Plan Review Details - Permit 03121047
Plan Review Stops For Permit 03121047
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-02-24 Cont ID  
Sent By rmcdouga Date 2004-02-20 Time 07:36 Rev Time 3.00
Received By rmcdouga Date 2004-02-20 Time 07:35 Sent To  
Notes
2004-02-20 00:00:00PROVISO
  
 1) STRUCTURE LOCATED IN AN "AO" FLOOD
 ZONE AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-03 Cont ID  
Sent By dpalmer Date 2004-02-13 Time 12:51 Rev Time 2.50
Received By rmcdouga Date 2004-02-02 Time 15:50 Sent To  
Notes
2004-02-02 00:00:00DENIED
  
 1) STRUCTURE IS LOCATED IN AN "AO" FLOOD
 ZONE AN ELEVATION CERTIFICATE.
  
 2) SUBMIT A SIGNED AND SEALED COPY OF
 THE SOIL TEST REPORT.
  
 3) SHEET A0.01 LISTS THE CONSTRUCTION AS
 TYPE III. BASED ON FBC TABLE 600 AND THE
 THE PLANS THE CONSTRUCTION IS TYPE VI.
  
 4) NOTE 22 ON A0.01 REFERS TO FBC
 1816.1.7, WHICH IS FOR TERMITE BAITING
 SYSTEMS. PLEASE CLARIFY. NOTE: A SIGNED
 CONTRACT PAID IN FULL FOR FIVE YEARS
 FROM THE DATE OF C.O. IS REQUIRED BEFORE
 THE SLAB IS POURED.
  
 5) ONE HOUR FIRE RATED GLASS BLOCK IS
 REQUIRED AT THE ZERO LOT LINE. SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND LIST-
 ING INFORMATION FOR ONE HOUR FIRE RATED
 GLASS BLOCK.
  
 6) REVISE THE DRYWALL FASTENING NOTE ON
 A3.01. THE FASTENER SPACING FOR SCREWS
 IS NOT MORE THAN 12"OC FOR CEILINGS AND
 WALLS ON FRAMING 24"OC PER FBC 2504.4.1
 AND GA 216.
  
 7) REVISE DETAIL 2 ON A4.01 TO SHOW
 FIREBLOCKING WHERE THE WALL AND CEILING
 MEET. SEE FBC 2305.1.
  
 8) REVISE THE GLASS BLOCK DETAIL 10 ON
 A4.02 TO A ONE HOUR FIRE RATED ASSEMBLY.
 SEE UL R2556.
  
 9) SPECIFY THE ATTIC LIVE LOADS ON S2.
 FBC TABLE 1604.1 REQUIRES 30PSF FOR
 ATTICS WITH STORAGE AND 10PSF FOR ATTICS
 WITHOUT STORAGE.
  
 10) THE KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS DO NOT
 MATCH THE PLANS. CHECK THE NUMBER AND
 SIZES OF OPENINGS. CHECK FOR MINIMUM
 PANEL LENGTH AS LISTED IN PRODUCT
 APPROVAL.
  
 11) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-07-07 Cont ID  
Sent By dpalmer Date 2004-07-07 Time 12:36 Rev Time 0.33
Received By dpalmer Date 2004-07-07 Time 12:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-06-17 Cont ID  
Sent By csiegber Date 2004-07-02 Time 13:24 Rev Time 0.33
Received By dpalmer Date 2004-06-17 Time 18:47 Sent To P
Notes
2004-06-17 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE SEE ONLY ONE SET OF PLANS
 WERE SUBMITTED FOR REVIEW.
 PLEASE SUBMIT TWO SETS.
  
 2)NOTE: PLEASE SEE SD'S ARE SHOWN ON
 TWO SEPARATE CIRCUITS. PLEASE SEE SD'S
 ARE REQUIRED TO BE WIRED "INLINE".
 TWO CIRCUITS TO SAME DEVICE?
 NFPA-72/NEC.
  
 3)NOTE: PLEASE SEE GFI IN MASTER BATH
 REQUIRED TO BE W/IN 3' OF SINK.210.52D
 THESE ARE THE FIRST FULL SIZED SCALED
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-02-13 Cont ID  
Sent By mjacobs Date 2004-06-14 Time 13:58 Rev Time 0.33
Received By dpalmer Date 2004-02-13 Time 12:51 Sent To B
Notes
2004-02-13 00:00:00REDLINED PLANS FOR REQ'D ARC FAULT
 PER 2002 NEC NOT 1999.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-24 Cont ID  
Sent By csiegber Date 2004-02-13 Time 11:19 Rev Time 0.33
Received By dpalmer Date 2003-12-24 Time 07:01 Sent To M
Notes
2003-12-24 00:00:00************** UNSAT *****************
  
 1)NOTE: PLANS STILL REFERENCE THE 1999
 NEC. PLEASE SEE THAT CODE CHANGED ON
 7/1/03. PLEASE SEE THAT ALL CODES REF
 ON PLANS SHOULD CORRELATE WITH 2002 #`S.
  
  
 2)NOTE: PLEASE SEE 210.12 /2002 NEC.
 THIS HAS CHANGED FROM 99 NEC.
  
 3)NOTE: PLANS ARE REQ'D TO BE SIGNED
 W/ A COMPLETE SIGNATURE FROM ENGINEER
 OF RECORD. INITIALS ARE NOT ACCEPTABLE
 PER THE FBPE'S. PER FS 471.025 AND FAC
 61G15-23.002
  
 PLEASE ADJUST PLANS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-07-02 Cont ID  
Sent By csiegber Date 2004-07-02 Time 13:24 Rev Time 0.00
Received By csiegber Date 2004-07-02 Time 13:24 Sent To E
Notes
2004-07-02 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-14 Cont ID  
Sent By mjacobs Date 2004-06-14 Time 13:57 Rev Time 0.00
Received By mjacobs Date 2004-06-14 Time 13:57 Sent To E
Notes
2004-06-14 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-13 Cont ID  
Sent By csiegber Date 2004-02-13 Time 11:18 Rev Time 0.00
Received By csiegber Date 2004-02-13 Time 11:18 Sent To E
Notes
2004-02-13 00:00:00TO DP DESK/RESUB/E REV OF MASTERED

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-03 Cont ID  
Sent By mmclean Date 2004-02-13 Time 11:18 Rev Time 0.00
Received By csiegber Date 2003-12-18 Time 13:36 Sent To  
Notes
2003-12-22 00:00:0012/18/03TO Z
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-14 Cont ID  
Sent By jleech Date 2004-01-03 Time 09:11 Rev Time 0.50
Received By hmoser Date 2004-01-14 Time 13:12 Sent To B
Notes
2004-01-14 00:00:00PASS PRIVISO
 1) REFER TO SECTION 307.2.3 AUXILIARY
 DRAIN PAN.AUXILIARY DRAIN PANS SHALL BE
 INSTALLED UNDER ALL COILS ON WITCH
 CONDENSATION WILL OCCUR.
 2) RETURN AIR REQUIREMENTS TO COMPLY
 WITH THE FLORIDA BUILDING CODE (M) 2003
 CHANGES.CHANGES WENT INTO EFFECT JULY 1
 2003
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-06-28 Cont ID  
Sent By kstevens Date 2004-06-28 Time 14:34 Rev Time 0.50
Received By kstevens Date 2004-06-28 Time 14:34 Sent To  
Notes
2004-06-28 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) NO CHANGES TO STAMPED SET OF PLANS ON
 FILE ARE NOTED ON REVISION. PLEASE IN-
 DICATE REVISION WITH CLOUDS AND TRI-
 ANGLES WITH NUMBERS. STAMPED SET OF
 PLANS SHOW REVISION NUMBER 2, AND REV-
 ISION SHOWS REVISION #2 ALSO. PLEASE
 CLARIFY. MINIMUM TWO SETS OF REVISIONS
 ARE REQUIRED, ONE SET SUBMITTED FOR RE-
 VISION. SECTION 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-03 Cont ID  
Sent By dpalmer Date 2004-06-17 Time 18:48 Rev Time 0.25
Received By jleech Date 2004-01-03 Time 09:11 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-19 Cont ID  
Sent By alange Date 2003-12-18 Time 13:36 Rev Time 0.00
Received By mmclean Date 2003-12-19 Time 16:31 Sent To I
Notes
***NONE***