Plan Review Details - Permit 03111034
Plan Review Stops For Permit 03111034
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-05-04 Cont ID  
Sent By shill Date 2004-05-03 Time 13:32 Rev Time 3.00
Received By shill Date 2004-05-03 Time 13:32 Sent To  
Notes
2004-05-03 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST, ITEM #1.THE
 SURVEY IS TO INCLUDE THE DISTANCE
 BETWEEN THE BUILDINGS.SHOW COMPLIANCE
 WITH TABLE 600 (SEE ATTACHED).
  
 2.)CHANGES TO THE PLAN ARE TO BE
 DONE BY THE DESIGNER OF RECORD AND ARE
 TO BE CLEARLY INDICATED.CHANGES DONE
 IN INK TO A DRAWING ARE TO BE INITIALED
 BY THE DESIGNER OF RECORD.
  
 3.)PLANS SUBMITTED ARE THE SAME AS
 THE FIRST REVIEW.WHAT HAPPENED TO
 THE PLANS FROM THE SECOND REVIEW? THE
 COMMENTS FROM BOTH THE FIRST AND SECOND
 REVIEWS NOW APPLY.
  
 4.)SEE REVIEWS #1 AND #2, ATTACHED.
 PLEASE ADDRESS ALL COMMENTS BEFORE
 RESUBMITTAL.
  
 5.)A 4X FEE HAS BEEN CHARGED AS PER
 FS553.BE ADVISED THAT THIS STATUTE
 APPLIES TO FUTURE RESUBMITTALS AS WELL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-01-21 Cont ID  
Sent By csiegber Date 2004-04-14 Time 11:28 Rev Time 3.00
Received By shill Date 2004-01-21 Time 09:46 Sent To  
Notes
2004-01-21 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST, ITEM #1.NOT
 ADDRESSED.SUBMIT A COPY OF A SURVEY
 FOR THIS PROPERTY, ADDRESSING TABLE 600
 ISSUES.SHOW THE DISTANCE BETWEEN THE
 TWO BUILDINGS ON THIS PROPERTY, DISTANCE
 TO THE PROPERTY LINE.SHOW THE
 ASSUMED PROPERTY LINE, WITH DIMENSIONS,
 AND SUBMIT CALCULATIONS SHOWING TABLE
 600 COMPLIANCE.FAILURE TO PROVIDE THE
 REQUESTED INFORMATION MAY RESULT IN
 ADDITIONAL PERMITTING DELAYS.
  
 2.)SEE PREVIOUS LIST, ITEM #3, NOT
 ADDRESSED.
  
 3.)THE PLANS MAKE REFERENCE "TO CODE".
 THIS IS NOT AN ACCEPTABLE AS A DETAIL,
 FBC104.2.1.ALL MATERIALS, DIMENSIONS,
 ETC. MUST BE SPECIFIED.
  
 4.)SEE PREVIOUS LIST, ITEM #5,
 REGARDING FBC3401.7.2.6.SOME COMMENTS
 ARE RELATED TO THIS CODE SECTION
 (ALTERATIONS OVER 50%).
  
 5.)THE STAIRS DO NOT COMPLY WITH FBC
 1007.3.
  
 6.)SEE PREVIOUS LIST, ITEM #9.CANNOT
 SPECIFY "TO CODE".ALL GUARDRAIL AND
 HANDRAILS DETAILS ARE TO COMPLY WITH
 FBC1608, FBC1007.5, FBC1015.THE
 DETAILS SHOWN ARE NOT CODE COMPLIANT IN
 DESIGN, INCLUDING HEIGHT, MAKE NO
 REFERENCE TO STRUCTURAL DESIGN LOAD.
 THIS ALSO APPLIES TO PREVIOUS LIST #10,
 EITHER NOT ADDRESSED OR ADDRESSED IN A
 MANNER WHICH IS NOT CODE COMPLIANT.
  
 7.)CHANGES MADE TO THE PLAN IN INK
 ARE TO BE INITIALED BY THE ARCHITECT.
  
 8.)SEE PREVIOUS LIST, ITEM #35. MANY
 CHANGES WERE DONE TO THE PLAN AND NOT
 INDICATED IN ANY MANNER.
  
 9.)ADDITIONAL FEES DUE, $2163.60,
 BZ235307.PLEASE RETURN THE BZ GIVEN
 AT THE LAST REVIEW.
  
 10.)SEE PREVIOUS LIST, ITEM #12.NOT
 ADDRESSED.TO MY KNOWLEDGE THE PRODUCT
 APPROVALS SUBMITTED FOR DOORS AND
 WINDOWS DO NOT HAVE ANY FIRE RATING.
  
 11.)SEE PREVIOUS LIST, ITEM #13,
 INDICATE CONSTRUCTION TYPE ON THE PLAN.
  
 12.)SHEET 4, LSAT 2", MUST SPECIFY A
 MODEL #, NOT A DIMENSION.LSTA IS A
 WOOD-TO-WOOD CONNECTOR WHICH YOU ARE
 USING IN A WOOD-TO-MASONRY APPLICATION.
 EITHER SUBMIT DOCUMENTATION FROM THE
 MANUFACTURER SHOWING THAT THIS
 APPLICATION IS ACCEPTABLE, SPECIFY A
 DIFFERENT CONNECTOR, OR SUBMIT SEALED
 CALCULATIONS FOR THIS CONNECTOR IN THIS
 APPLICATION.CHECK ALL CONNECTORS.
  
 13.)THE WINDOW/DOOR BUCK DETAIL
 SPECIFIES "CASE HARDENEND NAILS",SPECIFY
 SIZE.THE FASTENERS FOR THE WINDOW
 CONFLICT WITH THE PRODUCT APPROVAL IN
 BOTH DIAMETER AND SPACING, SEE ATTACHED
 HIGHLIGHTED PRODUCT APPROVAL.
  
 14.)NOTE THAT THE TEMPERED WINDOWS
 SHOWN ON THE 2ND FLOOR ARE ALSO REQUIRED
 TO HAVE A FIRE RESISTANCE RATING, FBC
 1006.2.4.DOCUMENTATION SUBMITTED FOR
 THIS WINDOW IS TO SHOW COMPLIANCE WITH
 CHAPTER 16, FBC2405.2, AND FBC1006.2.4.
  
 15.)THE GUARDRAIL IS TO BE A MINIMUM
 OF 44", FBC1015.2.THE DETAILS SHOW
 THE STAIRRAIL (WHICH SERVES AS A
 GUARDRAIL) AT 30" AND 36".
  
 16.)HANDRAIL REQUIRED FOR STAIR ON
 BOTH SIDES, FBC1007.5.
  
 17.)SEE PREVIOUS LIST, ITEM #22,
 NOT ADDRESSED.
  
 18.)SEE PREVIOUS LIST, ITEM #24.
 ENERGY CALCS REQUIRED.
  
 19.)SEE PREVIOUS LIST, ITEM #25.
 RATHER THAN ADDRESS THE COMMENT THE
 INSULATION WAS REMOVED.INSULATION IS
 REQUIRED FOR THE FLOOR (OCCUPANCY
 SEPARATION) AND ROOF.
  
 20.)SEE PREVIOUS LIST, ITEM #29.NOT
 ADDRESSED.IF THE REQUIRED INFORMATION
 IS NOT SUBMITTED PRIOR TO PERMIT
 ISSUANCE, A SEPARATE PERMIT FOR SHUTTERS
 WILL BE REQUIRED.
  
 21.)SEE PREVIOUS LIST, ITEM #26.ALSO
 HAVE THE NEW PLANS APPROVED BY HISTORIC
 PRIOR TO RESUBMITTAL.
  
 22.)SPECIFY THE SPACING AND LENGTH OF
 THE ANCHOR BOLT, SHEET 4, WALL SECTION
 AT BALCONY.
  
 23.)SEPARATE PERMITS REQUIRED.
  
 24.)SEE PREVIOUS LIST, ITEM #37.NOT
 ADDRESSED.
  
 25.)RESOLVE ANY EXPIRED PERMIT ISSUES
 PRIOR TO ISSUANCE OF THIS PERMIT.
  
 26.)AS DISCUSSED SEVERAL TIMES WITH
 THE CONTRACTOR, IF YOU WISH TO OBTAIN A
 PERMIT FOR THE ROOF JOISTS, SHEATHING,
 AND ROOF COVERING ONLY, SUBMIT A PERMIT
 APPLICATION WITH PLANS SHOWING ONLY
 THESE ITEMS.PLANS ARE REQUIRED SHOWING
 DRAINAGE, DESIGN LOAD AND UPLIFT.
  
 27.)SLIDING GLASS DOOR PRODUCT
 APPROVALS WERE SUBMITTED, NONE SHOWN ON
 THE PLAN.
  
 28.)MULLION PRODUCT APPROVALS
 REQUIRED, SUBMIT 2 COPIES.
  
 29.)SHEET 2 IS NOW MISSING FROM THE
 OLD SETS OF PLANS.ALWAYS SUBMIT ALL
 OLD SHEETS WITH RESUBMITTAL.THE NEW
 SHEET 2 NOW SHOWS WINDOWS AS EXISTING.
 MY UNDERSTANDING IS THAT THIS BUILDING
 DOES NOT HAVE WINDOWS AND THAT THIS WORK
 IS TO BE INCLUDED IN THIS PERMIT.
 REVISE.
  
 30.)SEE ATTACHED NOTICE IN REGARDS TO
 FS553.80(2)(B).
  
 31.)PAY FEES PRIOR TO RESUBMITTAL.
  
 32.)TWO COPIES OF ALL DOCUMENTATION
 REQUIRED FOR PERMITTING, ONLY ONE SET
 OF PLANS WERE SUBMITTED.
  
 33.)SEE PREVIOUS LIST, ITEM #6.THE
 FIRST FLOOR SHOULD BE DECLARED AS
 MERCANTILE, 2ND FLOOR AS R2 FBC CH.3.
  
 34.)SEE PREVIOUS LIST, ITEM #37.IN
 ADDITION TO PROVIDING THE REQUESTED
 INFORMATION FOR THE OCCUPANCY SEPARATION
 ALSO PROVIDE SAME FOR TENANT SEPARATION
 ON THE 1ST FLOOR, FBC704.3.1.
  
 35.)"EXISTING PLUMBING PIPE" IS SHOWN
 ON THE PLAN (SHEET2, 2ND FLOOR).
 PENETRATIONS ARE TO COMPLY WITH FBC705.2
 .1.3, 705.4.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-10 Cont ID  
Sent By csiegber Date 2003-11-21 Time 15:19 Rev Time 3.00
Received By shill Date 2003-12-05 Time 14:51 Sent To  
Notes
2003-12-05 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)PROVIDE A COPY OF A SURVEY FOR THIS
 PROPERTY.WHEN RESUBMITTING, ADDRESS
 FBC TABLE 600 ISSUES, IF ANY.
  
 2.)GIVE INFORMATION AS TO OCCUPANCY
 AND USE FOR THIS BUILDING.
  
 3.)SEE LETTER FROM HISTORICAL
 PRESERVATION DEPARTMENT DATED 11/20/03.
 BEFORE RESUBMITTAL HAVE THE EXTERIOR
 DOORS APPROVED.
  
 4.)THE APPLICATION INDICATES THAT YOU
 ARE REPLACING ALL WINDOWS AND DOORS.
 SHOW THE WINDOWS AND DOORS ON THE
 ELEVATIONS.ONE SET OF PLANS HAS
 WINDOWS PENCILLED IN.ALL EXISTING
 CONDITIONS SHOULD BE SHOWN.
  
 5.)REPAIRS AND ALTERATIONS OF OVER
 50% OF THE VALUE OF THE EXISTING
 BUILDING ARE REQUIRED TO COMPLY WITH
 FBC3401.7.2.6.
  
 6.)THE PLANS STATE "REHAB OF OFFICE
 BUILDING".THE CURRENT ZONING USE OF
 THIS BUILDING IS STORES ON 1ST FLOOR,
 APARTMENTS ON THE 2ND (SEE ATTACHED).
 PROVIDE INTENDED OCCUPANCY INFORMATION
 ON THE PLAN.
  
 7.)THE PERMIT APPLICATION IS FOR
 WINDOW REPLACEMENT.SLEEPING ROOMS ARE
 REQUIRED TO COMPLY WITH FBC1005.4,
 EMERGENCY EGRESS.INDICATE ANY FUTURE
 BEDROOMS ON THE PLAN AND SHOW COMPLIANCE
 BY SHOWING WINDOW SIZE, TYPE AND SILL
 HEIGHT.PROVIDE A WINDOW SCHEDULE.
  
 8.)SHOW TREAD AND RISER DIMENSIONS
 FOR THE EXTERIOR STAIR (FBC1007.3).
  
 9.)THE EXISTING STAIR RAILING DOES
 NOT COMPLY WITH FBC1007.5, FBC1015
 (HEIGHT, OPENINGS).PROVIDE A DETAIL
 FOR A NEW STAIR RAILING, ALSO SHOWING
 COMPLIANCE WITH FBC1608.2.
  
 10.) THE EXISTING GUARD RAILINGS
 (STAIR LANDING, BALCONIES) DO NOT COMPLY
 WITH FBC1015. PROVIDE A DETAIL FOR NEW
 GUARDRAILS, ALSO SHOWING COMPLIANCE WITH
 FBC1608.
  
 11.) STAIRWAYS SHALL HAVE HANDRAILS ON
 EACH SIDE, FBC1007.5.2.
  
 12.) EXTERIOR STAIRS TO COMPLY WITH
 FBC1006.2.4.INDICATE, TO SCALE, ALL
 WINDOWS NEAR THE STAIR, WITH DIMENSIONS
 FROM THE STAIR.DOOR IS REQUIRED TO
 HAVE FIRE RATING AND DOOR CLOSER,
 SHOW ON PLAN AND PROVIDE FIRE RATING
 INFORMATION FOR DOOR, FBC1006.2.4.
  
 13.)INDICATE THE CONSTRUCTION TYPE
 ON THE PLAN.
  
 14.)PROVIDE A CONTRACT FOR THIS JOB;
 VALUE APPEARS LOW.IF A REASONABLE
 VALUE IS NOT PROVIDED FOR THIS JOB, AN
 ESTIMATE WILL BE DONE USING MARSHALL &
 SWIFT.THE AMOUNT ON THE APPLICATION IS
 FOR VALUE.A PERMIT WAS APPLIED FOR
 WITH THE SAME SCOPE OF WORK WITH A
 VALUE OF $35,000.
  
 15.)PROVIDE LOADING INFORMATION FOR
 THE FLOOR JOISTS, FBC1604.
  
 16.)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 17.) PROVIDE UPLIFT INFORMATION ON THE
 FLOOR AND ROOF PLAN.
  
 18.) PROVIDE A WINDOW AND DOOR BUCK
 DETAIL.
  
 19.) IN ORDER TO ISSUE A WINDOW PERMIT,
 SHOW ON THE PLAN ANY WINDOWS WHICH
 WOULD BE REQUIRED TO BE SAFETY GLASS
 PER FBC2405.2.
  
 20.) 1503.4 ROOF DRAINS UNLESS ROOFS ARE
 SLOPED TO DRAIN OVER THE ROOF EDGE, ROOF
 DRAINS SHALL BE INSTALLED AT THE LOWEST
 POINT OF THE ROOF. WHERE REQUIRED FOR
 ROOF DRAINAGE,SCUPPERS SHALL BE LOCATED
 AS DETERMINED BY THE ROOF SLOPE AND CON-
 TRIBUTING ROOF AREA.
  
 21.) 1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 22.)INCLUDE WIND DESIGN INFORMATION
 REQUIRED TO BE ON THE PLAN, FBC1606.1.7,
 INCLUDING DESIGN PRESSURES FOR WINDOWS
 AND DOORS.
  
 23.)PROVIDE A SPECIFICATION FOR THE
 CONCRETE RESTORATION.IS WORK BEING
 DONE ON THE BALCONIES?
  
 24.)FBC 13-101.1.6SHELL BUILDINGS.
 THE WHOLE BUILDING (INCL. FUTURE TENANT
 SPACE) SHALL BE CONSIDERED.SHELL
 BUILDINGS SHALL BE SHOWN TO COMPLY WITH
 METHOD B (SEE SUB-CHAPTER 4).ALL
 ASSUMPTIONS MADE ABOUT SYSTEMS, NOT
 SHOWN ON THE CURRENT PLANS, SHALL BE
 LISTED AND APPENDED TO THE FORM 400B FOR
 SUBMITTAL.THIS WILL BE COMPARED TO THE
 ACTUAL SYSTEMS PROPOSED, AT A LATER, FOR
 INSTALLATION BY THE TENANT(S).THE
 ASSUMPTIONS LISTED ON THE APPENDIX SHEET
 SHALL BE AT LEAST THE MINIMUM STANDARD
 (LIGHTING, HVAC ETC) TO ALLOW THE WHOLE
 BUILDING TO BE OCCUPIED FOR IT'S
 INTENDED PURPOSE.
  
 25.) INSULATION IS SHOWN IN THE FLOOR
 JOISTS, WHAT IS THE RVALUE?
  
 26.) AS PER THE LETTER FROM SHERRY
 PILAND DATED 11/20/03, GET HISTORIC
 APPROVAL FOR THE DOORS.
  
 27.) SUBMIT A SITE SPECIFIC PRODUCT
 APPROVAL OR STATEWIDE PRODUCT APPROVAL
 FOR THE FOLLOWING BEFORE INSTALLATION:
 HARTMAN OUTSWING WOOD FRENCH DOOR
 STANLEY OUTSWING DOOR
  
 28.) THE FOLLOWING PRODUCT APPROVALS ARE
 ON THE PENDING LIST.THIS PERMIT WILL
 BE ISSUED WITH A PROVISO THAT STATEWIDE
 OR SITE SPECIFIC PRODUCT APPROVAL BE
 SUBMITTED BEFORE INSTALLATION:
 JOHNS MANVILLE BUILT UP ROOF, FL1037
 BINNINGS PAN AMERICAN SINGLE HUNG
  
 29.) PROVIDE A HURRICANE SHUTTER
 INSTALLATION SCHEDULE, SEE ATTACHED.
  
 30.) PRODUCT APPROVALS WERE SUBMITTED
 FOR ASPHALT SHINGLES, NONE ON THE PLAN.
 ALSO PLEASE NOTE THAT FOUR DIFFERENT
 DOOR PRODUCT APPROVALS WERE SUBMITTED.
  
 31.) THE EXTRA PRODUCT APPROVALS BOUND
 AND MARKED "RETURN TO CONTRACTOR" DO NOT
 NEED TO BE RESUBMITTED.
  
 32.) ADDITIONAL FEES, SEE ATTACHED BZ
 233269.
  
 33.) SEPARATE PERMITS REQUIRED.
  
 34.) THERE IS AN OPEN PLAN REVIEW ON
 THIS ADDRESS FOR THE SAME SCOPE OF
 WORK, #03030708.THIS APPLICATION
 SHOULD BE VOIDED.
  
 35.) WHEN RESUBMITTING, CLEARLY MARK
 ALL CHANGES TO THE PLAN WITH CLOUDS OR
 TRIANGLES.SUBMIT BOTH THE OLD SHEETS
 AND NEW REVISED PLANS.SUBMIT A
 TRANSMITTAL LETTER EXPLAINING HOW EACH
 ITEM WAS ADDRESSED.
  
 36.) SEE ATTACHED, CONTRACTOR HAS 3
 EXPIRED OPEN ROOF PERMITS.ADDRESS OR
 FURTHER ACTION AGAINST YOUR LICENSE
 AND ABILITY TO OBTAIN PERMITS WILL BE
 TAKEN.
  
 37.) PROVIDE FIRE RATING INFORMATION
 ON THE PLAN (UL ASSEMBLY NUMBER) OR
 CALCULATED FIRE RESISTANCE (FBC709) FOR
 THE OCCUPANCY SEPARATION (BETWEEN THE
 FIRST FLOOR M, AND 2ND FLOOR, R),
 FBC 704.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2004-04-30 Cont ID  
Sent By mcarsill Date 2004-04-30 Time 13:47 Rev Time 0.00
Received By mcarsill Date 2004-04-30 Time 13:47 Sent To  
Notes
2004-04-30 00:00:001) PLANS LACK REQUIRED INFORMATION.
 PREVIOUS COMMENTS FROM FIRE RESCUE
 HAVE NOT BEEN PROPERLY ADDRESSED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-01-07 Cont ID  
Sent By mcarsill Date 2004-01-07 Time 09:32 Rev Time 0.00
Received By mcarsill Date 2004-01-07 Time 09:31 Sent To  
Notes
2004-01-07 00:00:001) IT APPEARS THAT ALL PREVIOUSLY
 PLAN REVIEW COMMENTS HAVE NOT BEEN
 ADDRESSED. WHAT IS THE PLANNED TENANT
 SEPARATION BETWEEN THE FIRST FLOOR
 AND SECOND FLOOR.
  
 2) NO SMOKE DETECTORS SHOWN IN
 APARTMENT.
  
 3) IT APPEARS THAT A DOOR IS LOCATED
 WITHIN 10 FEET OF EXIT STAIRS.
  
 4) MORE DETAILS ON EGRESS WINDOWS.
  
 5) NO PRESCREPTIVE REQUIREMENTS ON
 HANDRAILS OR GUARDRAILS.
  
 6) BUILDING ADDRESS REQUIRED MINIMUM
 6" HIGH NUMBERS. PLEASE ADD NOTES
 TO PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-12-11 Cont ID  
Sent By mcarsill Date 2003-12-11 Time 13:37 Rev Time 0.00
Received By mcarsill Date 2003-12-11 Time 13:37 Sent To  
Notes
2003-12-11 00:00:001) BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION. A MINIMUM OF 6" HIGH
 NUMBERS ARE REQUIRED.
  
 2) PLANS INDICATE REHAB OF SHELL ONLY
 FOR OFFICE BUILDING.
  
 3) PLEASE PROVIDE MORE DETAILS ON ALL
 EXISTING HANDRAILS AND GUARDRAILS.
  
 4) PLANS DO NOT INDICATE PROPOSED
 OCCUPANT LOAD FOR THE BUILDING.
  
 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR HANDRAILS AND
 GUARDRAILS.
  
 6) PLEASE EXPLAIN SINGLE EXIT RATIONALE
 FROM SECOND FLOOR. WHAT EXCEPTION
 TO THE CODE ARE YOU USING THAT ALLOWS
 THIS.
  
 7) PLEASE PROVIDE MORE DETAILS ON
 EXISTING STAIR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-04-14 Cont ID  
Sent By csiegber Date 2004-04-14 Time 11:28 Rev Time 0.00
Received By csiegber Date 2004-04-14 Time 11:28 Sent To  
Notes
2004-04-14 00:00:00TO COMM BD#57

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-01-06 Cont ID  
Sent By csiegber Date 2004-01-06 Time 12:14 Rev Time 0.00
Received By csiegber Date 2004-01-06 Time 12:14 Sent To  
Notes
2004-01-06 00:00:00TO COMM BD#12

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-01 Cont ID  
Sent By csiegber Date 2003-11-26 Time 14:18 Rev Time 0.00
Received By csiegber Date 2003-11-26 Time 14:18 Sent To  
Notes
2003-12-01 00:00:00TO COMM BD#24

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-21 Cont ID  
Sent By csiegber Date 2003-11-21 Time 15:19 Rev Time 0.00
Received By csiegber Date 2003-11-21 Time 15:19 Sent To B
Notes
2003-11-21 00:00:00TO MISC BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-20 Cont ID  
Sent By csiegber Date 2003-11-20 Time 16:41 Rev Time 0.00
Received By csiegber Date 2003-11-20 Time 16:41 Sent To B
Notes
2003-11-20 00:00:00TO MISC BOX

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-04-21 Cont ID  
Sent By kstevens Date 2004-04-21 Time 13:57 Rev Time 1.00
Received By kstevens Date 2004-04-21 Time 13:57 Sent To  
Notes
2004-04-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FROM PREVIOUS REVIEWS: SUBMIT CALCU-
 LATIONS FOR PRIMARY AND SECONDARY ROOF
 DRAINS PER SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS.
 2) SHOW LOCATION OF ALL PRIMARY ROOF
 DRAINS. 104.2.1
 3) THE NEW PLANS HAVE NOT BEEN SUBMITTED
 AT THIS TIME. ONLY TWO SETS OF OLD
 SHEETS HAVE BEEN SUBMITTED. SUBMIT TWO
 SETS OF PLANS FOR REVIEW. SHEET 2 IS
 MISSING FROM BOTH OLD SETS OF PLANS.
 104.2.1
 4) SCUPPER DETAIL REQUIRED. 104.2.1
 5) A STORM RISER DIAGRAM IS REQUIRED IN
 ISOMETRIC FORM WITH ALL PIPE SIZES AND
 SHOW TERMINATION POINT. 104.3.1.1
 6) THE PERSON SEAL, SIGNATURE AND DATE
 OF THE ARCHITECT SHALL APPEAR ON ALL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD.
 ********THE DATE IS STILL MISSING*******
 FAC G161-16.003 & FS 481.2055.
 7) 4 TIMES THE FEE REQUIRED FOR PLAN RE-
 VIEW IS NOW BEING IMPOSED PER FS 533.80
 (2)(B). THE FEE WILL BE PAID AT THE TIME
 THE PLANS WILL BE PICKED UP. ($720.00)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-01-12 Cont ID  
Sent By kstevens Date 2004-01-12 Time 13:51 Rev Time 0.60
Received By kstevens Date 2004-01-12 Time 13:51 Sent To  
Notes
2004-01-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) FROM PREVIOUS REVIEW: RESPONSE NOTED:
 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW SQUARE FOOT-
 AGE OF ROOF AREA. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS. SEE
 SECTIONS 1106 & 1107 AND ALL SUBSECTIONS
 PRIMARY ROOF DRAINS SHALL BE INSTALLED
 IN THE "SHELL" PHASE OF THE BLDG.
 2) SCUPPER DETAIL DOES NOT SHOW THE
 WIDTH OF THE SCUPPERS.
 3) SUBMIT A STORM RISER DIAGRAM SHOWING
 ALL PIPE SIZES AND TERMINATION POINT.
 4) SHOW LOCATION OF ALL PRIMARY DRAINS.
 5) THE PERSONAL SEAL, SIGNATURE, AND
 DATE OF THE ARCHITECT SHALL APPEAR ON
 ALL DOCUMENTS TO BE FILED FOR PUBLIC
 RECORD. ***THE DATE IS STILL MISSING***
 61G1-16.003 & FS481.2055
 5) THE LICENSE NUMBER IS REQUIRED ON THE
 TITLE BLOCK ON EACH SHEET. 61G1-16.004
 FS481.2055
 6) SEE ATTATCHED SHT. CONCERNING FLORIDA
 STATUTE 533.80(2)(B).
 7) SUBMIT TWO COMPLETS SETS OF PLANS FOR
 REVIEW AND STAMPING. TWO OLD SETS AND
 ONE NEW SET WERE SUBMITTED THIS REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-12-15 Cont ID  
Sent By kstevens Date 2003-12-15 Time 17:57 Rev Time 0.50
Received By kstevens Date 2003-12-15 Time 17:57 Sent To  
Notes
2003-12-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106,
 AND 1107 AND ALL SUBSECTIONS. SHOW LOC-
 ATION OF ALL PRIMARY ROOF DRAINS AND
 THE LOCATION OF SECONDARY OR OVERFLOW
 SCUPPER DRAINS. SUBMIT A DETAIL OF
 SCUPPERS. IF GUTTER AND DOWNSPOUTS, SHOW
 THE SIZE OF THE GUTTERS PER TABLE 1106.6
 AND INDICATE SIZE OF DOWNSPOUTS. DOWN-
 SPOUTS SHALL TERMINATE MIN. OF 1' OFF
 SIDE OF STRUCTURE WALL.
 2) THE PERSONAL SEAL, SIGNATURE AND DATE
 OF THE ARCHITECT SHALL APPEAR ON ALL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD,
 ***THE DATE IS MISSING.*** 61G1-16.003
 FS 481.2055
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***