Plan Review Details - Permit 03121201
Plan Review Stops For Permit 03121201
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-02-20 Cont ID  
Sent By lsmith Date 2004-02-20 Time 16:23 Rev Time 2.50
Received By lsmith Date 2004-02-20 Time 16:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-02 Cont ID  
Sent By jleech Date 2004-02-19 Time 12:47 Rev Time 0.00
Received By lsmith Date 2004-02-02 Time 11:35 Sent To  
Notes
2004-02-02 00:00:00BUILDING PLAN REVIEW: FAILED!!
  
  
 1. SURVEY SAYS STRUCTURE IS IN A "B"
 ZONE. MAPS SHOW "AO" REQUIRING A
 COMPLETED ELEVATION CERTIFICATE.
  
 2. THE TYPE OF CONSTRUCTION SHOWN ON
 SHEET A0.01 HAS BEEN CHANGED TO TYPE
 V. ACCORDING TO TABLE 600 IT SHOULD BE
 A TYPE "VI" ZONE. CORRECT NOTES.
  
 3. A SIGNED AND SEALED COPY OF THE SOIL
 REPORT MUST BE SUBMITTED.
  
 4. CORRECT DETAIL FOR GLASS BLOCK TO
 COMPLY WITH 1 HOUR ASSEMBLY ON ZERO LOT
 LINE.
  
 5. PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 6. TERMITE PROTECTION: A SOIL BAIT
 TREATMENT IS THE METHOD DESCRIBED IN
 SEC. 1816.1.7.A SIGNED CONTRACT IS
 REQUIRED TO BE SUBMITTED ASSURING THE
 INSTALLATION, MAINTENANCE, & MONITORING
 OF THE BAITING SYSTEM FOR A MINIUM OF
 FIVE (5) YEARS. SEE FBC 1816 TERMITE
 PROTECTION.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-02-19 Cont ID  
Sent By dpalmer Date 2004-02-19 Time 11:09 Rev Time 0.33
Received By dpalmer Date 2004-02-19 Time 11:09 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-31 Cont ID  
Sent By csiegber Date 2004-02-11 Time 14:18 Rev Time 0.33
Received By dpalmer Date 2003-12-31 Time 10:16 Sent To M
Notes
2003-12-31 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SEE THAT PLANS REF 1999
 NEC. AS OF 7/1/03 WE ARE UNDER 2002 NEC
 PLEASE ADJUST ALL CODES AND NOTES REF
 1999
  
 2)NOTE: PLEASE HAVE PLANS SIGNED BY
 ENGINEER OF RECORD. FS 471.025 AND
 FAC 61G15-23.002
  
 3)NOTE: PLEASE SEE 210.12 OF THE 2002
 NEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 14:18 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 14:17 Sent To E
Notes
2004-02-11 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-02 Cont ID  
Sent By mmclean Date 2003-12-19 Time 16:20 Rev Time 0.00
Received By csiegber Date 2003-12-19 Time 09:56 Sent To  
Notes
2003-12-22 00:00:00TO SFD RACK/E
2003-12-19 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-15 Cont ID  
Sent By hmoser Date 2004-01-15 Time 17:06 Rev Time 0.25
Received By hmoser Date 2004-01-15 Time 17:06 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-01-05 Cont ID  
Sent By dpalmer Date 2003-12-31 Time 10:17 Rev Time 0.20
Received By pkrauss Date 2004-01-05 Time 08:35 Sent To P
Notes
2004-01-05 00:00:00MECHANICAL PLANS NOT SUBMITTED, PER
 CONVERSATION W/MARIANNA, MECHANICAL
 CONTRACTOR TO SUBMIT PLANS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-02-19 Cont ID  
Sent By jleech Date 2004-02-19 Time 12:47 Rev Time 0.33
Received By jleech Date 2004-02-19 Time 12:46 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-17 Cont ID  
Sent By dpalmer Date 2004-02-19 Time 11:11 Rev Time 0.33
Received By kstevens Date 2004-01-17 Time 09:19 Sent To B
Notes
2004-01-17 00:00:00DENIED
 REFERENCE: FLA. ADMIN CODE
 FLA. STATUTES
  
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1) - PER THE
 RULING BY FBPE INITALS ARE NOT ACCEPT-
 ABLE. FS 471.025.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-19 Cont ID  
Sent By mmclean Date 2003-12-19 Time 16:20 Rev Time 0.00
Received By mmclean Date 2003-12-19 Time 16:20 Sent To I
Notes
***NONE***