Plan Review Details - Permit 03121171
Plan Review Stops For Permit 03121171
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-03-03 Cont ID  
Sent By rmcdouga Date 2004-03-03 Time 11:10 Rev Time 1.00
Received By rmcdouga Date 2004-03-03 Time 11:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-02-25 Cont ID  
Sent By mmclean Date 2004-03-03 Time 09:57 Rev Time 1.30
Received By rmcdouga Date 2004-02-25 Time 14:06 Sent To  
Notes
2004-02-25 00:00:00DENIED
  
 1) THE FOOTPRINT OF THE STRUCTURE ON THE
 SURVEY IS THE REVERSE OF THE STRUCTURE
 ON THE ARCHITECTURAL PLANS. REVISE SO
 THAT THE SURVEY AND PLANS ARE AN EXACT
 MATCH.
  
 2) THE FLOOD ZONE AND MAP NUMBER ON THE
 SURVEY IS INCORRECT. SUBMIT A REVISED
 SURVEY. NOTE: THE STRUCTURE IS LOCATED
 IN AN "AO" FLOOD ZONE AN ELEVATION
 CERTIFICATE WILL BE REQUIRED.
  
 3) SUBMIT KEY PLANS FOR THE STORM PANELS
  
 4) THE LOCAL PRODUCT APPROVAL FORMS DO
 NOT LIST A QUALITY ASSURANCE ENTITY.
 PLEASE SUBMIT COMPLETE INFORMATION ON
 THE FORMS.
  
 5) THE COVER SHEET FOR THE ENTRY DOOR
 PRODUCT APPROVALS DOES NOT MATCH THE
 NOA. SUBMIT COVER SHEET AND MATCHING
 NOA.
  
 6) THE NOA # LISTED ON THE LOCAL PRODUCT
 APPROVAL FORM DOES NOT MATCH THE NOA FOR
 THE FIXED IMPACT WINDOW.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-29 Cont ID  
Sent By dpalmer Date 2004-02-25 Time 12:49 Rev Time 2.00
Received By rmcdouga Date 2004-01-29 Time 10:51 Sent To  
Notes
2004-01-29 00:00:00DENIED
  
 1) THE FOOTPRINT OF THE STRUCTURE IS THE
 REVERSE OF THE PLANS. SUBMIT SURVEY AND
 PLANS THAT MATCH.
  
 2) STRUCTURE IS LOCATED IN AN "AO" FLOOD
 ZONE AN ELEVATION CERTIFICATE WILL BE
 REQUIRED BEFORE C.O.
  
 3) SUBMIT A SIGNED AND SEALED COPY OF
 THE SOIL REPORT.
  
 4) THE CONSTRUCTION IS LISTED AS TYPE V
 ON A0.01. BASED ON FBC TABLE 600
 REQUIREMENTS, CONSTRUCTION IS TYPE VI.
 PLEASE CORRECT.
  
 5) NOTE 22 ON A0.01 REFERS TO FBC SECT.
 1816.1.7, WHICH IS FOR TERMITE BAITING
 SYSTEMS. A SIGNED CONTRACT PAID IN FULL
 FOR FIVE YEARS FROM THE DATE OF C.O. IS
 REQUIRED BEFORE THE SLAB IS POURED.
 PLEASE CLARIFY.
  
 6) REVISE THE DRYWALL FASTENING NOTE ON
 A3.01. THE FASTENER SPACING FOR SCREWS
 IS NOT MORE THAN 12"OC FOR CEILINGS AND
 WALLS FOR FRAMING 24"OC.SEE FBC 2504.4.1
 AND GA 216.
  
 7) REVISE THE ROOF SHEATHING FASTENER
 SPACING NOTE ON A1.02 TO CORRESPOND WITH
 THE NOTES ON A3.01 AND S4.
  
 8) REVISE THE GLASS BLOCK DETAIL 10 ON
 A4.02 TO A ONE HOUR FIRE RATED ASSEMBLY.
 SEE UL R2556.
  
 9) SPECIFY THE LENGTH/EMBED DEPTH OF THE
 3/4" DIA. WEDGE ANCHOR BOLTS IN DETAIL 2
 ON S5 AND THE 5/8" DIA. BOLTS IN
 SECTIONS E-E AND F-F ON S5.
  
 10) SPECIFY THE ATTIC LIVE LOADS ON S2.
 FBC TABLE 1604.1 REQUIRES 30 PSF FOR
 ATTICS WITH STORAGE AND 10 PSF FOR THOSE
 WITHOUT STORAGE.
  
 11) THE KEY PLAN AND INSTALLATION
 SCHEDULES FOR THE STORM PANELS DO NOT
 MATCH THE PLANS. CHECK THE NUMBER, SIZES
 AND LOCATIONS OF OPENINGS.
  
 12)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-27 Time 14:35 Rev Time 0.50
Received By dpalmer Date 2004-02-25 Time 12:49 Sent To B
Notes
2004-02-25 00:00:00NEW ELECTRICAL SHEETS BROUGHT IN 2/24/04
 OLD SHEETS WERE LEFT IN.
 REDLINED 210.12, ALL OUTLETS, PER 2002
 NEC.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-29 Cont ID  
Sent By csiegber Date 2004-02-11 Time 14:39 Rev Time 0.33
Received By dpalmer Date 2003-12-29 Time 06:39 Sent To M
Notes
2003-12-29 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE HAVE PLANS SIGNED, DATED
 BY ENGINEER WITH COMPLETE SIGNATURE
 AS PER FS 471.025 AND FAC 61G15-23.002
 PER FBPE'S INITIALS ARE NOT ACCEPTABLE
 AS SIGNATURE.
  
 2)NOTE: PLEASE SEE PLANS STILL REFERENCE
 THE 1999 NEC. THE 2002 NEC WAS ADOPTED
 BY STATE 7/1/03. PLEASE ADJUST ALL CODES
 AND NOTES ON PLANS.
  
 3)NOTE: PLEASE SEE 210.12 FOR ARC FAULT
 PROTECTION. PLEASE SEE THAT THIS HAS
 CHANGED SINCE 1999 NEC. PLEASE ADJUST
 NOTE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 14:37 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 14:37 Sent To B
Notes
2004-02-27 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-21 Cont ID  
Sent By csiegber Date 2004-02-27 Time 14:34 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 14:39 Sent To E
Notes
2004-02-11 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-29 Cont ID  
Sent By mmclean Date 2004-02-27 Time 14:34 Rev Time 0.00
Received By csiegber Date 2003-12-18 Time 16:19 Sent To  
Notes
2003-12-22 00:00:0012/18/03TO Z
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-15 Cont ID  
Sent By jleech Date 2004-01-03 Time 09:23 Rev Time 0.25
Received By hmoser Date 2004-01-15 Time 17:45 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-03 Cont ID  
Sent By jleech Date 2004-01-03 Time 09:23 Rev Time 0.25
Received By jleech Date 2004-01-03 Time 09:23 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-03-03 Cont ID  
Sent By mmclean Date 2004-03-03 Time 09:57 Rev Time 0.00
Received By mmclean Date 2004-03-03 Time 09:57 Sent To B
Notes
2004-03-03 00:00:00RE-STAMP SURVEY (CORRECT)

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-19 Cont ID  
Sent By alange Date 2003-12-18 Time 16:19 Rev Time 0.00
Received By mmclean Date 2003-12-19 Time 15:58 Sent To I
Notes
***NONE***