2004-02-02 00:00:00 | BUILDING PLAN REVIEW: FAILED!! |
| |
| 1. NO RECEIPT SUBMITTED FOR IMPACT FEES |
| PAID TO PBC. (PLANS ARE STAMPED BY PBC) |
| |
| 2. LOT IS LOCATED IN A "AO" FLOOD ZONE. |
| AN ELEVATIONCERTIFICATE WILL BE |
| REQUIRED BEFORE C/O. |
| |
| 3. A SIGNED & SEALED SOIL REPORT MUST BE |
| SUBMITTED. |
| |
| 4. CORRECT DETAIL FOR GLASS BLOCK IN A |
| 1 HOUR ASSEMBLY ON ZERO LOT LINE. |
| |
| 5. PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, |
| 2003ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATIONPLEASE SEE THE STATE WEBSITE |
| AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 6. GENERAL NOTES (A0.01) #22 DESCRIBES |
| TERMITE PROTECTION TO BE A SOIL BAIT |
| TREATMENT METHOD. A SIGNED CONTRACT IS |
| REQUIRED TO BE SUBMITTED ASSURING THE |
| INSTALLATION, MAINTENANCE & MONITORING |
| OF THE BAITING SYSTEM FOR A MINIUM OF 5 |
| YEARS. SEE FBC 1816 TERMITE PROTECTION. |
| PLANS REFERENCE 1816.1.7. |
| |
| 7. ONLY 1 COPY OF THEFLORIDA ENERGY |
| CODE WAS SUBMITTED.SUBMIT ANOTHER SET |
| AND 1 EXTRA COPY OF PAGE 1. |
| |
| ANY QUESTIONS PLEASE CALL: |
| LEA SMITH, BUILDING PLANS EXAMINER |
| 805-6713 |