Plan Review Details - Permit 03110816
Plan Review Stops For Permit 03110816
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-02-27 Cont ID  
Sent By alange Date 2004-02-27 Time 15:59 Rev Time 0.50
Received By alange Date 2004-02-27 Time 15:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-25 Time 16:01 Rev Time 0.00
Received By alange Date 2004-02-27 Time 15:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-01-26 Cont ID  
Sent By pkrauss Date 2004-02-05 Time 12:15 Rev Time 1.00
Received By alange Date 2004-01-26 Time 11:31 Sent To  
Notes
2004-01-26 00:00:001.SUBMIT AN ADDITIONAL COPY OF PRODUCT
 APPROVALS FOR...GLASS MASONARY AND
 JENWELD STEEL DOOR AND PITTSBURG
 SILICONE SYSTEM.
 2.ENERGY CALCULATIONS NOT SIGNED.
 SUBMIT 2 SIGNED COPIES.
 3. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-29 Cont ID  
Sent By pkrauss Date 2004-01-26 Time 06:53 Rev Time 1.25
Received By alange Date 2003-12-29 Time 14:46 Sent To Z
Notes
2003-12-29 00:00:001.SUBMIT PRODUCT APPROVALS FOR GLASS
 BLOCK AND #11 FIBERGLASS EXTERIOR DOOR.
 2.SPECIFY SIZE AND TYPE OF SHEATHINGS
 USED.
 3.SPECIFY SIZE AND TYPE OF BEAM AND
 COLUMNS USED ON COVERED PORCH .
 4.SPECIFY TYPES OF SIMPSON TIES USED.
 5.WEST PALM BEACH AMENDMENT TO
 FLORIDABUILDING CODE 1804.1.7 HABITABLE
 AREAS SHALL BE 4" OBOVE FINISH GRADE.
 SHOW LOCATION OF FINISH GRADE.
 6.FLORIDA BUILDING CODE 1804.1.3
 THE BOTTOM OF FOUNDATIONS SHALL EXTEND
 NO LESS THAN 12" BELOW FINISH GRADE.
 7. SECTION 2... ARE YOU PUTTING TILE ON
 A FLAT ROOF?PLEASE VERIFY ROOFING
 PRODUCTS IN PLAN.
 8.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 9.NOC REQUIRED
  
 ANY QUESTIONS PLEASE CALL ME
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-01-23 Cont ID  
Sent By btrobaug Date 2004-01-23 Time 16:48 Rev Time 0.50
Received By btrobaug Date 2004-01-23 Time 16:18 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-11-25 Cont ID  
Sent By csiegber Date 2004-01-21 Time 14:34 Rev Time 0.50
Received By btrobaug Date 2003-11-24 Time 17:05 Sent To P
Notes
2003-11-24 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE REVISE THE PLANS TO INDICATE THE
 FOLLOWING FOR CODE COMPLIANCE.
  
 1} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER
 OFRECORD. PER FS/FAC 481.221 & 471.025
  
 2} PLEASE SEE THAT THE RISER INDICATES
 3-6/0 CONDUCTORS FEEDING PANEL"B".SHOW
 ACTUAL SIZE.SEE SCHEDULE.
  
 3} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210.52E.
  
 4} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2',6',12' RULE PER 210.52.
 SEE REVIEWED PLANS.
  
 6} NOTE # 13 IN ELECTRICAL NOTES
 INCORRECTLY REFERS TO SLEEPING ROOM
 RECEPTACLES BEING ARC FAULT,PLEASE SEE
 210.12 REFERS TO ALL BRANCH CIRCUITS.
  
 7} PLEASE NOTE THAT THE 200 AMP EXISTING
 PANEL IS MARKED AS MLO AND SHOWN AS MCB
 ON THE RISER,PLEASE CORRELATE.
  
 8} PLEASE SHOW THE LOCATION OF THE NEW
 A/C EQUIPMENT ON THE PLAN,AND THE
 LOCATION OF THE DISCONNECTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 16:01 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 16:01 Sent To B
Notes
2004-02-25 00:00:00TO AL DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-27 Cont ID  
Sent By csiegber Date 2004-01-27 Time 14:51 Rev Time 0.00
Received By csiegber Date 2004-01-27 Time 14:51 Sent To M
Notes
2004-01-27 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-21 Cont ID  
Sent By csiegber Date 2004-01-21 Time 14:34 Rev Time 0.00
Received By csiegber Date 2004-01-21 Time 14:34 Sent To E
Notes
2004-01-21 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-20 Cont ID  
Sent By csiegber Date 2003-11-20 Time 17:04 Rev Time 0.00
Received By csiegber Date 2003-11-20 Time 17:04 Sent To E
Notes
2003-11-20 00:00:00TO E/THRU TRADES AND RETURN TO Z FOR
 HISTORIC APPROVAL/DEE

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-02-05 Cont ID  
Sent By pkrauss Date 2004-02-05 Time 12:15 Rev Time 0.25
Received By pkrauss Date 2004-02-05 Time 12:13 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-01-26 Cont ID  
Sent By csiegber Date 2004-01-27 Time 14:51 Rev Time 0.33
Received By pkrauss Date 2004-01-26 Time 06:44 Sent To B
Notes
2004-01-26 00:00:00DENIED: 2ND REQUEST
 1.RETURN AIR FROM THE MASTER BEDROOM
 IS NOT SIZED PROPERLY.PER 2001 FBC(M)
 EXCEPTION #1 & 3, ALL SUPPLY AIR TO THE
 MASTER SUITE SHALL BE INCLUDED IN THE
 CALCULATION FOR TOTAL SUPPLY AIR.THE
 RETURN SHALL BE A MINIMUM OF 1 1/2 TIMES
 THE SQUARE INCHES OF THE SUPPLY AIR TO
 THAT AREA.
  
 2.PLEASE CLARIFY DUCT SIZE TO THE
 MASTER SUITE, 20" X 10"?IF THIS IS
 CORRECT THE MINIMUM SIZE FOR THE RETURN
 AIR JUMPER SHALL BE 20".
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-12-03 Cont ID  
Sent By btrobaug Date 2004-01-23 Time 16:48 Rev Time 0.35
Received By pkrauss Date 2003-12-03 Time 09:37 Sent To B
Notes
2003-12-03 00:00:00DENIED:
 PRE 2001 FBC(M) 601.4 - RETURN AIR IS
 REQUIRED FROM THE MASTER BEDROOM AREA.
 (SEE ATTACHED FOR SIZING REQUIREMENTS)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-12-22 Cont ID  
Sent By btrobaug Date 2003-11-25 Time 06:49 Rev Time 0.00
Received By alange Date 2003-12-22 Time 15:13 Sent To M
Notes
2003-12-22 00:00:00PASSED PER PAUL SCHIMITZ SIGNED ON PLAN
 ALANGE 12/22/03

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-31 Cont ID  
Sent By alange Date 2003-12-29 Time 14:46 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***