Plan Review Details - Permit 03121324
Plan Review Stops For Permit 03121324
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-03-11 Cont ID  
Sent By shill Date 2004-03-11 Time 17:04 Rev Time 1.00
Received By shill Date 2004-03-11 Time 17:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-03-06 Cont ID  
Sent By csiegber Date 2004-03-11 Time 13:16 Rev Time 4.00
Received By shill Date 2004-03-06 Time 15:26 Sent To  
Notes
2004-03-06 00:00:00****CORRECTIONS****
  
 SAME COMMENTS APPLY TO #03121335,
 03121308, 03121290, 03121280,03121251.
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE NOTICE OF COMMENCEMENT EXPIRES
 AFTER 90 IF WORK HAS NOT COMMENCED
 REGARDLESS OF THE EXPIRATION DATE ON
 THE NOC.
  
 2.)SHEET S1 SHOWS THE WATERSTOP AT
 3/4" RATHER THAN 1 1/2", SEE PREVIOUS
 LIST #2, CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2111.1.9.ALSO
 REVISE NOTE4, FOUNDATION PLAN NOTES,
 S1.
  
 3.)SEE PREVIOUS LIST, ITEM #3,
 BOTTOM CHORD LIVE LOAD IS REQUIRED TO
 BE 10, 30 IN ATTICS WITH STORAGE,
 FBC1604.1 (SHEET S8, #9).
  
 4.)PRODUCT APPROVALS NOT SUBMITTED
 BEFORE ISSUANCE WILL REQUIRE SEPARATE
 PERMITS WITH ADDITIONAL FEES. HORIZONTAL
 ROLLER NOT SUBMITTED; SLIDING GLASS
 DOOR REQUIRES A SITE SPECIFIC OR LOCAL
 PRODUCT APPROVAL FORM WHICH IS FILLED
 OUT IN ITS ENTIRETY.
  
 5.)SEE PREVIOUS LIST, ITEM #7.PROVIDE
 THE IMPACT FEE STAMP.
  
 6.)PROVIDE A STATEWIDE PRODUCT
 APPROVAL NUMBER FOR CONNECTOR DTC.IF
 ONE IS NOT AVAILABLE, A SITE SPECIFIC OR
 LOCAL PRODUCT APPROVAL IS REQUIRED.
  
 7.)ADDITIONAL FEES DUE.
  
 8.)THE FOLLOWING DETAILS SPECIFY A
 BRAND OF CONNECTOR WITHOUT A MODEL
 NUMBER:1-S2, 1-S8, 1-S12, 2-S12.
 CHECK ALL CONNECTORS.SPECIFY A MODEL
 NUMBER AND PROVIDE A STATEWIDE PRODUCT
 APPROVAL NUMBER.IF ONE IS NOT
 AVAILABLE, APPLY FOR EITHER A SITE
 SPECIFIC OR LOCAL PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-01-22 Cont ID  
Sent By csiegber Date 2004-01-20 Time 16:54 Rev Time 0.50
Received By shill Date 2004-01-22 Time 09:18 Sent To  
Notes
2004-01-22 00:00:00THE TWO SETS OF PLANS SUBMITTED DO NOT
 MATCH - CONTRACTOR TO INFORM WHICH PLAN
 TO REVIEW PER TEL CALL W/MARIANA
 REVIEW PLANS WHICH MASTER AS PER
 MARIANA - PULLED OTHER SET OUT FOR
 CONTRACTOR P/U
 *****CORRECTIONS/PROVISO******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 ADDRESS ALL BUILDING CORRECTIONS AT THIS
 TIME IF THE PLANS DO NOT PASS OTHER
 TRADES!!!!!
  
 COMMENTS ALSO APPLY TO 03121290,
 03121308, 03121324, 03121335, 03121280
  
 1.)THE NOTICE OF COMMENCEMENT IS
 EXPIRED FS713.13 (90 DAYS WITHOUT
 COMMENCING WORK).
  
 2.)S-1, WATERSTOP TO BE 1 1/2" CITY
 OF WEST PALM BEACH AMENDMENTS TO THE FBC
 2111.1.9.CHECK ALL DETAILS.
  
 3.)BOTTOM CHORD LIVE LOAD IS REQUIRED
 TO BE 10, 30 IN ATTICS WITH STORAGE,
 FBC TABLE 1604.1 (SHEET S8, #9).
  
 THE FOLLOWING COMMENTS MUST BE
 ADDRESSED BEFORE THE PERMIT CAN BE
 ISSUED - NO PROVISO
  
 4.) SUBMIT TWO COMPLETE PACKAGES OF
 CURRENT PRODUCT APPROVALS WITH ONLY
 ITEMS TO BE INSTALLED ON THIS JOB.
  
 PRODUCT APPROVALS NOT SUBMITTED BEFORE
 ISSUANCE WILL REQUIRE SEPARATE PERMITS
 WITH ADDITIONAL FEES FOR THOSE ITEMS.
  
 5.)FLORIDA STATEWIDE PRODUCT APPROVALS
 OR SITE SPECIFIC REQUIRED, SEE DCA
 WEBSITE AT WWW.FLORIDABUILDING.ORG.
 RULE 9B-72 EFFECTIVE OCTOBER 1, 2003.
  
 6.)SUBMIT A HURRICANE INSTALLATION
 SCHEDULE, SEE ATTACHED.IF THIS IS NOT
 SUBMITTED BEFORE TIME OF PERMIT
 ISSUANCE A SEPARATE PERMIT FOR THIS
 ITEM WILL BE REQUIRED.
  
 7.)PROVIDE THE IMPACT FEE STAMP.THE
 RECEIPT IS IN THE PACKAGE BUT THE PLANS
 ARE NOT STAMPED.
  
 8.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 9.)PROVIDE AREA CALCULATIONS FOR
 EACH UNIT; A/C AREA, NON A/C AREA, AND
 TOTAL.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-03-05 Cont ID  
Sent By dpalmer Date 2004-03-05 Time 13:14 Rev Time 0.50
Received By dpalmer Date 2004-03-05 Time 13:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-03-01 Cont ID  
Sent By dpalmer Date 2004-03-01 Time 07:27 Rev Time 0.33
Received By dpalmer Date 2004-03-01 Time 07:27 Sent To  
Notes
2004-03-01 00:00:00***********UNSAT *************
  
 PLEASE SEE NOTES FROM FIRST REVIEW.
  
 1)NOTE: PLEASE PROVIDE ADDRESS IN TITLE
 BLOCK/ A MIN OF LOT # IS REQ'D.
 FAC 61G1-16.004
  
 2)NOTE: PLEASE HAVE ALL CIRCUITING
 CONFORM TO 2002 NEC 210.12B.
 PLEASE SEE CIRCUITS #'S 13/15.
  
 3)NOTE: PLEASE SEE SD'S ARE SHOWN ON
 MULTIPLE CIRCUITS. PLEASE SEE NFPA-72
 8-1.4.1.6.2 ALL SD'S ARE TO BE WIRED
 IN-LINE.
  
 4)NOTE: PLEASE REMOVE ALL OLD VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS FOR REVIEW AND STAMPING.
  
 PLANS/PERMIT APPLICATION/COMPUTER MAY
 NO LONGER REFERENCE A MASTER WHEN THE
 CODE HAS CHANGED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-29 Cont ID  
Sent By dpalmer Date 2004-01-29 Time 13:47 Rev Time 1.25
Received By dpalmer Date 2004-01-29 Time 13:47 Sent To  
Notes
2004-01-29 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE PROVIDE ADDRESS ON PLANS
 FOR JOBSITE. REQ'D ON TITLE BLOCK PER
 FAC 61G1-16.004
  
 2)NOTE: PLEASE SEE NOTES ON PLANS
 REFERENCE THE SFBC, AND THE 1999 NEC
 WHICH ARE NO LONGER IN EFFECT. PLEASE
 ADJUST NOTES AND ALL CODES REFERENCED
 ON PLANS. NEED TO CORRELATE TO THE 2002
 NEC
  
 3)NOTE: PLEASE PROVIDE CIRCUITING #'S ON
 PLANS AND PANEL SCHEDULES TO PROVIDE
 ARC FAULT PROTECTION AS REQ'D NOW UNDER
 THE 2002 NEC. AS SHOWN IS REQUIREMENTS
 UNDER 1999 NEC.
 2002 NEC WAS ADOPTED BY THE STATE JULY
 1ST ,2003.
  
 4)NOTE: PLEASE SEE REFERENCE FOR GROUND-
 ING ELECTRODE SYSTEM. SHOWN FOR 1999,
 CODE CHANGED FOR 2002.
  
 5)NOTE: PLEASE SEE NOTES FORM ANY OTHER
 REVIEWERS AS THEY MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT TWO COMPLETE SETS. ONLY
 ONE HERE FOR REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-02-20 Cont ID  
Sent By mcarsill Date 2004-02-20 Time 16:19 Rev Time 0.00
Received By mcarsill Date 2004-02-20 Time 16:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-01-29 Cont ID  
Sent By mcarsill Date 2004-01-29 Time 07:54 Rev Time 0.00
Received By mcarsill Date 2004-01-29 Time 07:54 Sent To  
Notes
2004-01-29 00:00:001) WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 2) BUILDING ADDRESSES ARE REQUIRED.
  
 3) PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 4) EGRESS WINDOWS SHALL COMPLY WITH
 BUILDING AND FIRE CODE REQUIREMENTS.
  
 THESE COMMENTS ARE ALSO FOR PERMIT
 NUMBERS 03121335, 03121308, 03121290,
 03121251, 03121280.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-05-14 Cont ID  
Sent By csiegber Date 2004-05-14 Time 12:48 Rev Time 0.00
Received By csiegber Date 2004-05-14 Time 12:48 Sent To P
Notes
2004-05-14 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-03-11 Cont ID  
Sent By csiegber Date 2004-03-11 Time 13:16 Rev Time 0.00
Received By csiegber Date 2004-03-11 Time 13:16 Sent To B
Notes
2004-03-11 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-02-18 Time 12:31 Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 12:31 Sent To  
Notes
2004-02-18 00:00:00TO COMM BD#52

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-22 Cont ID  
Sent By csiegber Date 2004-01-22 Time 09:58 Rev Time 0.00
Received By csiegber Date 2004-01-22 Time 09:58 Sent To  
Notes
2004-01-22 00:00:00TO COMM BD#51

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-20 Cont ID  
Sent By csiegber Date 2004-01-20 Time 16:54 Rev Time 0.00
Received By csiegber Date 2004-01-20 Time 16:54 Sent To B
Notes
2004-01-20 00:00:00TO SH DESK/MASTERED/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-02 Cont ID  
Sent By pkrauss Date 2004-02-02 Time 14:40 Rev Time 0.00
Received By csiegber Date 2003-12-19 Time 14:20 Sent To  
Notes
2003-12-23 00:00:00TO HP DESK/MASTERED

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-03-03 Cont ID  
Sent By pkrauss Date 2004-03-03 Time 09:37 Rev Time 0.25
Received By pkrauss Date 2004-03-03 Time 09:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-02-02 Cont ID  
Sent By pkrauss Date 2004-02-02 Time 14:00 Rev Time 0.55
Received By pkrauss Date 2004-02-02 Time 13:51 Sent To  
Notes
2004-02-02 00:00:00DENIED
 COMMENTS PERTAIN TO THE FOLLOWING PERMIT
 NUMBERS:03121251, 03121290, 03121308,
 03121324, 03121335, 03121280
  
 MODEL A, B, AND C
 1.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 402.2 OR 403.3.
  
 2.RETURN AIR TRANSFER GRILLE FROM THE
 MASTER BEDROOM IS NOT SIZED PROPERLY.
 REFERENCE 2001 FBC(M) 601.4 EXCEPTION #2
 AND 3. GRILLES SHALL HAVE 50 SQ INCHES
 TO 100 CFM OF SUPPLY AIR.FOR PROPER
 SIZING FOR THE RETURN TRANSFER GRILLE TO
 THE MASTER BEDROOM, ALL SUPPLY AIR TO
 THE SUITE IS TO BE INCLUDED IN THE
 CALCULATION.PLEASE REVISE.
  
 3.AUXILIARY DRAIN PAN REQUIRED PER
 2001 FBC(M) 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-06-02 Cont ID  
Sent By jleech Date 2004-06-02 Time 19:47 Rev Time 0.15
Received By jleech Date 2004-06-02 Time 19:47 Sent To  
Notes
2004-06-02 00:00:00REV. H2O PIPE FROM COPPER TO CPVC

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-03-03 Cont ID  
Sent By csiegber Date 2004-05-14 Time 12:48 Rev Time 0.50
Received By kstevens Date 2004-03-03 Time 18:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-31 Cont ID  
Sent By kstevens Date 2004-01-31 Time 11:59 Rev Time 0.33
Received By kstevens Date 2004-01-31 Time 11:59 Sent To  
Notes
2004-01-31 00:00:00DENIED
 REFERENCE: FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
  
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
  
 PER FBPE'S RULING INITIALS ARE NOT
 ACCEPTABLE. SUBMIT A COPY OF YOUR
 SIGNATURE WITH A COPY OF YOUR LICENSE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-22 Cont ID  
Sent By mmclean Date 2003-12-22 Time 12:44 Rev Time 0.00
Received By mmclean Date 2003-12-22 Time 12:44 Sent To I
Notes
***NONE***