Plan Review Details - Permit 03110332
Plan Review Stops For Permit 03110332
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-04-19 Cont ID  
Sent By alange Date 2004-04-19 Time 13:34 Rev Time 0.60
Received By alange Date 2004-04-19 Time 13:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-22 Cont ID  
Sent By alange Date 2004-01-22 Time 09:57 Rev Time 1.00
Received By alange Date 2004-01-22 Time 09:57 Sent To  
Notes
2004-01-22 00:00:00PROVISO
 BATHROOMS SHALL COMPLY WITH THE
 FOLLOWING.
 1. FBC 11-4.22.3 CLEAR FLOOR SPACE
 2. FBC11-4.2.3 WHEEL CHAIR TURNING SPACE
 THE SPACE REQUIRED FOR A WHEEEL CHAIR
 TO MAKE A 180 DEGREE TURN IS A CLEAR
 SPACE OF 60 INCHES.
 SEE ATTACHED DETAIL.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-02 Cont ID  
Sent By lmartine Date 2003-12-02 Time 17:26 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2003-12-02 00:00:00 
 BUILDING REVIEW COMMENTS
  
  
 WHEN CHANGING OCCUPANCY USE FROM
 RESIDENTIAL TO COMMERCIAL, ALL AREA'S
 WITHIN THE SPACE SHALL COMPLY WITH
 FLORIDA BUILDING CODE CHAPTER 11 FOR
 ACCESSIBILITY REQUIREMENTS.
  
  
  
  
  
  
 L. MARTINEZ
 805-6710

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-04-15 Cont ID  
Sent By dpalmer Date 2004-04-15 Time 14:37 Rev Time 0.33
Received By dpalmer Date 2004-04-15 Time 14:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-03-08 Cont ID  
Sent By dpalmer Date 2004-03-08 Time 16:52 Rev Time 0.33
Received By dpalmer Date 2004-03-08 Time 16:52 Sent To  
Notes
2004-03-08 00:00:00LETTERS BACK FROM ELECTRICAL INSPECTOR.
 OK.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-01-02 Cont ID  
Sent By csiegber Date 2004-02-25 Time 09:44 Rev Time 0.33
Received By dpalmer Date 2004-01-02 Time 05:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-11-07 Cont ID  
Sent By dpalmer Date 2003-11-07 Time 06:26 Rev Time 0.33
Received By dpalmer Date 2003-11-07 Time 06:26 Sent To  
Notes
2003-11-07 00:00:00******************** UNSAT *************
  
 RESIDENTIAL TO COMMERICAL
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULE(
 S) TO BE SUBMITTED.
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.
  
 2)NOTE: PLEASE SEE 600.5 FOR REQ'D
 SIGN CIRCUIT.
  
 3)NOTE: PLEASE SHOW LOAD CALC FOR
 COMMERICAL USE. PLEASE INCLUDE ALL
 CONTINUOUS LOADS AT 125%. 215.3,230.42
 ETC.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWS
 THAT MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-04-16 Cont ID  
Sent By mcarsill Date 2004-04-16 Time 09:07 Rev Time 0.00
Received By mcarsill Date 2004-04-16 Time 09:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-12-29 Cont ID  
Sent By mcarsill Date 2003-12-29 Time 16:41 Rev Time 0.00
Received By mcarsill Date 2003-12-29 Time 16:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-11-14 Cont ID  
Sent By mcarsill Date 2003-11-14 Time 15:44 Rev Time 0.00
Received By mcarsill Date 2003-11-14 Time 15:44 Sent To  
Notes
2003-11-14 00:00:001) PLEASE LABEL AREAS ON PLAN.
  
 2) PLEASE INDICATE ANY NEW OR EXISTING
 FIRE ALARM EQUIPMENT.
  
 3) PLEASE INDICATE RATED DEMISING WALLS.
  
 4) PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-02 Cont ID  
Sent By csiegber Date 2004-04-02 Time 10:18 Rev Time 0.00
Received By csiegber Date 2004-04-02 Time 10:18 Sent To  
Notes
2004-04-02 00:00:00TO COMM BD#1

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 09:44 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 09:44 Sent To E
Notes
2004-02-25 00:00:00TO DP DESK/SUBMITTAL FROM INSPECTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-23 Cont ID  
Sent By csiegber Date 2003-12-23 Time 09:20 Rev Time 0.00
Received By csiegber Date 2003-12-23 Time 09:20 Sent To  
Notes
2003-12-23 00:00:00TO COMM BD#6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-02 Cont ID  
Sent By lmartine Date 2003-12-02 Time 17:39 Rev Time 0.00
Received By lmartine Date 2003-11-06 Time 16:04 Sent To  
Notes
2003-11-06 00:00:00TO COMM BD#4

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-04-15 Cont ID  
Sent By pkrauss Date 2004-04-15 Time 15:11 Rev Time 0.30
Received By pkrauss Date 2004-04-15 Time 15:11 Sent To  
Notes
2004-04-15 00:00:00PER CONVERSATION WITH DEBRA NICHOLS,
 EXISTING EQUIP; CARRIER FA4ANC024005AFAA
 (2) UNITS TOTAL AIR WILL NOT EXCEED
 2,000 CFM, DUCT SMOKE DETECTORS NOT
 REQUIRED.NO COMBUSTIBLES ARE IN THE
 EXISTING RETURN AIR PLENUM.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2004-04-06 Cont ID  
Sent By pkrauss Date 2004-04-06 Time 14:46 Rev Time 0.40
Received By pkrauss Date 2004-04-06 Time 14:46 Sent To  
Notes
2004-04-06 00:00:00DENIED:
 BUILDING WAS ORIGINALLY APPROVED FOR
 RESIDENTIAL.THE FOLLOWING SHALL BE
 ADDRESSED FOR CODE COMPLIANCE FOR
 COMMERCIAL STANDARDS:
  
 1.OUTSIDE AIR CALCULATIONS PER 2001
 FBC(M) 403.3.
  
 2.INDICATE O.A. INTAKE, DUCT SIZE,
 MATERIAL, AND LAYOUT.
  
 3.PLEASE CLARIFY RETURN TO THE AHU.
 IS THIS A PLENUM?PER 2001 FBC(M)
 602.2.1, NO COMBUSTIBLES ALLOWED ABOVE
 THE CEILING IN THE RETURN AIR PLENUM.
  
 4.DUCT SMOKE DETECTORS REQUIRED WHERE
 SYSTEMS HAVE AN AGGREGATE SUPPLY GREATER
 THAN 2,000 CFM.2001 FBC(M) 606.2.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-06 Cont ID  
Sent By pkrauss Date 2004-01-06 Time 07:45 Rev Time 0.40
Received By pkrauss Date 2004-01-06 Time 07:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-12-01 Cont ID  
Sent By hmoser Date 2003-12-01 Time 17:44 Rev Time 0.50
Received By hmoser Date 2003-12-01 Time 17:44 Sent To  
Notes
2003-12-01 00:00:00PLAN DENIED
 NEED DUCT & GRILL SIZE,AND CFM ON NEW
 A/C VENTS.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***