Plan Review Details - Permit 03121144
Plan Review Stops For Permit 03121144
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-03-08 Cont ID  
Sent By rmcdouga Date 2004-03-08 Time 15:39 Rev Time 2.00
Received By rmcdouga Date 2004-03-08 Time 15:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-22 Cont ID  
Sent By dpalmer Date 2004-02-13 Time 09:16 Rev Time 2.50
Received By rmcdouga Date 2004-01-22 Time 08:28 Sent To P
Notes
2004-01-22 00:00:00DENIED
  
 1) STRUCTURE IS LOCATED IN AN "AO" FLOOD
 ZONE AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 2) SUBMIT A COPY OF THE PAID RECIEPT FOR
 THE IMPACT FEES.
  
 3) THE GLASS BLOCK IN THE WALL ON THE
 ZERO LOT LINE IS REQUIRED TO HAVE A ONE
 HOUR FIRE RATING. SEE FBC TABLE 600,
 WHICH REQUIRES THE EXTERIOR WALL TO HAVE
 A ONE HOUR FIRE RATING AND HAVE NO
 OPENINGS.
  
 4) SUBMIT A SIGNED AND SEALED COPY OF
 THE SOIL REPORT.
  
 5) SHEET A0.01 LISTS THE CONSTRUCTION AS
 TYPE III. BASED ON FBC TABLE 600, THE
 CONSTRUCTION IS TYPE VI. PLEASE CORRECT.
  
 6) NOTE 22 ON A0.01 REFERENCES FBC
 1816.1.7, WHICH IS FOR TERMITE BAITING
 SYSTEMS. PLEASE CLARIFY. NOTE: A SIGNED
 CONTRACT FOR A MINIMUM OF 5 YEARS FROM
 THE DATE OF THE C.O. THAT HAS BEEN PAID
 IS REQUIRED BEFORE THE SLAB IS POURED.
  
 7) REVISE THE GYPSUM FASTENING NOTE ON
 A3.01. THE NAIL SPACING FOR SINGLE
 NAILING IS 7"OC FOR CEILINGS AND 8"OC
 FOR WALLS. THE SPACING FOR SCREWS IS NOT
 MORE THAN 12"OC FOR WALLS AND CEILINGS
 WHEN FRAMING IS 24"OC. SEE FBC 2504.4.1
 AND GA 216.
  
 8) SPECIFY ON THE PLAN IN A CONSPICUOUS
 LOCATION THAT THE DEN IS NOT TO BE USED
 AS A SLEEPING ROOM.
  
 9) REVISE DETAIL 2 ON A4.01 TO SHOW
 FIREBLOCKING WHERE THE WALL AND CEILING
 MEET PER FBC 2305.1.
  
 10) DETAIL 10 ON A4.02 IS NOT FOR A FIRE
 RATED GLASS BLOCK ASSEMBLY. PLEASE
 REVISE. SEE UL R2556.
  
 11) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 12) SPECIFY THE ATTIC LIVE LOAD ON S2.
 FBC TABLE 1604.1 REQUIRES 30PSF FOR
 ATTICS WITH STORAGE AND 10PSF FOR ATTICS
 WITHOUT STORAGE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-02-13 Cont ID  
Sent By dpalmer Date 2004-02-13 Time 09:16 Rev Time 0.33
Received By dpalmer Date 2004-02-13 Time 09:16 Sent To B
Notes
2004-02-13 00:00:00*** REDLINED PLANS ***
 ARC FAULT PROTECTION REQ'D FOR ALL
 BDEROOM OUTLETS, NOT ONLY RECEPTS AS
 NOTED. 210.12 2002 NEC.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-31 Cont ID  
Sent By csiegber Date 2004-02-05 Time 12:37 Rev Time 0.33
Received By dpalmer Date 2003-12-31 Time 10:26 Sent To M
Notes
2003-12-31 00:00:00************** UNSAT ***********
  
 1)NOTE: PLEASE SEE PLANS STILL REF 19991
 NEC. PLEASE ADJUST ALL NOTES AND CODES
 TO 2002 NEC.
  
 2)NOTE: PLEASE SEE 210.12 OF THE 2002
 NEC. REQUIREMENT HAS CHANGED.
  
 3)NOTE: PLEASE HAVE ENGINEER SIGN PLANS
 WITH COMPLETE SIGNATURE. FS 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-05 Cont ID  
Sent By csiegber Date 2004-02-05 Time 12:37 Rev Time 0.00
Received By csiegber Date 2004-02-05 Time 12:37 Sent To E
Notes
2004-02-05 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-22 Cont ID  
Sent By mmclean Date 2004-02-05 Time 12:36 Rev Time 0.00
Received By csiegber Date 2003-12-18 Time 15:00 Sent To  
Notes
2003-12-22 00:00:0012/18/03TO Z
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-15 Cont ID  
Sent By hmoser Date 2004-01-15 Time 16:38 Rev Time 0.50
Received By hmoser Date 2004-01-15 Time 16:37 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-01-05 Cont ID  
Sent By dpalmer Date 2003-12-31 Time 10:44 Rev Time 0.20
Received By pkrauss Date 2004-01-05 Time 08:31 Sent To  
Notes
2004-01-05 00:00:00PLANS SUBMITTED W/O MECHANICAL, PER
 CONVERSATION W/MARIANNA, MECHANICAL
 CONTRACTOR TO BRING IN PLANS.ENERGY
 AND MANUAL J CALCS ARE SUBMITTED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-22 Cont ID  
Sent By rmcdouga Date 2004-01-22 Time 11:10 Rev Time 0.33
Received By kstevens Date 2004-01-22 Time 12:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-19 Cont ID  
Sent By alange Date 2003-12-18 Time 15:00 Rev Time 0.00
Received By mmclean Date 2003-12-19 Time 16:35 Sent To I
Notes
***NONE***