Plan Review Details - Permit 03121158
Plan Review Stops For Permit 03121158
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-03-02 Cont ID  
Sent By rmcdouga Date 2004-03-02 Time 07:40 Rev Time 2.00
Received By rmcdouga Date 2004-03-02 Time 07:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-27 Cont ID  
Sent By dpalmer Date 2004-02-13 Time 13:31 Rev Time 3.00
Received By rmcdouga Date 2004-01-27 Time 15:15 Sent To  
Notes
2004-01-27 00:00:00DENIED
  
 1) STRUCTURE IS LOCATED IN AN "AO" FLOOD
 ZONE AN ELEVATION CERTIFICATE WILL BE
 REQUIRED BEFORE C.O.
  
 2) SUBMIT A SIGNED AND SEALED COPY OF
 THE SOIL REPORT.
  
 3) SHEET A0.01 LISTS THE CONSTRUCTION AS
 TYPE V. BASED ON FBC TABLE 600, THE
 CONSTRUCTION IS TYPE VI. PLEASE CORRECT.
  
 4) NOTE 22 ON A0.01 REFERS TO FBC
 1816.1.7, WHICH IS FOR TERMITE BAITING
 SYSTEMS. PLEASE CLARIFY. NOTE: A SIGNED
 CONTRACT PAID IN FULL FOR FIVE YEARS
 FROM THE DATE OF C.O. IS REQUIRED BEFORE
 THE SLAB IS POURED.
  
 5) REVISE THE DRYWALL FASTENING NOTE ON
 A3.01 THE FASTENER SPACING FOR SCREWS IS
 NOT MORE THAN 12"OC FOR CEILINGS AND
 WALLS ON FRAMING 24"OC PER FBC 2504.4.1
 AND GA 216.
  
 6) REVISE THE ROOF SHEATHING FASTENER
 SPACING NOTE ON A1.02 TO CORRESPOND WITH
 THE NOTES ON A3.01 AND S4.
  
 7) REVISE DETAIL 2 ON A4.01 TO SHOW
 FIREBLOCKING WHERE THE WALL AND CEILING
 MEET PER FBC 2305.1.
  
 8) REVISE THE GLASS BLOCK DETAIL 10 ON
 A4.02 FOR A ONE HOUR FIRE RATED ASSEMBLY
 SEE UL R2556.
  
 9) SPECIFY THE LENGTH/EMBED DEPTH OF THE
 3/4"DIA. WEDGE ANCHOR BOLTS IN DETAIL 2
 ON S5 AND THE 5/8" DIA. W.A. BOLTS IN
 SECTIONS E-E AND F-F ON S5.
  
 10) SPECIFY THE ATTIC LIVE LOADS ON S2.
 FBC TABLE 1604.1 REQUIRES 30PSF FOR
 ATTICS WITH STORAGE AND 10PSF FOR ATTICS
 WITHOUT STORAGE.
  
 11) THE KEY PLAN AND INSTALLATION
 SCHEDULES FOR THE STORM PANELS DO NOT
 MATCH THE PLANS. CHECK NUMBER AND SIZES
 OF OPENINGS.
  
 12) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-02-13 Cont ID  
Sent By dpalmer Date 2004-02-13 Time 13:30 Rev Time 0.33
Received By dpalmer Date 2004-02-13 Time 13:29 Sent To B
Notes
2004-02-13 00:00:00****** NOTES REDLINED ********
 ARC FAULT PER 2002 NEC AND NOT PER 1999
 AS NOTED ON PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-31 Cont ID  
Sent By csiegber Date 2004-02-11 Time 14:16 Rev Time 0.33
Received By dpalmer Date 2003-12-31 Time 08:33 Sent To M
Notes
2003-12-31 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE SEE PLANS STILL REF 1999
 NEC. PLEASE ADJUST ALL NOTES AND REF
 2002 NEC.
  
 2)NOTE: PLEASE SEE 210.12 OF 2002 NEC
  
 3)NOTE: PLEASE HAVE PLANS SIGNED WITH
 FULL SIGNATURE FROM ENGINEER. FS 471.025
 FAC 61G15-23.002
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 14:16 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 14:16 Sent To E
Notes
2004-02-11 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-27 Cont ID  
Sent By mmclean Date 2004-01-27 Time 09:08 Rev Time 0.00
Received By rmcdouga Date 2003-12-18 Time 16:16 Sent To  
Notes
2003-12-22 00:00:0012/18/03 TO Z
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-15 Cont ID  
Sent By hmoser Date 2004-01-15 Time 17:37 Rev Time 0.50
Received By hmoser Date 2004-01-15 Time 17:37 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-05 Cont ID  
Sent By dpalmer Date 2003-12-31 Time 08:33 Rev Time 0.33
Received By pkrauss Date 2004-01-05 Time 08:45 Sent To P
Notes
2004-01-05 00:00:00DENIED:
 PLAN IS NOT LEGIBLE.PER 2001 FBC(M)
 104.2.1, DRAWINGS SHALL BE DRAWN WITH
 CLARITY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-03-02 Cont ID  
Sent By rmcdouga Date 2004-03-02 Time 09:10 Rev Time 0.33
Received By rmcdouga Date 2004-03-02 Time 09:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-17 Cont ID  
Sent By hmoser Date 2004-01-15 Time 17:37 Rev Time 0.50
Received By kstevens Date 2004-01-17 Time 09:01 Sent To B
Notes
2004-01-17 00:00:00DENIED
 REFERENCE: FLA. ADMIN. CODE
 FLA. STATUTES
  
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING IFLED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1) - PER A
 RULING BY FBPE INITALS ARE NOT ACCEPT-
 ABLE.FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-19 Cont ID  
Sent By alange Date 2003-12-18 Time 16:16 Rev Time 0.00
Received By mmclean Date 2003-12-19 Time 16:24 Sent To I
Notes
***NONE***