2004-02-20 00:00:00 | DENIED |
| |
| 1) SURVEY HAS WRONG FLOOD ZONE AND MAP |
| NUMBER LISTED. SUBMIT CORRECTED SURVEY. |
| |
| 2) 1001.1.3/ 1005.4 ZERO LOT LINE |
| EGRESS:WHEN ACCESS TO OR FROM A RE- |
| QUIRED EMERGENCY ESCAPE AND RESCUE OPEN- |
| ING OF A STRUCTURE TO THE PUBLIC WAY, |
| REQUIRES TRANSVERSING A PROPERTY |
| (ADJOINING LOT) THAT IS NOT PART OF THE |
| ONE WHICH THE STRUCTURE IS LOCATED, AN |
| EGRESS EASEMENT THROUGH THE ADJOINING |
| PROPERTY IS REQUIRED AND SHALL BE RECORD |
| ED IN THE COUNTY RECORDS. THIS EASEMENT |
| SHALL BE A MINIMUM OF 3' WIDE AND NOTH- |
| ING SHALL BE PLACED WITHIN THE EASEMENT |
| AREA WHICH WOULD BLOCK ACCESS TO THE |
| EASEMENT AND OR IMPEDE EMERGENCY EGRESS |
| FROM THE RESCUE OPENING TO THE PUBLIC |
| WAY. NO LANDSCAPING, FENCES OR OTHER |
| IMPEDIMENTS SHALL BE INSTALLED IN THIS |
| EASEMENT. SUBMIT RECORDED COPY OF |
| SUBDIVISION COVENANTS WHICH SPECIFY AN |
| EMERGENCY EGRESS EASEMENT AS SPECIFIED |
| ABOVE. |
| |
| 3) THE FLOOR PLANS DO NOT SPECIFY A MARK |
| FOR THE TRANSOM ABOVE THE FRONT DOORS. |
| PLEASE CLARIFY IF THIS IS A WINDOW OR |
| NOT. THE STORM PANEL KEY PLAN AND |
| SCHEDULE INDICATE A WINDOW AT THIS |
| LOCATION. |
| |
| 4) ON THE ROOF FRAMING PLANS ON S-1 THE |
| LINES TYING THE TRUSS ANCHORS TO THE |
| TRUSSES ARE TOO FAINT TO SEE. PLEASE |
| SUBMIT LEGIBLE SHEETS. |
| |
| 5) REVISE DETAIL 4 ON S4. THE WEDGE |
| ANCHOR SHOWN IN THE TRUSS SHOULD BE A |
| THROUGH BOLT. |
| |
| 6) SUBMIT STATE OR LOCAL PRODUCT |
| APPROVALS FOR THE DOUBLE OUTSWING ENTRY |
| DOORS. |
| |
| 7) SUBMIT THE EVALUATION REPORT FOR THE |
| STORM PANELS. |
| |
| 8) SUBMIT LOCAL PRODUCT APPROVAL FORMS |
| FOR THE SUSHINE WINDOWS MANUFACTURING |
| PRODUCTS WITH THE REQUIRED QUALITY |
| ASSURANCE ENTITY LISTED. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |