Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-02-20 Cont ID  
Sent By btrobaug Date 2004-02-20 Time 12:17 Rev Time 1.00
Received By btrobaug Date 2004-02-20 Time 11:35 Sent To  
Notes
2004-02-20 00:00:00 
 PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW PRIOR TO FINAL INSPECTION.
  
 1} ITEM #2 FROM LAST REVIEW WAS NOT
 ADDRESSED. SUBMIT A PANEL SCHEDULE
 INDICATING WIRE AND OCP SIZES.
  
 2} ITEMS #4 & 5 FROM LAST REVIEW ARE
 REDLINED ON THIS PLAN FOR COMPLIANCE,
 SHOW ACTUAL LOCATION ON RESUBMITTED
 PLANS.
  
 3} SHOW LOCATION OF THE PANEL ON THE 2ND
 FLOOR.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-01-30 Cont ID  
Sent By csiegber Date 2004-02-17 Time 16:35 Rev Time 1.00
Received By btrobaug Date 2004-01-30 Time 13:37 Sent To  
Notes
2004-01-30 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} REGARDING THE PANEL RELOCATION
 SUBMITTHE FOLLOWING:
 A) A RISER DIAGRAM OF RELOCATED
 EQUIPMENT.
 B) DISCONNECTING MEANS FOR THE CIRCUITS
 REFEEDING THE HOUSE PER 225.31.
 C) GROUNDING PER 250.32.
 D) AIC FOR EQUIPMENT PER 110.9 & 110.10
 EVEN IF REUSING THE SAME EQUIPMENT
 THE AIC CALC WILL CHANGE DEPENDING
 ON THE LENGTH OF WIRE FROM THE
 TRANSFORMER LOCATION.
  
 2} A PANEL SCHEDULE INDICATING WIRE AND
 OCP SIZES SO AS TO DETERMINE COMPLIANCE
 WITH CODE ARTICLES IG: 210.11(C)(1),(2)
 & (3). 210.12 ETC.
  
 3} A LOAD CALCULATION PER 215.5.
  
 4} INDICATE COMPLIANCE WITH 210.63 IF
 APPLICABLE.
  
 5} INDICATE COMPLIANCE WITH 210.52(E).
  
 6} THERE MAY BE ADDITIONAL COMMENTS WHEN
 THE PLANS ARE RESUBMITTED FROM THE
 ARCHITECT.
  
 7} PLEASE NOTE THAT TWO SETS OF PLANS
 ARE REQUIRED TO BE SUBMITTED FOR REVIEW
 PER 104 FBC.
  
 8} ALL PLANS CONTAINING AN ARCHITECTS
 SEAL ARE REQUIRED TO BE PREPARED BY HIM.
 PLEASE ALSO INCLUDE CERTIFICATE OF
 AUTHORIZATION NUMBERS WHERE REQUIRED.
 ALSO A TITLE BLOCK IS REQUIRED.SEE
 FS 481.219, FAC 61G1-16.004 FOR ABOVE
 STATED REQUIREMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-11-20 Cont ID  
Sent By csiegber Date 2003-11-12 Time 11:19 Rev Time 0.50
Received By btrobaug Date 2003-11-20 Time 12:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-17 Cont ID  
Sent By csiegber Date 2004-02-17 Time 16:35 Rev Time 0.00
Received By csiegber Date 2004-02-17 Time 16:35 Sent To E
Notes
2004-02-17 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-12 Cont ID  
Sent By csiegber Date 2003-11-12 Time 11:19 Rev Time 0.00
Received By csiegber Date 2003-11-12 Time 11:19 Sent To E
Notes
***NONE***