Plan Review Details - Permit 03121166
Plan Review Stops For Permit 03121166
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-02-24 Cont ID  
Sent By rmcdouga Date 2004-02-24 Time 11:42 Rev Time 2.00
Received By rmcdouga Date 2004-02-24 Time 11:42 Sent To  
Notes
2004-02-24 00:00:00PROVISO
  
 SUBMIT A REVISED SURVEY WITH CORRECTED
 FLOOD ZONE AND FLOOD MAP NUMBER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-21 Cont ID  
Sent By dpalmer Date 2004-02-13 Time 13:54 Rev Time 2.50
Received By rmcdouga Date 2004-01-21 Time 12:22 Sent To  
Notes
2004-01-21 00:00:00DENIED
  
 1) SUBMIT A COPY OF THE IMPACT FEE
 RECIEPT.
  
 2) THE GLASS BLOCK IN THE WALL ON THE
 ZERO LOT LINE IS REQUIRED TO HAVE A ONE
 HOUR FIRE RATING. SEE FBC TABLE 600,
 WHICH REQUIRES THE EXTERIOR WALL TO BE
 FIRE RATED FOR ONE HOUR AND HAVE NO
 OPENINGS.
  
 3) SUBMIT A SIGNED AND SEALED COPY OF
 THE SOIL REPORT.
  
 4) THE CONSTRUCTION TYPE LISTED ON SHEET
 A0.01 IS INCORRECTLY LISTED AS TYPE III.
 BASED ON TABLE 600 REQUIREMENTS, IT IS
 TYPE VI.
  
 5) NOTE 22 ON A0.01 REFERENCES FBC SECT.
 1816.1.7, WHICH IS FOR TERMITE BAITING
 SYSTEMS. PLEASE CLARIFY. NOTE: A SIGNED
 CONTRACT THAT HAS BEEN PAID FOR A MIN.
 OF 5 YEARS FROM THE DATE OF C.O. IS
 REQUIRED BEFORE THE SLAB IS POURED.
  
 6) SPECIFY CONSPICUOUSLY ON THE PLAN
 THAT THE DEN IS NOT TO BE USED AS A
 SLEEPING ROOM.
  
 7) REVISE THE GYPSM FASTENING NOTE ON
 A3.01. THE NAIL SPACING FOR SINGLE
 NAILING IS 7"OC FOR CEILINGS AND 8"OC
 FOR WALLS. THE SPACING FOR SCREWS IS NOT
 MORE THAN 12"OC FOR WALLS AND CEILINGS
 WHEN FRAMING IS 24"OC. SEE FBC 2504.4.1
 AND GA 216.
  
 8) REVISE DETAIL 2 ON A4.01 TO SHOW
 FIREBLOCKING WHERE WALL AND CEILING
 MEET PER FBC 2305.1.
  
 9) DETAIL 10 ON A4.02 IS NOT FOR A FIRE
 RATED GLASS BLOCK ASSEMBLY. PLEASE
 REVISE. SEE UL #R2556.
  
 10) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-02-13 Cont ID  
Sent By dpalmer Date 2004-02-13 Time 13:54 Rev Time 0.33
Received By dpalmer Date 2004-02-13 Time 13:54 Sent To B
Notes
2004-02-13 00:00:00**** NOTES REDLINED**
 ARC FAULT RE'QD FOR ALL OUTLETS,INCLUD-
 -ING LTS/ SD'S. PER 210.12 2002 NEC.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-29 Cont ID  
Sent By csiegber Date 2004-02-05 Time 12:35 Rev Time 0.50
Received By dpalmer Date 2003-12-29 Time 06:29 Sent To M
Notes
2003-12-29 00:00:00************ UNSAT **************
  
 1)NOTE: PLANS STILL REFERENCE THE 1999
 NEC.2002 NEC WAS ADOPTED 7/1/2003.
 PLEASE ADJUST ALL CODES REF AND ADJUST
 NOTES.
  
 2)NOTE: PLEASE SEE 210.12 FOR ARC FAULT
 PROTECTION. THIS HAS CHANGE IN THE 2002
 CODE.
  
 3)NOTE: PLEASE HAVE ENGINEER OF RECORD
 SIGN PLANS WITH FULL NAME. FBPE'S HAS
 NOTED TO THIS OFFICE THAT INITIALS ARE
 NOT ACCEPTABLE. PER FS 471.025
 FAC 61G15-23.002.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-05 Cont ID  
Sent By csiegber Date 2004-02-05 Time 12:35 Rev Time 0.00
Received By csiegber Date 2004-02-05 Time 12:35 Sent To E
Notes
2004-02-05 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-21 Cont ID  
Sent By mmclean Date 2004-02-05 Time 12:36 Rev Time 0.00
Received By csiegber Date 2003-12-18 Time 16:17 Sent To  
Notes
2003-12-22 00:00:0012/18/03 TO Z
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-15 Cont ID  
Sent By jleech Date 2004-01-03 Time 08:57 Rev Time 0.25
Received By hmoser Date 2004-01-15 Time 16:49 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-03 Cont ID  
Sent By jleech Date 2004-01-03 Time 08:57 Rev Time 0.25
Received By jleech Date 2004-01-03 Time 08:56 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-19 Cont ID  
Sent By alange Date 2003-12-18 Time 16:17 Rev Time 0.00
Received By mmclean Date 2003-12-19 Time 16:21 Sent To I
Notes
***NONE***