Plan Review Details - Permit 03110777
Plan Review Stops For Permit 03110777 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2004-01-07 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2004-01-07 |
Time |
10:16 |
Rev Time |
0.50 |
Received By |
alange |
Date |
2004-01-07 |
Time |
10:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2004-01-05 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-12-08 |
Time |
14:33 |
Rev Time |
0.75 |
Received By |
alange |
Date |
2004-01-05 |
Time |
11:24 |
Sent To |
|
|
Notes |
2004-01-05 00:00:00 | 1.PRODUCT APPROVALS FOR WINDOWS AND | | SHUTTERS ARE NOT APPROVED BY THE FBC | | PRODUCT APPROVAL SITE. | | PRODUCT APPROVALS SUBMITTED WITH PERMIT | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | 2.SUBMIT A WINDOW SCHEDULE SHOWING THE | | FOLLOWING: | | - LOCATION OF WINDOWS | | - SIZE OF WINDOWS | | - HEIGHT FROM FLOOR OF BEDROOM WINDOWS. | | | | ART LANGE | | BUILDING PLANS EXAMINER | | 561-805-6672 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
N |
Date |
2004-01-07 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-11-19 |
Time |
09:21 |
Rev Time |
0.33 |
Received By |
btrobaug |
Date |
2003-11-21 |
Time |
12:54 |
Sent To |
P |
|
Notes |
2003-11-21 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE SUBMIT A LOAD CALCULATION | | SHOWING EXISTING AND ALL NEW LOADS | | BEING ADDED(IG: A/C SYSTEM),ALSO | | INDICATE SIZE IN AMPERAGE,OF THE | | SERVICE, PER 215.5. | | | | AN ELECTRICAL PERMIT IS REQUIRED FOR | | THIS WORK.PLEASE HAVE THE ELECTRICAL | | CONTRACTOR SUBMIT PLANS SHOWING THE | | SCOPE OF HIS WORK WITH THE APPLICATION | | PER 104.2.1 FBC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-11-19 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-11-19 |
Time |
09:21 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-11-19 |
Time |
09:21 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2003-12-08 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2003-12-06 |
Time |
12:57 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2003-12-08 |
Time |
12:21 |
Sent To |
B |
|
Notes |
2003-12-08 00:00:00 | PLEASE PROVIDE THE FOLLOWING INFORMATION | | WITH MECHANICAL PERMIT APPLICATION: | | | | AS PER 2001 FBC CHAPTER 13 SUB-CHAPTER | | 101.4.1.1, PREVIOUSLY UNCONDITIONED | | BUILDINGS SHALL COMPLY WITH METHOD C OF | | SUB-CHAPTER 6 OR PROVIDE ENERGY AND | | MANUAL J CALCULATIONS.PLEASE PROVIDE | | PLANS & SPECIFICATIONS AS PER 2001 FBC | | CHAPTER 13 SUB-CHAPTER 103.2. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2003-12-06 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2004-01-07 |
Time |
11:31 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2003-12-06 |
Time |
12:55 |
Sent To |
M |
|
Notes |
2003-12-06 00:00:00 | FIXTURE CHANGE OUT ONLY |
|
|
|