Plan Review Details - Permit 03111366
Plan Review Stops For Permit 03111366
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-26 Cont ID  
Sent By csiegber Date 2003-11-26 Time 16:22 Rev Time 0.00
Received By csiegber Date 2003-11-26 Time 16:22 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-12-11 Cont ID  
Sent By csiegber Date 2003-11-26 Time 16:22 Rev Time 0.25
Received By pkrauss Date 2003-12-11 Time 10:01 Sent To  
Notes
2003-12-11 00:00:00PROVISO:
 TRANSFER GRILLES NOT PROPERLY.
 PER REVISION TO THE 2001 FBC(M) 601.4
 EFFECTIVE JUNE 30, 2003 -
 EXCEPTION:
 2.TRANSFER GRILLES SHALL USE 50 SQ
 INCHES (OF GRILLE AREA) TO 100 CFM OF
 SUPPLY AIR WITH DOORS HAVING A CLEAR 1"
 UNDERCUT.
  
 PLEASE SIZE RETURN TRANSFERS ACCORDINGLY
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved