Plan Review Details - Permit 03121198
Plan Review Stops For Permit 03121198
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-03-08 Cont ID  
Sent By rmcdouga Date 2004-03-08 Time 13:42 Rev Time 2.00
Received By rmcdouga Date 2004-03-08 Time 13:42 Sent To  
Notes
2004-03-08 00:00:00BUILDING PROVISO
  
 1) STRUCTURE IS IN AN "AO" FLOOD ZONE AN
 ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 2) SUBMIT A COPY OF THE RECORDED
 REVISION TO THE SUBDIVISION COVENANTS
 CREATING AN EMERGENCY EGRESS EASEMENT
 ACROSS THE ADJACENT PROPERTY ON THE ZERO
 LOT LINE SIDE. A C.O. CAN NOT BE ISSUED
 UNTIL THIS ITEM HAS BEEN APPROVED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-02-23 Cont ID  
Sent By csiegber Date 2004-03-01 Time 10:10 Rev Time 2.50
Received By rmcdouga Date 2004-02-23 Time 09:10 Sent To  
Notes
2004-02-23 00:00:00DENIED
  
 1) THE STRUCTURE IS LOCATED IN AN "AO"
 ZONE AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 2) 1001.1.3/ 1005.4 ZERO LOT LINE
 EGRESS:WHEN ACCESS TO OR FROM A RE-
 QUIRED EMERGENCY ESCAPE AND RESCUE OPEN-
 ING OF A STRUCTURE TO THE PUBLIC WAY,
 REQUIRES TRANSVERSING A PROPERTY
 (ADJOINING LOT) THAT IS NOT PART OF THE
 ONE WHICH THE STRUCTURE IS LOCATED, AN
 EGRESS EASEMENT THROUGH THE ADJOINING
 PROPERTY IS REQUIRED AND SHALL BE RECORD
 ED IN THE COUNTY RECORDS. THIS EASEMENT
 SHALL BE A MINIMUM OF 3' WIDE AND NOTH-
 ING SHALL BE PLACED WITHIN THE EASEMENT
 AREA WHICH WOULD BLOCK ACCESS TO THE
 EASEMENT AND OR IMPEDE EMERGENCY EGRESS
 FROM THE RESCUE OPENING TO THE PUBLIC
 WAY. NO LANDSCAPING, FENCES OR OTHER
 IMPEDIMENTS SHALL BE INSTALLED IN THIS
 EASEMENT. SUBMIT A RECORDED COPY OF THE
 SUBDIVISION COVENENTS THAT SPECIFY AN
 EMERGENCY EGRESS AS INDICATED ABOVE.
  
 3)THE PLANS DO NOT SPECIFY A TRANSOM
 WINDOW ABOVE THE ENTRY DOOR. THE STORM
 PANEL KEY PLAN AND INSTALLATION SCHEDULE
 INDICATE A WINDOW AT THIS LOCATION.
 PLEASE CLARIFY.
  
 4) THE PRODUCT APPROVAL FOR THE STORM
 PANELS IS MISSING THE SBCCI EVALUATION
 REPORT.
  
 5) SOME OF THE PANEL SPANS LISTED ON THE
 STORM PANEL SCHEDULE ARE LESS THAN THE
 MINIMUM PANEL LENGTHS SPECIFIED IN TABLE
 5 OF THE PRODUCT APPROVAL. PLEASE
 CORRECT.
  
 6) THE LOCAL PRODUCT APPROVAL FORMS THAT
 WERE SUBMITTED DO NOT LIST A QUALITY
 ASSURANCE ENTITY. PLEASE CORRECT.
  
 7) THE NOA NUMBER ON THE LOCAL PRODUCT
 APPROVAL FORM FOR THE FIXED WINDOW DOES
 NOT MATCH THE MIAMI-DADE NOA THAT IS
 ATTACHED.
  
 8) THE STATE PRODUCT APPROVAL SHEET FOR
 THE FIREDOOR,LLC DOES NOT MATCH THE
 THERMA-TRU NOA THAT IS ATTACHED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-04 Cont ID  
Sent By jleech Date 2004-02-19 Time 13:11 Rev Time 3.00
Received By rmcdouga Date 2004-02-03 Time 16:22 Sent To  
Notes
2004-02-03 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SUBMIT A SIGNED AND SEALED COPY OF
 THE SOIL REPORT.
  
 3) THE STRUCTURE IS LOCATED IN AN "AO"
 FLOOD ZONE. AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 4) THE SURVEY LISTS THE INCORRECT FLOOD
 ZONE AND THE WRONG FIRM MAP NUMBER.
 SUBMIT A CORRECTED SURVEY.
  
 5)1001.1.3/ 1005.4 ZERO LOT LINE
 EGRESS:WHEN ACCESS TO OR FROM A RE-
 QUIRED EMERGENCY ESCAPE AND RESCUE OPEN-
 ING OF A STRUCTURE TO THE PUBLIC WAY,
 REQUIRES TRANSVERSING A PROPERTY
 (ADJOINING LOT) THAT IS NOT PART OF THE
 ONE WHICH THE STRUCTURE IS LOCATED, AN
 EGRESS EASEMENT THROUGH THE ADJOINING
 PROPERTY IS REQUIRED AND SHALL BE RECORD
 ED IN THE COUNTY RECORDS. THIS EASEMENT
 SHALL BE A MINIMUM OF 3' WIDE AND NOTH-
 ING SHALL BE PLACED WITHIN THE EASEMENT
 AREA WHICH WOULD BLOCK ACCESS TO THE
 EASEMENT AND OR IMPEDE EMERGENCY EGRESS
 FROM THE RESCUE OPENING TO THE PUBLIC
 WAY. NO LANDSCAPING, FENCES OR OTHER
 IMPEDIMENTS SHALL BE INSTALLED IN THIS
 EASEMENT.
  
 6) SHEET A0.01 LISTS THE CONSTRUCTION
 TYPE III. BASED ON FBC TABLE 600 AND THE
 PLANS THE CONSTRUCTION IS TYPE VI.
  
 7) NOTE 22 ON A0.01 REFERS TO FBC
 1816.1.7, WHICH IS FOR TERMITE BAITING
 SYSTEMS. PLEASE CLARIFY. NOTE: A SIGNED
 CONTRACT PAID IN FULL FOR 5 YEARS FROM
 THE DATE OF CO IS REQUIRED BEFORE THE
 SLAB IS POURED.
  
 8) REVISE THE DRYWALL FASTENING NOTE ON
 A3.01. THE FASTENER SPACING FOR SCREWS
 IS NOT MORE THAN 12"OC PER FBC 2504.4.1
 AND GA 216.
  
 9) REVISE DETAIL 2 ON A4.01 TO SHOW
 FIREBLOCKING WHERE THE WALL AND CEILING
 MEET. SEE FBC 2305.1.
  
 10) REVISE THE GLASS BLOCK DETAIL 10 ON
 A4.02 TO A ONE HOUR FIRE RATED ASSEMBLY.
 SEE UL R2556.
  
 11) SPECIFY THE ATTIC LIVE LOADS ON S2.
 FBC TABLE 1604.1 REQUIRES 30PSF FOR
 ATTICS WITH STORAGE AND 10PSF FOR ATTICS
 WITHOUT STORAGE.
  
 12) THE KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS INDICATE
 A GLAZED WINDOW ABOVE THE ENTRY DOORS.
 THIS IS NOT SHOWN ON THE PLANS. PLEASE
 CLARIFY.
  
 13) ITEM #4 IN THE DOOR SCHEDULE IS
 LISTED AS A 6'- 8" WIDE SLIDING GLASS
 DOOR AND THE FLOOR PLAN SHOWS A 6' WIDE
 OPENING. PLEASE CORRECT.
  
 14) THE KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS CONTAIN
 SOME ERRORS. CHECK THE OPENING SIZES AND
 MINIMUM PANEL LENGTH AS LISTED IN THE
 PRODUCT APPROVAL. PLEASE CORRECT.
  
 15) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-02-19 Cont ID  
Sent By dpalmer Date 2004-02-19 Time 10:06 Rev Time 0.33
Received By dpalmer Date 2004-02-19 Time 10:06 Sent To P
Notes
2004-02-19 00:00:00REDLINED 210.12, 2002 NEC.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-31 Cont ID  
Sent By csiegber Date 2004-02-18 Time 11:03 Rev Time 0.33
Received By dpalmer Date 2003-12-31 Time 07:27 Sent To M
Notes
2003-12-31 00:00:00************** UNSAT ***********
  
 1)NOTE: PLEASE HAVE PLANS SIGNED WITH
 A COMPLETE SIGNATURE FROM ENGINEER OF
 RECORD. PER FS 471.025 AND FAC 61G15-23.
 002.
  
 2)NOTE: PLEASE SEE THAT PLANS STILL
 REFERENCE THE 1999 NEC. PLEASE ADJUST
 ALL CODES REFERENCED ON PLANS.
 AS OF 7/1/03WE ARE UNDER THE 2002 NEC
  
 3)NOTE: PLEASE SEE 2002 ART 210.12.
 ARC FAULT PROTECTION HAS CHANGED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-01 Cont ID  
Sent By csiegber Date 2004-03-01 Time 10:08 Rev Time 0.00
Received By csiegber Date 2004-03-01 Time 10:08 Sent To B
Notes
2004-03-01 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-02-18 Time 11:03 Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 11:02 Sent To E
Notes
2004-02-18 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-04 Cont ID  
Sent By mmclean Date 2003-12-19 Time 16:28 Rev Time 0.00
Received By rmcdouga Date 2003-12-19 Time 09:17 Sent To  
Notes
2003-12-22 00:00:00TO SFD RACK/E
2003-12-19 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-15 Cont ID  
Sent By hmoser Date 2004-01-15 Time 17:18 Rev Time 0.25
Received By hmoser Date 2004-01-15 Time 17:18 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-01-05 Cont ID  
Sent By dpalmer Date 2003-12-31 Time 07:33 Rev Time 0.20
Received By pkrauss Date 2004-01-05 Time 08:38 Sent To P
Notes
2004-01-05 00:00:00PLANS SUBMITTED W/O MECHANICAL PLANS,
 PER CONVERSATION W/MARIANNA, MECHANICAL
 CONTRACTOR TO BRING IN PLANS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-02-19 Cont ID  
Sent By jleech Date 2004-02-19 Time 13:11 Rev Time 0.25
Received By jleech Date 2004-02-19 Time 13:10 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-17 Cont ID  
Sent By dpalmer Date 2004-02-19 Time 10:07 Rev Time 0.33
Received By kstevens Date 2004-01-17 Time 09:10 Sent To B
Notes
2004-01-17 00:00:00DENIED
 REFERENCE: FLA. ADMIN. CODE
 FLA. STATUTES
  
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING IFLED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1) - PER A
 RULING BY FBPE INITIALS ARE NOT ACCEPT-
 ABLE. FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-19 Cont ID  
Sent By mmclean Date 2003-12-19 Time 16:28 Rev Time 0.00
Received By mmclean Date 2003-12-19 Time 16:28 Sent To I
Notes
***NONE***