEWS BEING
 DONE. PLANS ARE BEING SENTTO
 RESIDENTIAL RACK FOR OTHER TRADE REVIEWS
  
 1)NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING. ONE SET HAS REDLINED AREAS.
  
 2)NOTE: PLEASE SEE 210.52C-3 FOR PENIN-
 -SULAR RECEPT.
  
 3)NOTE: PLEASE SEE CORNERS OF HOUSE
 SHOW SCONCES AS SHOWN ON FRONT OF GARAGE
 ? PLEASE SEE PLANS DO NOT INDICATE TYPE
 FIXTURE AND/OR CONTROL FOR THESE.
  
 4)NOTE: PLEASE SEE PANEL SHOWS A MCB,
 AND A MAIN DISCONNECT ON OUTSIDE OF
 HOUSE. THIS IS PERMITTED, HOWEVER IT IS
 NOT REQUIRED. IF SHOWN THIS WAY ON PLANS
 THEN THEY BOTH WILL BE REQUIRED TO BE
 INSTALLED. THIS IS ONLY A NOTE.
  
 5)NOTE: PLEAS VERIFY HEAT/ KW FOR AHU.
 MECH PLANS DO NOT INDICATE HEAT STRIP
 SIZE?
 THIS IS ALSO ONLY A NOTE. IF HEAT IS
 10KW, PLEASE ADJUST OCP ON PANEL SCHED-
 -ULE AND LOAD CALCS. 424.3B
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-31 Cont ID  
Sent By csiegber Date 2004-06-10 Time 09:51 Rev Time 0.50
Received By dpalmer Date 2003-12-31 Time 15:22 Sent To Z
Notes
2004-01-02 00:00:00PLANS TAKEN BY ZONING, 1/2/04
2003-12-31 00:00:00************** UNSAT ***************
  
 ********** NOTE *******
 UNABLE TO COMPLETE PLAN REVIEW AT THIS
 TIME, PLANS ARE MISSING RISER DIAGRAM
 ETC.
  
 1)NOTE: PLEASE CORRELATE PLANS, 200A AND
 250A IS SHOWN.
  
 2)NOTE: PLEASE SHOW COMPLETE RISER DIA-
 -GRAM, SEC'S, AWG, OCP, GROUNDING ELEC--
 TRODE SYSTEM ETC. 110.9, 250.50, 310.15
 B6 ETC.
  
 3)NOTE: PLEASE SEE 210.52
  
 4)NOTE: PLEASE SEE 210.52D AND 210.11C3
 FOR BATH CIRCUIT(S). SHOWS BATHS ALL ON
 ONE.
  
 5)NOTE: PLEASE SEE PLANS NOTE , PER
 PALM BEACH COUNTY, PLEASE ADJUST TO
 CITY OF WPB.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-10-15 Cont ID  
Sent By csiegber Date 2004-10-15 Time 09:50 Rev Time 0.00
Received By csiegber Date 2004-10-15 Time 09:50 Sent To B
Notes
2004-10-15 00:00:00TO RM DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-08-20 Cont ID  
Sent By csiegber Date 2004-08-20 Time 14:54 Rev Time 0.00
Received By csiegber Date 2004-08-20 Time 14:54 Sent To E
Notes
2004-08-20 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-07-16 Cont ID  
Sent By csiegber Date 2004-07-16 Time 16:45 Rev Time 0.00
Received By csiegber Date 2004-07-16 Time 16:45 Sent To E
Notes
2004-07-16 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-10 Cont ID  
Sent By csiegber Date 2004-06-10 Time 09:51 Rev Time 0.00
Received By csiegber Date 2004-06-10 Time 09:51 Sent To E
Notes
2004-06-10 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-08 Cont ID  
Sent By mmclean Date 2004-06-09 Time 16:40 Rev Time 0.00
Received By csiegber Date 2004-06-08 Time 11:12 Sent To Z
Notes
2004-06-08 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-02 Cont ID  
Sent By sgraham Date 2004-01-02 Time 12:13 Rev Time 0.00
Received By csiegber Date 2003-12-23 Time 11:32 Sent To  
Notes
2003-12-29 00:00:0012/23/03TO Z
 12/29/03TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-06-14 Cont ID  
Sent By dpalmer Date 2004-06-11 Time 07:59 Rev Time 0.35
Received By pkrauss Date 2004-06-14 Time 10:16 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-06-17 Cont ID  
Sent By pkrauss Date 2004-06-14 Time 10:32 Rev Time 0.33
Received By jleech Date 2004-06-17 Time 19:35 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-06-09 Cont ID  
Sent By mmclean Date 2004-06-09 Time 16:40 Rev Time 0.00
Received By mmclean Date 2004-06-09 Time 16:40 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-01-02 Cont ID  
Sent By csiegber Date 2004-06-08 Time 11:12 Rev Time 0.00
Received By sgraham Date 2003-12-24 Time 12:38 Sent To I
Notes
2004-01-02 00:00:00ILLEGAL SUBDIVISION, 40 FT LOTS ARE
 NOT LEGALLY PLATTED.