Plan Review Details - Permit 03110633
Plan Review Stops For Permit 03110633
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-07-20 Cont ID  
Sent By csiegber Date 2004-07-22 Time 16:22 Rev Time 0.00
Received By rbrown Date 2004-07-20 Time 17:35 Sent To  
Notes
2004-07-20 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 DOOR SCHEDULE WAS REDLINED ON 7/20/04 BY
 THE ARCHITECT TO CHANGE DOOR #107 FROM A
 GLAZED INSWING DOOR TO A HOLLOW METAL
 INSWING DOOR DUE TO LACK OF PRODUCT
 APPROVAL FOR A GLAZED DOOR. IF THE SHEET
 IS SUBMITTED AGAIN AFTER PERMIT ISSUE,
 AS PART OF ANY REVISION, IT MUST
 INCORPORATE THE REDLINED AMENDMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-07-12 Cont ID  
Sent By rbrown Date 2004-05-19 Time 16:53 Rev Time 0.00
Received By rbrown Date 2004-05-19 Time 16:52 Sent To  
Notes
2004-07-16 00:00:00PLAN REVIEW COMMENTS AMENDED AGAIN.SEE
 BELOW.
 .
2004-07-12 00:00:00PLAN REVIEW COMMENTS HAVE BEEN AMENDED
 TO COVER THE ADDITIONAL PRODUCT
 APPROVALS SUBMITTED BY WEST CONSTRUCTION
 SEE AMENDED COMMENTS BELOW.
 .
2004-06-30 00:00:00PLAN REVIEW COMMENTS LISTED AS 5/19/04
 HAVE BEEN AMENDED TO COVER THE PRODUCT
 APPROVALS SUBMITTED AFTER THE INITIAL
 PLAN REVIEW.
 .
2004-05-19 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 WORKING DRAWING REVIEW ONLY.NO
 PERMIT CAN BE ISSUED UNTIL THE PERMIT
 APPLICATION AND FEES ARE SUBMITTED BY
 THE SELECTED CONTRACTOR.
  
 ADDRESS INFORMATIVE:
 OF THE PARCELS REFERENCED BY THE UNITY
 OF TITLE, THE ONE ADDRESSED 525 49TH ST
 HAS THE LOWEST PROPERTY CONTROL NUMBER
 (74-43-43-04-04-003-0351).THAT IS THE
 PROPERTY CONTROL NUMBER WHICH SHOULD BE
 USED TO REFERENCE THE SITE.DUE TO THE
 LOCATION OF THE ENTRANCE(S), THE DEFAULT
 ADDRESS 525 49TH ST IS NOT SUITABLE.
 NEW ADDRESSES MUST BE ASSIGNED.THE
 ADDRESSES FOR THE COMMUNITY/TRAINING
 ROOM AND THE FIRE RESCUE STATION MUST
 BE EVEN NUMBERS BETWEEN 5000 AND 5098
 AND THE COMMUNITY/TRAINING ROOM ADDRESS
 MUST BE NUMERICALLY LOWER THAN THE
 FIRE RESCUE STATION ADDRESS.THE
 COMMUNITY/TRAINING ROOM WILL BE A TENANT
 ADDRESS OF THE FIRE RESCUE STATION.
 **AS REQUESTED BY JEFF HALVERSON ON
 7/12/04 THE COMMUNITY/TRAINING ROOM
 ADDRESS WILL BE 5000 BROADWAY AND THE
 FIRE RESCUE STATION WILL BE
 5050 BROADWAY.
  
 PROVISO
 ON 7/20/04 THE DOOR SCHEDULE WAS RED-
 LINED BY ARCHITECT TO CHANGE DOOR #107
 FROM A GLAZED INSWING DOOR TO A HOLLOW
 METAL INSWING DUE TO LACK OF PRODUCT
 APPROVAL FOR THE GLAZED DOOR.IF THE
 SHEET IS SUBMITTED AGAIN AFTER PERMIT
 ISSUE, AS PART OF ANY REVISION, IT MUST
 INCORPORATE THE RED-LINED AMENDMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-04-28 Cont ID  
Sent By rbrown Date 2004-04-28 Time 13:50 Rev Time 0.00
Received By rbrown Date 2004-04-28 Time 13:50 Sent To  
Notes
2004-04-28 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 12/11/03:
  
 3) FBC 13-103ENERGY CODE COMPLIANCE
 (A) FBC 13-103.1.1.1IT IS NOTED THAT
 THE MECHANICAL ENGINEER HAS SIGNED
 SHEET 2 OF THE SUBMITTED ENERGY CODE
 COMPLIANCE FORMS.THE PROFESSIONALS
 RESPONSIBLE FOR THE DESIGN OF THE
 BUILDING SHELL AND THE ELECTRICAL,
 LIGHTING AND PLUMBING SYSTEMS SHALL EACH
 SIGN SHEET 2 OF THE ENERGY CODE CODE
 COMPLIANCE FORM, IN THE SPACE PROVIDED,
 TO CERTIFY COMPLIANCE.
 (B) FBC 13-103.1.2BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 4) PRODUCT APPROVAL FOR THE PROPOSED
 SPANISH 'S' TILE AND BUILT-UP ROOFING.
 THE RESPONSE REFERING TO NOTE 1 ON
 SHEET G-2 IS NOTED.PRODUCT APPROVALS
 MUST BE SUBMITTED BEFORE A PERMIT CAN BE
 ISSUED.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
  
 4) PRODUCT APPROVAL FOR THE PROPOSED
 WINDOWS, GLASS BLOCK, EXTERIOR DOORS AND
 SIDELITES, HURRICANE SHUTTERS AND ROLL-
 UP DOORS.THE RESPONSE REFERING TO
 NOTE 1 ON SHEET G-2 IS NOTED.PRODUCT
 APPROVALS MUST BE SUBMITTED BEFORE A
 PERMIT CAN ISSUED.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 6) SHEET A6.1AMEND THE WINDOW SCHEDULE
 TO STATE WINDOW TYPE AS FIXED, CASEMENT
 ETC SO THAT THE APPLICABILITY OF THE
 PRODUCT APPROVALS (SEE COMMENT #4) CAN
 BE VERIFIED WHEN THEY ARE SUBMITTED.
  
 13) SHEET S-2, ROOF FRAMING PLAN.THE
 SPECIFIED ANCHOR TYPE FOR THE MONOSLOPE
 ROOF IS TYPE J.THE TRUSS TIE DOWN
 SCHEDULE, ON SHEET S-3, STATES THE
 REFERENCE AS LUS26, WITH AN UPLIFT
 CAPACITY OF 1140#.THIS DOES NOT
 REFLECT THE 930# CAPACITY STATED IN THE
 2004 SIMPSON CATALOG.NEITHER CAPACITY
 IS SUFFICIENT FOR THE EXPECTED UPLIFT ON
 THE MONOSLOPE ROOF TRUSS.SPECIFY
 ALTERNATIVE ANCHORS AND CORRECT THE
 CAPACITY STATED ON THE SCHEDULE.
  
 15) THE REVISIONS MADE SINCE THE LAST
 REVIEW HAVE NOT BEEN HIGHLIGHTED BY
 REVISION CLOUDS/MARKERS AND ONE COPY OF
 THE OLD PLANS WAS NOT SUBMITTED.AS A
 RESULT THE PLANS HAVE BEEN SUBJECT TO
 ANOTHER FULL REVIEW, SEE COMMENTS
 NUMBERED 16 AND UP.
 NOTE:TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 COMMENTS RESULTING FROM SECOND FULL
 REVIEW OF PLANS PER COMMENT 15:
  
 16) FBC 11-4.8.2RAMP.SHEET A2.1 DOES
 NOT CLEARLY SHOW THE EXTENT OF THE RAMP
 FROM THE FOUNTAIN UP TO THE ENTRY TOWER
 AND THERE IS NO CROSS-SECTION SHOWING
 THE CHANGE IN LEVEL.AMEND THE PLANS TO
 PROVIDE THIS INFORMATION AND DEMONSTRATE
 PROVISION OF THE REQUIRED HANDRAILS AND
 A COMPLIANT RAMP SLOPE OF 1 IN 12 (OR
 BETTER).
  
 17) FBC 1608.2.1ALL HANDRAILS SHALL BE
 DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB AND A LINE
 LOAD OF 50 PLF.THESE LOADS SHALL NOT
 BE APPLIED SIMULTANEOUSLY BUT SHALL BE
 APPLIED INDIVIDUALLY AT ANY POINT, AND
 IN ANY DIRECTION, TO PRODUCE MAXIMUM
 STRESS IN EACH OF THE COMPONENTS OR
 SUPPORTS.AMEND/ANNOTATE THE PLANS.
 SEE ALSO FIRE PLAN REVIEW COMMENT.
  
 18) FBC 705.1.3GENERATOR ROOM DOOR.
 DOOR 147A IS IN A 2-HR FIRE-RATED WALL
 BUT IS NOT SHOWN AS RATED ON THE DOOR
 SCHEDULE (SHEET A6.1).AMEND THE DOOR
 SCHEDULE.
  
 19) BOUNDARY SURVEY SHT FP1977 (1 OF 2).
 THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.SUBMIT A COPY OF THE 'UNITY
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-11 Cont ID  
Sent By rbrown Date 2003-12-11 Time 14:24 Rev Time 0.00
Received By rbrown Date 2003-12-11 Time 14:24 Sent To Z
Notes
2003-12-11 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) WHEN THE PLANS ARE SUBMITTED FOR
 PERMIT, THE TITLE BLOCK ON EACH SHEET
 SHALL INCLUDE THE SIGNATURE, SEAL AND
 PRINTED LICENSE NUMBER OF ARCHITECT OR
 ENGINEER OF RECORD.
  
 2) THE PLANS ARE STATED AS BEING 90%
 COMPLETE.THE FOLLOWING REVIEW COMMENTS
 ARE BASED ON THE INCOMPLETE PLANS
 SUBMITTED.
  
 3) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 4) SUBMIT PRODUCT APPROVALS FOR THE
 SPANISH 'S' TILE AND FOR THE BUILT UP
 ROOFING.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 5) SUBMIT PRODUCT APPROVALS FOR THE
 WINDOWS, GLASS BLOCK, EXTERIOR DOORS AND
 SIDELITES, HURRICANE SHUTTERS AND ROLL-
 UP DOORS.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 6) SHEET A6.1THE WINDOW SCHEDULE IS
 INCOMPLETE.
  
 7) SHEET A2.5THE WALL TYPES PLAN
 LEGEND SHOULD BE AMENDED TO REFER TO
 SHEET A2.6 FOR THE WALL TYPE DETAILS.
 ALSO THE PLAN DOES NOT SHOW A WALL TYPE
 FOR MANY OF THE WALLS (JUST SHOWN AS
 TYPE X).
  
 8) FBC 2405.2SHEET A2.5 SHOWS A NUMBER
 OF INTERIOR WALLS WHICH APPEAR TO BE
 GLAZED WITHIN 24 INCHES OF DOORS.THESE
 ARE'HAZARDOUS LOCATIONS' AND ARE
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 9) FBC 11-4.24.4SHEET A5.3, SECTION 6A
 THE PANTRY SINK SHALL BE MAXIMUM 6-1/2"
 DEEP.ANNOTATE THE PLANS ACCORDINGLY.
  
 10) SHEET A6.4, SECTION 1.WHERE DOES
 THIS DETAIL OCCUR?SHOULD IT BE CALLED
 UP ON SHEET A4.3, SECTION 2?ANNOTATE
 THE PLANS TO SHOW THE LOCATIONS WHERE
 THIS DETAIL OCCURS.
  
 11) FBC TABLE 1606SHEET S-3, CODES
 AND STANDARDS NOTE #1.FOR A FIRE
 RESCUE STATION, THE IMPORTANCE FACTOR
 SHOULD BE 1.15 (NOT 1.0).AMEND THE
 NOTE AND MAKE ANY NECESSARY DESIGN
 CHANGES.
  
 12) SHEET S-3, WIND LOAD SCHEDULE.THE
 ZONE 3 ROOF WIND SUCTION LOAD SHOULD BE
 -78.3 PSF (NOT -38.3 PSF).AMEND THE
 PLAN.
  
 13) SHEET S-4, SECTION 6.THE MONOSLOPE
 TRUSSES FOR THE LOWER ROOF ARE SHOWN
 SUPPORTED BY LEDGERS BOLTED INTO THE
 BOND BEAM.SHEET S-2 (ROOF PLAN) SHOWS
 THE TRUSSES TIED DOWN WITH TYPE N
 ANCHORS WHICH ARE SIMPSON HHETA 20. THAT
 TYPE OF ANCHOR IS NOT SUITABLE FOR
 CONNECTION BETWEEN WOOD LEDGERS AND A
 WOOD TRUSS SUBJECT TO UPLIFT.AMEND THE
 PLAN TO SPECIFY A SUITABLE ANCHOR.
  
 14) INFORMATIVE:
 SHEET S-3, TRUSS TIE DOWN SCHEDULE.IT
 IS NOTED THAT ONLY ANCHOR TYPES B,D & N
 ARE SPECIFIED ON THE ROOF PLAN.NOTE
 THAT ANCHOR TYPES J & K ARE LISTED AS
 'HUGHES' ANCHORS, AND THAT COMPANY NO
 LONGER SUPPLIES TRUSS ANCHORS.
  
 15) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-05-19 Cont ID  
Sent By dpalmer Date 2004-05-19 Time 17:49 Rev Time 1.25
Received By dpalmer Date 2004-05-19 Time 17:49 Sent To  
Notes
2004-05-19 00:00:00REDLINED
  
  
 FOOTER STEEL REQ'D FOR GROUNDING ELEC-
 -TRODE 250.50
  
 GFI PROTECTION FOR KITCHEN RECEPTS PER
 210.8B3
  
 STAMPED PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-04-21 Cont ID  
Sent By dpalmer Date 2004-04-21 Time 16:38 Rev Time 3.00
Received By dpalmer Date 2004-04-18 Time 19:00 Sent To  
Notes
2004-04-21 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002
 PLEASE INCLUDE PRINTED NAME AND LICENSE
 # OF ENGINEER ON TITLE BLOCK.
  
 2)NOTE: PLEASE SEE SOME ITEMS ARE
 WHITED OUT ON PLANS. WHITE OUT IS NOT
 PERMITTED ON SIGNED AND SEALED PLANS.
 FS 471/481
  
 3)NOTE: PLEASE SUBMIT SPECIFICATIONS
 FOR GENERATOR/ATS/ ETC.
 PLEASE INDICATE IF MCB IS LOCATED ON
 THE OUTSIDE OF GENERATOR W/ OUT EXSPOS-
 -URE OF LIVE PARTS IN VIOLATION OF
 NEC 110.27
  
 4)NOTE: PLEASE SHOW/INDICATE POINTS
 OF CONNECTION FOR GROUNDING OF TRANS-
 -FORMERS PER 250.30
  
 5)NOTE: PLEASE SEE RISER, CONDUCTORS
 FEEDING LPD ARE SHOWN AS 1/0'S TO A
 225A PANEL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-03 Cont ID  
Sent By dpalmer Date 2003-12-03 Time 07:38 Rev Time 3.00
Received By dpalmer Date 2003-12-03 Time 07:27 Sent To  
Notes
2003-12-03 00:00:00************* UNSAT *******************
  
 1)NOTE: PLEASE HAVE PLANS SIGNED, DATED
 AND SEALED BY THE ENGINEER OF RECORD.
 PLEASE INCLUDE ALL LICENSE #`S ON TITLE
 BLOCK FOR ENG FIRM AND INDIVIDUAL THAT
 SEALS PLANS.:ABOVE PER: FS471.025 AND
 61G15-23.002 OF THE FAC.
  
 2)NOTE: PLEASE BE AWARE THAT THERE MAY
 BE OTHER COMMENTS TO FOLLOW AS PLANS/
 DRAWINGS ARE LABELED AS 90% COMPLETE AS
 OF SUBMITTAL FOR REVIEW.??
 UNABLE TO DO A COMPLETE REVIEW AT THIS
 DUE TO PLANS NOT BEING COMPLETE.
  
 PLEASE SUBMIT THE ABOVE INFOMATION FOR
 REVIEW. IF THERE ARE ANYQUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2004-04-22 Cont ID  
Sent By mamini Date 2004-04-22 Time 15:17 Rev Time 1.00
Received By mamini Date 2004-04-22 Time 15:17 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-12-05 Cont ID  
Sent By mamini Date 2003-12-05 Time 13:50 Rev Time 1.00
Received By mamini Date 2003-12-05 Time 13:50 Sent To  
Notes
2003-12-05 00:00:00FAILED:
 1. PLEASE PROVIDE STORM WATER
 CALCULATION FOR OUR REVIEW, INCLUDE
 PERVIOUS AND IMPERVIOUS AREA FOR TOTAL
 SITE.
 2. DCDA MUST BE INSTALLED ON PROPERTY
 AT BACK OF THE SIDEWALK.
 3. A CLEAN-OUT MUST BE INSTALLED IN
 SEWER LATERAL ON PROPERTY, BACK OF THE
 SIDEWALK.
 4. PLEASE SUBMIT CIVIL PLANS ONLY TO THE
 PUBLIC UTILITIES AND ENGINEERING FOR
 ALL THE CONNECTIONS TO CITY SERVICES AND
 THEIR REQUIREMENTS.
 5. PLEASE CONTACT RODNEY COMPO FOR
 INSTALLATION OF GREASE/WATER SEPARATOR,
 SIZE, LOCATION.TWO DETAILS SHOWN,SHEET
 C-4.2. 837-4051 EX. 4074
 6. ALL PARKING STALLS MUST BE PAINTED
 WITH DOUBLE 4" WIDE STRIPES, PLEASE
 REVISE DETAILS, SHEET C-4.3
 7. DUMPSTER INCLOSURE MUST BE SIZED AT
 MIN. 12'-6" OPENING BETWEEN THE POSTS
 AND 12'-0" DEEP.
 8. PULLOTION PREVENTION PLANS MUST BE
 INCLUDED IN CIVIL PLAN AND MUST BE
 INSTALLED IN THE FEILD PRIOR TO ANY
 EARTH/CONSTRUCTION WORK BEGINS.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-05-26 Cont ID  
Sent By mcarsill Date 2004-05-21 Time 13:31 Rev Time 0.00
Received By mcarsill Date 2004-05-21 Time 13:31 Sent To  
Notes
2004-05-21 00:00:001) ENSURE THAT A MINIMUM OF AT LEAST
 ONE FOOT CANDLE IS PROVIDED BY THE
 EMERGENCY LIGHTING SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-04-09 Cont ID  
Sent By mcarsill Date 2004-04-09 Time 11:22 Rev Time 0.00
Received By mcarsill Date 2004-04-09 Time 11:22 Sent To  
Notes
2004-04-09 00:00:001) ELECTRONIC SWITCHES, CHANIN AND
 LOCK REQUIRED ON BACKFLOW DEVICE.
 NO CHANGE NOTED TO PAGE C-4.2.
  
 2) DOOR 147A IS NOT RATED PER THE DOOR
 SCHEDULE. DOOR IS LOCATED IN RATED
 WALL THEREFORE AN OPENING PROTECTIVE
 IS REQUIRED. PLEASE REVISE PLANS
 AS NECESSARY.
  
 3) PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR HANDRAILS AND GUARDRAILS SHALL
 MEET THE FLORIDA BUILDING CODE AND
 THE FLORIDA FIRE PREVENTION CODE.
  
 4) THE ABOVE GROUND FUEL STORAGE TANK
 SHALL BE PROTECTED BY BOLLARDS TO
 PREVENT MECHANICAL DAMAGE, BE LABELED
 AS TO ITS DEISEL CONTENT, AND BE
 PLACARDED IN ACCORDANCE WITH NFPA
 704. ALSO NO SMOKING SIGNS SHALL
 BE PROVIDED.
  
 5) THE FIRE DEPARTMENT CONNECTION FOR
 THE FIRE SPRINKLER SYSTEM SHALL BE
 PROVIDED WITH CLEAR ACCESS AND BE
 PROVIDED WITH SEVEN FEET, SIX INCHES
 OF CLEARANCE.
  
 6) WHAT PREVENTS THE GENERATOR EXHAUST
 FROM BACKFEEDING INTO THE AIR EXHAUST
 LOUVERS.
  
 7) ALL SMOKE DETECTORS SHALL BE MOUNTED
 A MINIMUM OF THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
  
 8) PLEASE CLEARLY IDENTIFY ALL
 EMERGENCY LIGHT FIXTURES ON THE PLAN.
  
 9) THE OPENING FROM 50TH STREET SHOULD
 BE WIDER BECAUSE SERVICE VEHICLES WILL
 HAVE TO ENTER THOUGH THE SEPARATED
 OPENING. THESE INCLUDE SANITATION
 TRUCKS AND FUEL TRUCKS. THE DIVIDER
 SERVES NO REAL PURPOSE BUT WOULD
 PROVIDE A POTENTIAL FOR MISHAPS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-11-26 Cont ID  
Sent By mcarsill Date 2003-11-26 Time 17:20 Rev Time 0.00
Received By mcarsill Date 2003-11-26 Time 17:19 Sent To  
Notes
2003-11-26 00:00:001) SITE PLAN DOES NOT REFLECT
 EXISTING FIRE HYDRANT LOCATIONS.
  
 2) ELECTRONIC SWITCHES WILL BE REQUIRED
 ON THE FIRE LINE BACKFLOW DEVICE.
  
 3) THE AUTOMATIC GATE ON 50TH STREET
 SHALL PROVIDE AT LEAST 20 FEET IN
 CLEAR WIDTH.
  
 4) PLEASE INDICATE ON PLANS WHICH
 OFFICE WILL BE FOR THE FIRE
 PREVENTION BUREAU.
  
 5) NO FIRE EXTINGUISHER SHOWN
 IN COMMUNITY/TRAINING ROOM.
  
 6) ROOM NEAR RADIO EQUIPMENT IS
 NOT LABELED.
  
 7) PROVIDE DETAILS ON FUEL TANK.
 PLEASE DISPLAY BARRIER PROTECTION,
 WARNING LABELS, AND PROVIDE PRODUCT
 APPROVALS.
  
 8) ALL NEW STAIRS AND RAMPS SHALL
 HAVE HANDRAILS ON BOTH SIDES.
  
 9) ROOF PLAN DISPLAYS TWO KITCHEN
 SUPPLIES AND NO EXHAUST. PLEASE CORRECT.
 THE KITCHEN EXHAUST DUCT TERMINATION
 SHALL HAVE AT LEAST 10 FEET SEPARATION
 FROM KITCHEN SUPPLY.
  
 10) THE BUILDING ADDRESS IS REQUIRED
 ON THE CORRECT ELEVATION. A MINIMUM
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 11) THE FIRE HYDRANT AND THE FIRE
 DEPARTMENT CONNECTION SHALL BE
 PROVIDED WITH 7'-6" OF CLEARANCE.
  
 12) THE GENERATOR EXHAUST SHALL BE
 A MINIMUM OF AT LEAST 10 FEET FROM
 ANY BUILDING OPENINGS.
  
 13) THE LIGHTING PLAN DOES NOT MATCH
 THE LIFE SAFETY PLAN.
  
 14) THE FIRE ALARM SYSTEM IS TO BE
 UL LISTED FOR CENTRAL STATION SERVICE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-07-22 Time 16:22 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 16:22 Sent To B
Notes
2004-07-22 00:00:00TO RB DESK/TO ISSUE PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-18 Cont ID  
Sent By mmclean Date 2004-06-02 Time 15:27 Rev Time 0.00
Received By csiegber Date 2004-05-18 Time 16:14 Sent To  
Notes
2004-05-18 00:00:00TO COMM BD#38

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-08 Cont ID  
Sent By csiegber Date 2004-04-08 Time 12:54 Rev Time 0.00
Received By csiegber Date 2004-04-08 Time 12:54 Sent To  
Notes
2004-04-08 00:00:00TO COMM BD#38

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-11 Cont ID  
Sent By mmclean Date 2003-11-25 Time 10:13 Rev Time 0.00
Received By rbrown Date 2003-11-14 Time 09:11 Sent To  
Notes
2003-12-11 00:00:00WILL CHECK WITH MICHELLE MCLEAN RE:
 STATUS OF ZONING REVIEW (SEE FRONT
 SCREEN NOTE DATED 11/25/03)
2003-11-25 00:00:00TO COMM BD#37
2003-11-14 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-06-02 Cont ID  
Sent By pkrauss Date 2004-05-26 Time 06:55 Rev Time 0.55
Received By pkrauss Date 2004-05-25 Time 16:22 Sent To  
Notes
2004-05-26 00:00:00PROVISO:
 1.ADDITIONAL PERMITS REQUIRED FOR THE
 HOOD & FIRE SUPPRESSION.PLEASE PROVIDE
 PLANS WITH PERMIT APPLICATION.
  
 2.PROVIDE SUBMITTAL FOR TESTING OF
 THE CO SENSORS PRIOR TO FINAL INSPECTION
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-04-10 Cont ID  
Sent By pkrauss Date 2004-04-10 Time 08:25 Rev Time 0.45
Received By pkrauss Date 2004-04-10 Time 07:44 Sent To  
Notes
2004-04-10 00:00:00DENIED:
 1.PLAN SHEET M1.1 OUTSIDE AIR CALC FOR
 AHU 4 INDICATES 1 CFM PER SQ FT.PER
 2001 FBC (M) 403.4.1 MINIMUM VENTILATION
 SHALL BE 5 CFM PER PERSON OR 1.5 CFM PER
 SQ FT.
  
 2.PLAN SHEET M2.1 KEY NOTE #7
 INDICATES CO SENSOR SHALL BE SET AT 40
 PPM.PER 2001 FBC(M) 403.4 CO SENORS
 SHALL BE SET AT 25 PPM.PLEASE CLARIFY.
  
 SEE ALSO COMMENTS FROM ASST FIRE
 MARSHALL, MIKE CARSILLO.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-12-09 Cont ID  
Sent By pkrauss Date 2003-12-09 Time 09:11 Rev Time 4.00
Received By pkrauss Date 2003-12-09 Time 08:44 Sent To  
Notes
2003-12-09 00:00:00DENIED:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
 1.OUTSIDE AIR CALCUALTIONS PER 2001
 FBC(M) 403.3, FOR ALL AREAS.
  
 2.AHU #3 NOT LOCATION NOT SHOWN ON
 THE PLAN (MECH RM 106?).
  
 3.CU-5 INDICATED ON PLAN SHEET M2.1
 AND IS NOT LISTED ON THE EQUIPMENT
 SCHEDULE ON SHEET M4.1.PLEASE CLARIFY.
  
 4.VENTILATION FANS 6 & 7.PLEASE
 CLARIFY WHEN THESE FANS ARE IN OPERATION
 (WHILE ROLL-UP DOORS ARE CLOSED/OPEN?).
 WILL THE APPARATUS BAY HAVE MECHANICAL
 EXHAUST WHEN THE DOORS ARE CLOSED?
  
 5.PLAN SHEET A2.3 INDICATES 2 KITCHEN
 SUPPLY FANS AND NO KITCHEN EXHAUST.
 PLEASE NOTE, 10 FT SEPARATION BETWEEN
 EXHAUST TERMINATION & FRESH AIR INTAKES
 OR HORIZONTALLY FROM PARTS FOR THE SAME
 OR CONTIGUOUS BUILDINGS (REFERENCE A7.2
 EXHAUST FAN DETAIL).
  
 6.ADDITIONAL PERMIT REQUIRED FOR HOOD
 AND FIRE SUPPRESSION.PLEASE PROVIDE
 THE FOLLOWING INFORMATION WITH PERMIT
 APPLICATION.
 A) PLANS INDICATING DUCT LAYOUT
 B) TERMINATION OF EXHAUST
 C) CLEARANCE TO COMBUSTIBLES PER NFPA
 96 1-3.2 & 2001 FBC(M)506.3.8.
 D) MANUFACTURER SUBMITTAL FOR THE HOOD
 E) EXHAUST FAN SHALL BE A HINGED
 UPBLAST. (DETAIL M3.3)
 F) SHOW COMPLIANCE WITH NFPA 96 &
 FBC(M) 506.
  
 7. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
  
 8.PLAN SHEET P2.1 INDICATES FUEL OIL
 DAY TANK.SHEET E4.1 INDICATES THE DAY
 TANK IS A SUBBASE TO THE GENERATOR -
 PLEASE CLARIFY.
  
 9.ADDITIONAL PERMIT REQUIRED FOR FUEL
 OIL.
  
 10. PROVIDE PIPING DETAIL FOR THE
 CONDENSATE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-07-21 Cont ID  
Sent By kstevens Date 2004-05-25 Time 10:06 Rev Time 2.00
Received By kstevens Date 2004-05-22 Time 10:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-04-12 Cont ID  
Sent By kstevens Date 2004-04-12 Time 13:45 Rev Time 5.00
Received By kstevens Date 2004-04-12 Time 13:43 Sent To  
Notes
2004-04-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FROM PREVIOUS REVIEW: CONTACT RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE, INDUST-
 RIAL PRETREATMENT FOR SIZING OF OIL/
 WASTE INTERCEPTOR. WASTE ORD. #2938-96.
 (561) 837-4074. - RESPONSE NOTED BUT NOT
 SURE WHAT WAS REVISED. PLEASE CLARIFY.
 2) CLARIFICATION OF RESPONSE CONCERNING
 THE WATER SUPPLY TO FOUNTAIN. PLEASE IN-
 DICATE IF THE WATER SUPPLY TO FOUNTAIN
 WILL BE DIRECT TO FOUNTAIN OR WILL IT BE
 FILLED BY HOSE FROM A HOSE BIBB. IF
 DIRECTLY TIED IN A BACKFLOW WILL BE RE-
 QUIRED ON THE SUPPLY LINE.
 3) IRRIGATION SHEETS, A CERTIFICATE OF
 AUTHORIZATION NUMBER IS REQUIRED ON THE
 TITLE BLOCK PER FS 481.219(2)(3)
 4) SHTS P2.1, P2.3, (DETAIL 7), & P3.1
 THE TRIAGE SINK SHALL NOT DRAIN THROUGH
 THE WET VENTED HORIZONTAL DRAIN FOR THE
 BATHROOM FIXTURES. SECTION 909.1 THE
 SINK SHALL DISCHARGE DOWNSTREAM OF THE
 BATHROOM FIXTURES.
 5) SHTS P2.1, & P3.1 (SANITARY RISER
 DIAGRAM), THE FLOOR DRAIN IN ROOM #145
 BY THE COMPRESSOR REQUIRES A VENT.
 SECTION 901.2.1
 6) SHTS P2.1, P2.3 (DETAIL 5), & P3.1
 SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN. FLOOR DRAIN OUTSIDE THE
 SHOWERS IS NOT SHOWN ON RISER DIAGRAM.
 7) SHT 3.2 WATER RISER DIAGRAM. WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9 (AT WASH MACHINE, ICE MAKERS, AND
 DISH WASHER), OR ANY OTHER QUICK CLOSING
 VALVES SHALL BE SHOWN ON RISER DIAGRAM.
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE
 NOT IN THE CEILING. PDI-WH 201 AND MANUF
 INSTALLATION INSTRUCTIONS.
 8) SHT P3.2 GAS ISOMETRIC RISER DIAGRAM,
 2" PIPE REQUIRED UP TO WHERE THE LINE TO
 THE STOVE/RANGE CONNECTS TO THE GAS MAIN
 (INFORMATIONAL - 1" MINIMUM REQUIRED TO
 WATER HEATER "2 - SHOWS 1-1/4" NOW).
 9-ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-12-08 Cont ID  
Sent By kstevens Date 2003-12-08 Time 06:08 Rev Time 1.50
Received By kstevens Date 2003-12-08 Time 06:08 Sent To  
Notes
2003-12-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 FUEL GAS
 FLA. ADMIN. CODE
 FLA STATUTES
  
 1) SHTS C-2.1 & C-4.1 WATER SERVICE IN-
 DICATES A PRESSURE VAC BREAKER ON THE
 WATER SERVICE. AN RPZ BACKFLOW IS REQ-
 UIRED. 608.13.2
 2) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE, INDUSTRIAL PRETREATMENT FOR
 SIZING OF OIL/WATER INTECEPTOR. WASTE
 ORD. #2938-96. (561) 837-4074
 3) SHT L1 MORE INFORMATION REQUIRED ON
 THE FOUNTAIN. WILL THERE BE DRAINAGE OR
 WATER SUPPLIED TO THE FOUNTAIN?
 4) SEPARATE PLANS/PERMIT REQUIRED FOR
 IRRIGATION.
 5) SHT A2.4 EQUIPMENT & ACCESSORIES SHC-
 EDULE. CLAIRFY #42 GAS LINE OUTLET, IS
 THIS NATURAL GAS, OR A FUEL LINE FOR THE
 TRUCKS?
 6) SHT A5.1 TOILET ROOMS #113 & 122
 SHOWER STALLS SHALL BE ACCESSIBLE. SHOW
 BENCH REQUIRED IN STALLS.
 7) SHT A5.1 DRINKING FOUNTAIN SHALL BE
 ACCESSIBLE. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH 11-4.15 AND ALL SUB-
 SECTIONS. ALSO SHOW COMPLIANCE WITH
 11-4.1.3(10)(A) PROVISI0NS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 8) SHT P2.2 THE FOLLOWING INFORMATION
 WILL BE REQUIRED FOR GAS PERMIT APPLIC-
 ATION. (SEPARATE PERMIT REQUIRED)
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 9) SHT P2.3 INDIRECT WASTE FOR ICE MAKER
 SHALL BE A FLOOR SINK. FLOOR DRAINS ARE
 NOT APPROVED FOR INDIRECT WASTE. 802.3
 10) SHT P2.3 KITCHEN/DINING ROOM. IN-
 DIRECT WASTE REQUIRED FOR ICE MAKER ON
 THE COUNTER. SUBMIT A DETAIL. 802.1.1
 11) PLANS SHALL BE SIGNED. SEALED, AND
 DATED BY THE ENGINEER/ARCHITECT OF REC-
 ORD. INCLUDE ALL LICENSE NUMBERS ON
 TITLE BLOCK AND CERTIFICATE OF AUTHOR-
 IZATION IF APPLICABLE. 61G15-23.002/FS
 471.025 - 61G1-16.003-.004/FS481.2055
 12) OTHER COMMENTS MAY FOLLOW AS THIS
 PLAN REVIEW SHOWS THAT PLANS ARE ONLY
 90% COMPLETE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2004-06-02 Cont ID  
Sent By mmclean Date 2004-06-02 Time 15:27 Rev Time 0.00
Received By mmclean Date 2004-06-02 Time 15:27 Sent To I
Notes
2004-06-02 00:00:00APPROVED BY ROBIN SINGER, PLANNING &
 ZONING ADMINISTRATOR 659-8031 MM

Review Stop Z ZONING
Rev No 2 Status F Date 2004-04-22 Cont ID  
Sent By sgraham Date 2004-04-22 Time 15:59 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2004-04-22 00:00:002ND CHECKLIST
 1. PERCENTAGE OF OPENING IN FACADE ARE
 REQUIRED TO BE BETWEEN 25 & 45%.
 CALCULATION INDICATE 12.85%
 2. PLEASE DIMENSION FULL WIDTH OF S/W
 UPUBLIC & PRIVATE) MIN. 8' REQUIRED
 3. INDICATE PARKING CALCULATIONS ON PLAN

Review Stop Z ZONING
Rev No 1 Status F Date 2004-01-13 Cont ID  
Sent By rbrown Date 2003-12-11 Time 17:40 Rev Time 0.00
Received By mmclean Date 2004-01-13 Time 16:08 Sent To  
Notes
2004-01-13 00:00:00DENIED BY ROBIN SINGER - NEED A FULLY
 DIMENSIONED SITEPLAN TO COMPLETE REVIEW.
 PARKING SPACES, DRIVE ASLES & LANDSCAPE
 BUFFERS NOT DIMENSION.
 - PARKING SPACES MUST BE DOUBLE STRIPED
 DETAIL C4.3 SHOWS SINGLE STRIPING
 -FENCE GATE EXCEEDS ALLOWABLE HEIGHT
 (72"+10% OF HEIGHT FOR DECOATIVE ELEMENT
 -34 PARKING SPACES REQUIRED, 30SHOWN.
 PLEASE PROVIDE PARKING CALCUATIONS
 -MAIN PEDESTIAN ENTRY MUST FACE THE
 SHEET. SUGGEST OPENING UP ENTRY NEXT TO
 OFFICE @ TOWER.RAILING SHOWN ON
 ELEVATION BUT DOES NOT SHOW UPON SITE OR
 FLOORPLAN PLEASE CLARIFY.
 -NEED CALCULATIONS FOR % OF OPENINGS IN
 FACADE
 -PLEASE PROVIDE LANDSCAPE CALCULATIONS.
 BASED ON OPEN SPACE & LINEAR BUFFER 101-
 118 TREES.PLANS SHOWS 79 TREES
 -BUFFER WALL NEXT TO RESIDENTIAL SHOULD
 DROP TO 30", 20FT FRON 49TH & 50TH ST
 -VARIANCES TO NUMMERIAL & DIMENSIONAL
 REQUIREMENTS ARE POSSIBLE NEED THE
 ABOVE INFORMATION TO DETERMINE WHAT
 VARIANCE ARE NECESSARY
 - MECHANICAL EQUIPMENT MUST BE SCREENED
 BACK IS NOT
 -8FT SIDEWALK REQ'D ALONG BROADWAY
2003-11-25 00:00:0011/25/03 ZONING WILL REVIEW LAST MM