Plan Review Details - Permit 03121040
Plan Review Stops For Permit 03121040
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-03-13 Cont ID  
Sent By shill Date 2004-03-13 Time 05:06 Rev Time 0.50
Received By shill Date 2004-03-13 Time 05:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-22 Cont ID  
Sent By shill Date 2004-01-21 Time 17:31 Rev Time 3.00
Received By shill Date 2004-01-21 Time 17:31 Sent To  
Notes
2004-01-21 00:00:00*****PROVISO/CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 ADDRESS ALL BUILDING CORRECTIONS AT THIS
 TIME IF THE PLANS DO NOT PASS OTHER
 TRADES!!!
  
 COMMENTS ALSO APPLY TO 03121105,
 03121071,03121087, 03121095, 03121058
  
 1.)THE NOTICE OF COMMENCEMENT IS
 EXPIRED FS713.13 (90 DAYS WITHOUT
 COMMENCING WORK).
  
 2.)S-1, WATERSTOP TO BE 1 1/2" CITY OF
 WEST PALM BEACH AMENDMENTS TO THE FBC
 2111.1.9.CHECK ALL DETAILS.
  
 3.)BOTTOM CHORD LIVE LOAD IS REQUIRED
 TO BE 10, 30 IN ATTICS WITH STORAGE,
 FBC TABLE 1604.1., (SHEET S8, #9).
  
 THE FOLLOWING COMMENTS MUST BE
 ADDRESSED BEFORE THE PERMIT CAN BE
 ISSUED - NO PROVISO
  
 4.)MANY PRODUCT APPROVALS WERE
 SUBMITTED FOR ITEMS WHICH DO NOT APPEAR
 ON THE PLAN.PRODUCT APPROVALS FOR
 FIXED GLASS AND SINGLE HUNG WINDOWS
 WERE SUBMITTED, BUT NOT FOR HORIZONTAL
 SLIDERS (THE ONLY WINDOW SHOWN ON THE
 PLAN).SUBMIT ONLY PRODUCT APPROVALS
 FOR DOORS, WINDOWS, AND ROOF WHICH
 APPEAR ON THE PLAN.
  
 PRODUCT APPROVALS NOT SUBMITTED BEFORE
 ISSUANCE WILL REQUIRE SEPARATE PERMITS
 WITH ADDITIONAL FEES FOR THOSE ITEMS.
  
 5.)FLORIDA STATEWIDE PRODUCT APPROVALS
 OR SITE SPECIFIC REQUIRED, SEE DCA
 WEBSITE AT WWW.FLORIDABUILDING.ORG.
 RULE 9B-72 EFFECTIVE OCTOBER 1, 2003.
  
 6.)SUBMIT A HURRICANE SHUTTER
 INSTALLATION SCHEDULE, SEE ATTACHED.IF
 THIS IS NOT SUBMITTED BEFORE TIME OF
 PERMIT ISSUANCE A SEPARATE PERMIT FOR
 THIS ITEM WILL BE REQUIRED.
  
 7.)PROVIDE AREA CALCULATIONS FOR
 EACH UNIT TYPE - A/C SPACE, NON A/C
 SPACE, TOTAL.
  
 8.)PROVIDE A SOILS INVESTIGATION
 REPORT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-29 Cont ID  
Sent By csiegber Date 2004-01-20 Time 16:53 Rev Time 1.50
Received By shill Date 2003-12-29 Time 12:57 Sent To  
Notes
2003-12-29 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEVERAL SHEETS DO NOT MATCH THE
 MASTER PERMIT #03030456:
  
 A1.01, A1.02, A3.03, A5.01, E101, M2,S9
  
 2.)NOTE THAT FBC 2003 AMENDMENTS
 AND NEC2002 CAME INTO EFFECT 7/1/03
 (AFTER THE MASTER WAS REVIEWED).PLANS
 WILL BE REVIEWED FOR ANY CHANGES WHICH
 MAY BE REQUIRED BY THE CODE CHANGES
 AND A PERMIT WILL BE ISSUED WITH A
 PROVISO THAT ANY CHANGES REQUIRED, IF
 ANY, BE ADDRESSED WITH A REVISION.
  
 3.)SAME COMMENTS APPLY TO 03121105,
 03121071, 03121087, 03121095, 03121058.
  
 4.)SUBMIT PRODUCT APPROVALS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-03-05 Cont ID  
Sent By dpalmer Date 2004-03-05 Time 14:33 Rev Time 0.33
Received By dpalmer Date 2004-03-05 Time 14:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-03-01 Cont ID  
Sent By dpalmer Date 2004-03-01 Time 06:25 Rev Time 0.50
Received By dpalmer Date 2004-03-01 Time 06:25 Sent To  
Notes
2004-03-01 00:00:00*************** UNSAT ***********
  
 1)NOTE: PLEASE SEE COMMENTS FROM FIRST
 REVIEW.
  
  
 2)NOTE: PLEASE PROVIDE ADDRESS IN TITLE
 BLOCK/LOT #MIN FOR SITE. AS REQ'D UNDER
 FAC 61G1-16.004.
  
 3)NOTE: PLEASE HAVE ALL CIRCUITING
 CONFORM TO THE 2002 NEC FOR ARC FAULT
 PROTECTION. 210.12CIRCUITS#'S 13,15
  
 4))NOTE: PLEASE SEE NFPA-72 8-1.4.1.6.2
 ALL SD'S ARE REQ'D TO BE WIRED INLINE,
 HOWEVER, SD'D ARE NOW SHOWN ON SEPARATE
 CIRCUITS?
  
 5)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND INSERT NEW ONLY.
  
 PLANS/PERMIT APPLICATION/COMPUTER WILL
 NO LONGER REFERENCE MASTER SINCE THE
 CODE CHANGED 7/1/03
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-29 Cont ID  
Sent By dpalmer Date 2004-01-29 Time 14:51 Rev Time 0.50
Received By dpalmer Date 2004-01-29 Time 14:51 Sent To  
Notes
2004-01-29 00:00:00*************** UNSAT ***********
  
 1)NOTE: PLEASE PROVIDE ADDRESS ON PLANS
 AS REQ'D UNDER FAC 61G1-16.004
  
 2)NOTE: PLEASE SEE NOTES ON PLANS
 REFERENCE THE 1999 NEC AND THE SFBC
 WHICH NEITHER ONE IS ANY LONGER IN
 EFFECT. PLEASE ADJUST PLANS AND ALL
 CODE #'S TO CORRELATE TO 2002 NEC.
  
 3)NOTE: PLEASE PROVIDE CIRCUITING'S ON
 PLANS AND PANEL SCHEDULE IN ORDER TO
 PROVIDE REQ'D ARC FAULT PROTECTION PER
 THE 2002 NEC. PLANS NOW SHOW WHAT IS
 REQ'D UNDER THE 1999 NEC.
  
 4)NOTE: PLEASE SEE CODE REFERENCED FOR
 GROUNDING ELECTRODE SYSTEM. CODES ARE
 FOR 1999 NEC. PLEASE SEE 2002
  
 5)NOTE: PLEASE SEE NOTES FROM OTHER
 REVIEWERS.
  
 PLEASE REMOVE ALL OLD/ VOIDED SHEETS
 AND INSERT NEW SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-02-20 Cont ID  
Sent By mcarsill Date 2004-02-20 Time 16:18 Rev Time 0.00
Received By mcarsill Date 2004-02-20 Time 16:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-01-29 Cont ID  
Sent By mcarsill Date 2004-01-29 Time 07:58 Rev Time 0.00
Received By mcarsill Date 2004-01-29 Time 07:58 Sent To  
Notes
2004-01-29 00:00:001) WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 2) BUILDING ADDRESSES ARE REQUIRED.
  
 3) PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 4) EGRESS WINDOWS SHALL COMPLY WITH
 BUILDING AND FIRE CODE REQUIREMENTS.
  
 THESE COMMENTS ALSO APPLY TO
 PERMIT NUMBERS 03121058, 03121058,
 031212095, 03121087, 03121071, 03121105
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-05-17 Cont ID  
Sent By csiegber Date 2004-05-17 Time 09:11 Rev Time 0.00
Received By csiegber Date 2004-05-17 Time 09:11 Sent To P
Notes
2004-05-17 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-22 Cont ID  
Sent By csiegber Date 2004-01-22 Time 09:44 Rev Time 0.00
Received By csiegber Date 2004-01-22 Time 09:43 Sent To  
Notes
2004-01-22 00:00:00TO COMM BD#50

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-20 Cont ID  
Sent By csiegber Date 2004-01-20 Time 16:53 Rev Time 0.00
Received By csiegber Date 2004-01-20 Time 16:53 Sent To B
Notes
2004-01-20 00:00:00TO SH DESK/RESUB/MASTERED

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-02 Cont ID  
Sent By mmclean Date 2004-05-05 Time 16:15 Rev Time 0.00
Received By csiegber Date 2003-12-18 Time 13:23 Sent To  
Notes
2003-12-22 00:00:0012/18/03TO Z
 TO HP DESK/MASTERED

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-03-03 Cont ID  
Sent By pkrauss Date 2004-03-03 Time 06:37 Rev Time 0.33
Received By pkrauss Date 2004-03-03 Time 06:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-02-02 Cont ID  
Sent By pkrauss Date 2004-02-02 Time 12:33 Rev Time 1.00
Received By pkrauss Date 2004-02-02 Time 11:46 Sent To  
Notes
2004-02-02 00:00:00DENIED
 COMMENTS PERTAIN TO THE FOLLOWING PERMIT
 NUMBERS:03121040, 03121058, 03121095,
 03121087, 03121071, 03121105
  
 MODEL A, B, & C
 1.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 402.2 OR 403.3.
  
 2.RETURN AIR TRANSFER GRILLE FROM THE
 MASTER BEDROOM IS NOT SIZED PROPERLY.
 REFERENCE 2001 FBC(M) 601.4 EXCEPTION #2
 AND 3. GRILLES SHALL HAVE 50 SQ INCHES
 TO 100 CFM OF SUPPLY AIR. FOR PROPER
 SIZING FOR THE RETURN TRANSFER GRILLE TO
 THE MASTER BEDROOM, ALL SUPPLY AIR TO
 THE SUITE IS TO BE INCLUDED IN THE
 CALCULATION.PLEASE REVISE.
  
 3.AUXILIARY DRAIN PAN REQUIRED PER
 2001 FBC(M) 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-06-02 Cont ID  
Sent By jleech Date 2004-06-02 Time 19:17 Rev Time 0.15
Received By jleech Date 2004-06-02 Time 19:17 Sent To  
Notes
2004-06-02 00:00:00REV. H2O PIPE FROM COPPER TO CPVC

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-03-03 Cont ID  
Sent By csiegber Date 2004-05-17 Time 09:12 Rev Time 0.50
Received By kstevens Date 2004-03-03 Time 11:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-31 Cont ID  
Sent By kstevens Date 2004-01-31 Time 11:43 Rev Time 0.33
Received By kstevens Date 2004-01-31 Time 11:43 Sent To  
Notes
2004-01-31 00:00:00DENIED
 REFERENCE: FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
  
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
  
 PER FBPE'S RULING INITIALS ARE NOT
 ACCEPTABLE. SUBMIT A SAMPLE OF YOUR
 SIGNATURE WITH COPY OF LICENSE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-19 Cont ID  
Sent By alange Date 2003-12-18 Time 13:24 Rev Time 0.00
Received By mmclean Date 2003-12-19 Time 16:33 Sent To I
Notes
***NONE***