Plan Review Details - Permit 03110048
Plan Review Stops For Permit 03110048
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-06-08 Cont ID  
Sent By rmcdouga Date 2004-06-08 Time 08:42 Rev Time 2.00
Received By rmcdouga Date 2004-06-08 Time 08:42 Sent To  
Notes
2004-06-08 00:00:00BUILDING PROVISO
  
 1) STRUCTURE IS LOCATED IN AN "A5" FLOOD
 ZONE AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 2) THE STATE PRODUCT APPROVAL FOR THE
 WOOD FRENCH DOOR IS PENDING. AN APPROVED
 STATUS FROM THE STATE OR LOCAL PRODUCT
 APPROVAL WILL BE REQUIRED BEFORE A C.O.
 IS ISSUED.
  
 3) SEPARATE PERMITS WILL BE REQUIRED FOR
 SUBCONTRACTORS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-06-01 Cont ID  
Sent By dpalmer Date 2004-06-07 Time 07:56 Rev Time 3.00
Received By rmcdouga Date 2004-06-01 Time 13:38 Sent To Z
Notes
2004-06-01 00:00:00BUILDING DENIED
  
 1)SUBMIT STATE OR LOCAL PRODUCT APPROVAL
 FOR THE FOLLOWING:
 - THREE PANEL SLIDING GLASS DOOR
 - SOLID CORE OUTSWING DOOR AT GARAGE
 - STRUCTURAL WINDOW MULLIONS (IMPACT)
  
 2) THE STATE PRODUCT APPROVAL FOR THE
 WOOD FRENCH DOORS IS LISTED AS PENDING.
 AN APPROVED STATUS IS REQUIRED BEFORE A
 C.O. WILL BE ISSUED OR LOCAL PRODUCT
 APPROVAL CAN BE APPLIED FOR.
  
 3) THE STRUCTURE IS LOCATED IN AN "A5"
 FLOOD ZONE, AN ELEVATION CERTIFICATE
 WILL BE REQUIRED. THE LOWEST FLOOR
 ELEVATION IS REQUIRED TO BE 6" ABOVE
 BASE FLOOD ELEVATION PER CITY OF WPB
 MUNICIPLE CODE.
  
 4) ENGINEERED HAMBRO FLOOR SYSTEM
 DRAWINGS ARE TO BE REVIEWED AND APPROVED
 BY THE DESIGNER OF RECORD. HAVE THEM
 STAMPED AND SIGNED BY HIM AS REVIEWED
 AND ACCEPTED.
  
 5) SUBMIT THE INSTALLATION MANUAL FOR
 THE HAMBRO FLOOR SYSTEM.
  
 6) THE ORIGIONAL PERMIT APPLICATION IS
 NOT WITH THIS RESUBMITTAL. ADDITIONAL
 FEES WILL BE REQUIRED TO ADD SUBS TO
 THIS PERMIT OR SEPARATE PERMITS WILL BE
 REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-04-20 Cont ID  
Sent By jleech Date 2004-05-29 Time 12:22 Rev Time 2.00
Received By rmcdouga Date 2004-04-19 Time 16:21 Sent To  
Notes
2004-04-19 00:00:00DENIED
  
 1)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2) SUBMIT STATE OR LOCAL PRODUCT
 APPROVAL FOR THE FOLLOWING ITEMS:
 - GARAGE DOORS
 - ARCHED TOP (DESIGNER) FIXED WINDOWS
 - MULTIEDGED FIXED GLASS WINDOW
 - THREE PANEL SLIDING GLASS DOOR
 - SOLID CORE OUTSWING DOOR AT GARAGE
 - CASEMENT WINDOW
 - STRUCTURAL MULLIONS
  
 3) IN ADDITION TO THE MIAMI-DADE NOAS
 SUBMITTED FOR THE FRENCH DOORS AND THE
 SLIDING GLASS DOORS (TWO PANEL), STATE
 OR LOCAL PRODUCT APPROVAL IS REQUIRED.
 SUBMIT COVERSHEETS FROM STATE DCA
 WEBSITE WITH FLORIDA PRODUCT APPROVAL
 NUMBER OR LOCAL PRODUCT APPROVAL
 APPLICATION FORM.
  
 4) THE STRUCTURE IS LOCATED IN AN "A5"
 FLOOD ZONE, AN ELEVATION CERTIFICATE
 WILL BE REQUIRED. THE LOWEST FLOOR
 ELEVATION IS REQUIRED TO BE 6" ABOVE
 BASE FLOOD ELEVATION PER CITY OF WPB
 MUNICIPAL CODE.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND UL OR OTHER LISTING INFORMATION FOR
 THE GAS BBQ SHOWN ON THE PLANS.
  
 6) SEVERAL NOTES ON SHEET S3 SAY SEE
 SECTION A. HOWEVER, NO SECTION A IS
 GIVEN. PLEASE CLARIFY.
  
 7) SUBMIT SIGNED AND SEALED ENGINEERED
 SHOP DRAWINGS AND LAYOUT FOR THE HAMBRO
 FLOOR SYSTEM THAT HAS BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD.
  
 8) SUBMIT THE INSTALLATION MANUAL FOR
 THE HAMBRO FLOOR SYSTEM.
  
 9) SPECIFY THE WELD TYPE AND THICKNESS
 FOR THE CONNECTION OF THE HAMBRO FLOOR
 JOISTS TO THE STEEL IMBEDS.
  
 10) SPECIFY ALL PERMANENT BRACING AND
 ATTACHMENTS FOR THE HAMBRO SYSTEM.
  
 11) CORRECT THE TYPO IN THE STAIR NOTES
 ON SHEET D2 WHERE DBC IS LISTED RATHER
 THAN FBC.
  
 12) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE MOUNT TYPE AND SPECIFIC
 ANCHORS THAT WILL BE USED FOR THE STORM
 PANELS, UNLESS ALL OF THE EXTERIOR
 GLAZING IS IMPACT RATED.
  
 13) ADDITIONAL FEES WILL BE CHARGED TO
 ADD SUBS TO PERMIT APPLICATION. ASK
 PERMIT CLERK WHEN RESUBMITTING TO ADD
 SUBCONTRACTORS TO PERMIT.
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-03-11 Cont ID  
Sent By kstevens Date 2004-04-17 Time 05:46 Rev Time 3.00
Received By rmcdouga Date 2004-03-11 Time 12:48 Sent To  
Notes
2004-03-11 00:00:00DENIED
  
 1) SUBMIT A SIGNED AND SEALED COPY OF A
 SUB-SURFACE SOIL TEST REPORT AS REQUIRED
 BY FBC 1804.2.2. THE REPORT SHALL
 CONTAIN THE CONCLUSIONS REACHED AS A
 RESULT OF THE TESTING AND SPECIFY THE
 SAFE BEARING CAPACITY OF THE SOIL.
  
 2)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE SAMPLE
 OF COVERSHEET FROM THE STATE WEBSITE FOR
 PGT SINGLE HUNG WINDOWS,ATTACHED.
 SUBMIT PRODUCT APPROVALS FOR EACH TYPE
 OF DOOR, WINDOW, ETC. THAT WILL BE
 INSTALLED IN THIS PROJECT.
  
 3) SUBMIT PRODUCT APPROVALS AS SPECIFIED
 ABOVE FOR THE FOLLOWING:
 - GARAGE DOORS
 - ARCHED WINDOWS
 - MULTIEDGED FIXED GLASS WINDOW
 - THREE PANEL SLIDING GLASS DOOR
 - CUSTOM DOORS AT ENTRY
 - SOLID CORE OUTSWING DOOR AT GARAGE
 - CASEMENT WINDOW
 - STRUCTURAL MULLIONS
  
 4) THE STRUCTURE IS LOCATED IN AN "A5"
 FLOOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 5) SPECIFY THE SIZES OF THE TWO ATTIC
 ACCESS OPENINGS AT THE SECOND FLOOR. SEE
 FBC 2309.6 (MIN.20"X 36").
  
 6) ENERGY CALCS. WERE NOT RESUBMITTED.
 SEE COMMENTS FROM SECOND REVIEW.
  
 7) SUBMIT MANUFACTURER'S SPECS. AND UL
 LISTING INFORMATION FOR THE GAS BBQ.
  
 8) SUBMIT SIGNED AND SEALED ENGINEERED
 SHOP DRAWINGS AND LAYOUT THAT HAS BEEN
 REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD.
  
 9) SPECIFY THE WELD TYPE FOR THE
 CONNECTION OF THE HAMBRO JOISTS TO THE
 STEEL EMBEDS.
  
 10)THE HAMBRO JOIST SPACING IS SPECIFIED
 AS 4'O.C. AND THE BEARING PLATES(EMBEDS)
 ARE SPACED 24"O.C. PLEASE CLARIFY. SEE
 SHEET S3.
  
 11) PROVIDE A DETAIL INDICATING THE
 ATTACHMENT OF THE CEILING TO THE HAMBRO
 FLOOR SYSTEM. INDICATE FURRING,FASTENERS
 SPACINGS,ETC.
  
 12) SPECIFY THE BRIDGING MATERIAL,
 SPACING, ATTCHMENT TO JOIST, ETC.FOR THE
 HAMBRO JOISTS ON THE PLANS.
  
 13) CORRECT THE TYPO IN THE STAIR NOTES
 ON D2 WHERE DBC SHOULD BE FBC.
  
 14) REVISE TRUSS CONNECTOR MARKS A4 AND
 A5 ON THE FIRST AND SECOND FLOOR ROOF
 PLANS ON S4 AND S5. THESE ID MARKS ARE
 NO LONGER LISTED IN THE REVISED TRUSS
 ANCHOR SCHEDULE.
  
 15) THE PRODUCT APPROVAL SUBMITTED FOR
 THE FRENCH DOORS IS FOR NON-IMPACT RATED
 DOORS. STORM PANELS WILL BE REQUIRED.
  
 16)PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS. UNLESS ALL
 EXTERIOR GLAZING IS IMPACT RATED.
  
 17) SEPARATE PERMITS WILL BE REQUIRED
 FOR OTHER TRADES THAT WERE NOT SIGNED ON
 PERMIT APPLICATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-01-26 Cont ID  
Sent By dpalmer Date 2004-03-03 Time 06:23 Rev Time 3.00
Received By rmcdouga Date 2004-01-26 Time 14:31 Sent To Z
Notes
2004-01-26 00:00:00DENIED
  
 1) BOTH SETS OF PLANS ARE REQUIRED TO BE
 STAMPED BY PB COUNTY FOR IMPACT FEES.
  
 2) SUBMIT A SIGNED AND SEALED COPY OF A
 SUB-SURFACE SOIL TEST REPORT AS REQUIRED
 BY FBC 1804.2.2.
  
 3)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 SUBMIT FOR ALL WINDOWS, DOORS, GARAGE
 DOORS, STORM PANELS, TRUSS CONNECTORS,
 ETC. THAT IS SPECIFIED ON THE PLANS.
  
 4) THE STRUCTURE IS LOCATED IN AN "A5"
 FLOOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED BEFORE THE C.O. IS ISSUED.
  
 5) SPECIFY THE SIZES OF THE TWO ATTIC
 ACCESS OPENINGS ON THE SECOND FLOOR.
  
 6) THE CONDITIONED FLOOR AREA LISTED ON
 THE ENERGY CALC. FORM DOES NOT AGREE
 WITH THE A/C AREA LISTED ON THE PLANS.
 THE FORM IS REQUIRED TO BE SIGNED AND
 DATED BY THE OWNER/AGENT.
  
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND LISTING INFORMATION FOR THE BBQ ON
 THE LANAI.
  
 8) INDICATE THE BEAM ELEVATIONS (TOB)
 ON SHEETS S1 AND S2.
  
 9) SPECIFY ON THE PLANS THAT THE WIRE
 MESH WILL BE SUPPORTED ON APPROVED
 SUPPORTS AT NO MORE THAN 3'OC PER FBC
 1909.3.
  
 10) SUBMIT SIGNED AND SEALED ENGINEERING
 FOR THE HAMBRO FLOOR SYSTEM.
  
 11) PLEASE UPDATE THE ANCHOR SCHEDULES
 ON S4 AND S5. FAC RULE 9B-72 REQUIRES
 TRUSS CONNECTORS TO HAVE STATE PRODUCT
 APPROVAL. THERE IS NO USP RTPGA
 CONNECTOR LISTED. SEMCO AND HUGHES ARE
 NO LONGER IN BUSINESS AND ARE NOT LISTED
 WITH THE STATE, PLEASE REMOVE REFRENCES
 TO THEM.
  
 12) 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS.INCREASE IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
 REVISE TRUSS ANCHOR SCHEDULE WITH VALUES
 THAT DO NOT INCLUDE THIS STRESS INCREASE
 SEE LATEST USP CATALOG.
  
 13) SPECIFY FIREBLOCKING ON THE WALL
 SECTIONS ON D1 AT THE INTERSECTIONS OF
 THE CONCEALED VERTICAL AND HORIZONTAL
 SPACES. SEE FBC 2305.1.
  
 14) CLARIFY ON THE STAIR DETAILS ON D2
 THAT THE HANDRAILS FOR THE CIRCULAR
 STAIRS ARE BETWEEN 34" AND 38" ABOVE THE
 LEADING EDGE OF THE TREADS AS REQUIRED
 BY FBC 1007.5.
  
 15)PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
 A SEPARATE PERMIT AND FEES WILL BE
 REQUIRED IF ALL INFORMATION IS NOT
 SUBMITTED BEFORE PERMIT IS ISSUED.
  
 16) SEPARATE PERMITS WILL BE REQUIRED
 FOR OTHER TRADES AS THEY WERE NOT SIGNED
 ONTO PERMIT APPLICATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-12 Cont ID  
Sent By pkrauss Date 2004-01-23 Time 13:52 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2003-12-11 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PLANS ARE REQUIRED TO BE SIGNED,
 SEALED AND DATED BY THE DESIGNER OF
 RECORD.
  
 4) INDICATE IN THE DESIGN INFORMATION ON
 A-3 THAT STRUCTURE IS DESIGNED AS
 ENCLOSED.
  
 5) SPECIFY THE REQUIRED BEARING CAPACITY
 OF THE SOIL ON THE PLANS.
  
 6) SUBMIT A SUB-SURFACE SOIL BEARING
 TEST REPORT AS REQUIRED BY FBC 1804.2.2.
  
 7) SPECIFY THE FINISH FLOOR ELEVATION ON
 THE PLANS. THE STRUCTURE IS LOCATED IN
 AN A5 FLOOD ZONE. A MINIMUM ELEVATION OF
 7'- 6" IS REQUIRED. AN ELEVATION
 CERTIFICATE WILL BE REQUIRED FOR C.O.
  
 8)PRODUCT APPROVALS SUBMITTED FOR PERMIT
 APPLICATIONS AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. SUBMIT PRODUCT APPROVALS FOR
 WINDOWS, DOORS, ROOFING, ETC.
  
 9) SUBMIT A SURVEY AND SITE PLAN FOR
 DETERMINING SETBACK REQUIREMENTS AND
 FBC TABLE 600.
  
 10) THE WORD WIDTH IS MISSING FROM THE
 NET CLEAR OPENING FOR THE EGRESS WINDOWS
 ON A-3.
  
 11) SPECIFY THE SIZES OF THE ATTIC
 ACCESSES ON A3 AND A4.
  
 12) SPECIFY THE WINDOW TYPES ON THE
 PLANS (I.E. SINGLE HUNG, FIXED, CASEMENT
 ETC.).
  
 13) THERE ARE ALOT OF ERRORS IN THE
 WINDOW LEGEND AND ON THE PLANS. THE
 SIZES & WINDOW TYPES, DO NOT CORRESPOND
 TO ELEVATIONS. PLEASE CORRECT.
  
 14) DIMENSION FROM FRONT OF STRUCTURE TO
 FRONT OF COVERED ENTRY IS NOT GIVEN.
 PROVIDE EXTERIOR WALL DIMENSIONS ON THE
 FLOOR PLAN.
  
 15) PROVIDE OVERALL DIMENSIONS FOR THE
 WALL SECTIONS ON S1 AND S2.
  
 16) SUBMIT UL LISTING INFORMATION FOR
 THE BBQ GRILL ON LANAI.
  
 17) PROVIDE AN EGRESS WINDOW AT THE
 STUDY OR SPECIFY ON THE PLAN THAT THIS
 ROOM WILL NOT BE USED FOR SLEEPING
 PURPOSES.
  
 18) INDICATE ON THE PLANS THAT TEMPERED
 GLASS IS REQUIRED IN BATHROOM WINDOWS IF
 SILL HEIGHT IS LESS THAN 60" ABOVE
 STANDING AREA PER FBC 2405.2.1. (IMPACT
 RESISTANT GLASS IS ACCEPTABLE)
  
 19) THE SECOND FLOOR BEDROOMS ARE
 REQUIRED TO COMPLY WITH FBC 1005.4 FOR
 EGRESS WINDOWS. (5.7 SQFT CLEAR OPENING
 AREA IS REQUIRED)
  
 20) INDICATE THE TOP OF BEAM ELEVATIONS
 ON SHEETS S1 AND S2.
  
 21) CORRECT FOOTING SIZE FOR FOOTING AT
 LIVING ROOM ON S1 THAT IS GIVEN AS 22"X
 42".
  
 22) SPECIFY THE SLAB THICKNESS, WIRE
 REINFORCEMENT SUPPORTED PER FBC 1909.3,
 VAPOR BARRIER AND TERMITE TREATED SOIL.
  
 23) INDICATE THAT TIE BEAM IS FOR THE
 SECOND FLOOR IS 8"X 12" EXCEPT AT
 OPENINGS.
  
 24) SUBMIT SIGNED AND SEALED ENGINEERING
 FOR THE HAMBRO FLOOR SYSTEM.
  
 25) SUBMIT MORE COMPLETE DETAILS FOR THE
 WOOD FRAME TOWER. SPECIFY DIMENSIONS,
 FRAMING DETAILS, CONNECTORS, EXTERIOR
 FINISH, FIRE BLOCKING, ETC.
  
 26) PLEASE REVISE THE TRUSS ANCHOR
 SCHEDULE S4 AND S5. THERE IS NO USP
 RTPGA836 CONNECTOR LISTED IN THE 2003
 USP CATALOG OR ON THE STATE PRODUCT
 APPROVAL LISTING. USE VALUES THAT DO NOT
 INCLUDE A ONE THIRD INCREASE IN THE
 STEEL CALCULATIONS PER FBC 1609.4.3.
 REVIEW THE UPLIFT CAPACITY FOR THE A6
 CONNECTOR IN THE SCHEDULE. DUE TO THE
 PROXIMITY OF THE THREE STRAPS, THE
 UPLIFT CAPACITIES ARE REDUCED BECAUSE
 OF OVERLAPPING CONE PULLOUTS OF THE
 CONCRETE BEAMS. REMOVE THE REFERENCE TO
 SEMCO AND HUGHES FROM THE SCHEDULES AS
 THEY NO LONGER EXIST.
  
 27) PROVIDE AN ID TAG ON S4 FOR THE
 LEDGER THAT TIES IT TO THE DETAIL ON D2.
 THE UPLIFT FOR ONE OF THE GIRDERS IS
 2100# WHICH EXCEEDS THE UPLIFT CAPACITY
 OF THE HUS28 HANGER. PLEASE CORRECT.
  
 28) PUT THE NOTE THAT CLARIFIES THE
 DETAIL "O" AND "Q" ON SHEET S5 WHERE
 THESE CONNECTORS ARE SPECIFIED.
  
 29) REVISE THE ROOFING NAIL TYPE THAT IS
 SPECIFIED ON D1. FOR A MEAN ROOF HEIGHT
 GREATER THAN 25' USE 8D RING-SHANK NAILS
 IN ZONE 3 AS REQUIRED BY THE CITY OF WPB
 AMENDMENTS TO FBC TABLE 2306.1.
  
 30) PROVIDE INTERIOR WALL DETAILS.
  
 31) SPECIFY FIRE BLOCKING ON THE WALL
 SECTIONS ON D1 AND THE TOWER DETAIL ON
 D2.
  
 32) THE 2 STORY WALL SECTION ON D1 SHOWS
 PRECAST LINTELS AT OPENINGS AND THE
 REST OF THE PLANS INDICATE POURED BEAMS.
 PLEASE REVISE.
  
 33) CLARIFY THE (2) 16" DIMENSIONS THAT
 ARE SHOWN AT THE FOOTER ON THE 2 STORY
 DETAIL ON D1.
  
 34) PROVIDE ADDITIONAL DETAILS FOR THE
 CIRCULAR STAIRS. SPECIFY THE WIDTH OF
 THE STAIRS, HANDRAILS 34"- 38" ABOVE THE
 LEADING EDGE OF TREADS PER FBC 1007.5,
 GUARDRAILS WITH INTERMEDIATE RAILS PER
 FBC 1015 AND SHOW COMPLIANCE WITH FBC
 1007.8.3 FOR MINIMUM TREAD DEPTHS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2004-06-07 Cont ID  
Sent By dpalmer Date 2004-06-07 Time 07:56 Rev Time 0.33
Received By dpalmer Date 2004-06-07 Time 07:56 Sent To B
Notes
2004-06-07 00:00:00REDLINED 400A MAIN ON OUTSIDE OF HOUSE.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2004-05-26 Cont ID  
Sent By csiegber Date 2004-06-03 Time 11:01 Rev Time 0.75
Received By dpalmer Date 2004-05-26 Time 07:54 Sent To P
Notes
2004-05-26 00:00:00************UNSAT **************
  
 1)NOTE: PLEASE SEE NEW SHEET E-1 IS NOW
 SUBMITTED W/OUT PRINTED NAME AND SIGNAT-
 -URE OF THE PERSON RESPONSIBLE FOR
 PLANS. FBC 104.2.1
 IF PLANS ARE DONE BY AN ARCH OR ENGINEER
 THEN A TITLE BLOCK WILL BE REQ'D WITH
 ALL INFORMATION AS SET FORTH IN
 FAC 61G1-16.004,61G15-23.002
 SIGNED, DATED AND SEALED BY SAID ARCH/
 ENGINEER.
  
 2)NOTE: PLEASE SEE SHEET E-2, NOTE 5
 FROM FIRST REVIEW NOT DONE. THIS CAN
 BE REDLINED.
  
 NOTE# 1 NEEDS TO BE ADDRESSED BEFORE
 STAMPING OF ELECTRICAL PLANS. PLANS
 ROUTED TO OTHER TRADES FOR REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-04-16 Cont ID  
Sent By alange Date 2004-05-24 Time 11:18 Rev Time 1.00
Received By dpalmer Date 2004-04-16 Time 18:40 Sent To P
Notes
2004-04-16 00:00:00************ UNSAT ***************
  
 PLEASE SEE COMMENTS BELOW AND ALL PREVI-
 -OUS COMMENTS. PLEASE CALL IF THERE ARE
 ANY QUESTIONS, OR IF A MEETING CAN BE
 SET UP TO GO OVER PLANS AND COMMENTS.
 PREVIOUS REVIEWS GAVE # FOR QUESTIONS.
  
 1)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU'S AND 10KW HEAT. A MIN OF 125%
 IS REQ'D. PLANS INDICATE 50A OCP FOR
 ALL THREE UNITS.
  
 2)NOTE: PLEASE SEE SERVICE RISER,
 PLEASE INDICATE METERCAN SIZE/AMPERAGE.
 PLEASE SEE RISER NOW SHOWS WHAT APPEARS
 TO BE A MAIN DISC? LOAD CALCS MENTION
 A 400A SERVICE, BUT MAIN DOES NOT INDI-
 -CATE THIS. SERVICE ENT CONDUCTORS ARE
 SHOWN AS 2/0'S, WHICH ARE ONLY RATED FOR
 A 200A SERVICE. PLEASE SEE 310.15B6 FOR
 MIN SIZE FOR 400A SERVICE.
  
 3)NOTE: PLEASE SEE RISER, WHAT APPEARS
 TO BE A RISER MAIN DOES NOT LIST OR
 INDICATE OCP/BRKRS TO SUB-FEED OF EACH
 200A PANELS. IF THIS IS A 400A SERVICE,
 WHERE IS THE OCP FOR 2/0'S TO EACH PANEL
 AND PANELS RATED FOR 200A'S???
  
 THIS IS ONLY A NOTE: PANELS ARE SHOWN AS
 MCB. PANELS SHOULD BE FED W/ OCP, MCB
 ARE NOT REQ'D BUT MAY BE INSTALLED.
 IF SHOWN ON PLANS THEN THEY WILL BE
 REQ'D TO BE INSTALLED.
  
 4)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR FOR 400A SERVICE. 250.66,310.
 15B6. 1/0 MIN.
  
 5)NOTE:PLEASE LABEL PANELS. PLEASE
 ALSO SEE RISER INDICATES 2/0'S FOR
 ONE PANEL BUT NOT THE OTHER.
 PLANS ONLY SHOW A METERCAN ON OUTSIDE OF
 HOUSE.
  
 NEW NOTE:
 6)NOTE: PLEASE INDICATE REQ'D LT/RECEPTS
 FOR AHU'S. 210.70/ 210.63
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
 PLEASE SEE ATTACHED COPY OF FS 553.80(2)
 (B). THIS NOTICE IS GIVEN TO THE DESIGN
 PROFESSIONAL FOR PLANS FOR NEXT REVIEW.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-03-03 Cont ID  
Sent By pkrauss Date 2004-04-12 Time 11:08 Rev Time 1.50
Received By dpalmer Date 2004-03-02 Time 14:37 Sent To B
Notes
2004-03-03 00:00:00************* UNSAT *************
  
 1)NOTE : PLANS NOW HAVE TITLE BLOCK
 REMOVED. HOWEVER, PLANS ARE STILL REQUI-
 -RED TO BE SIGNED BY THE PERSON EAL
 RESPONSIBLE FOR THE PLANS. 104.2.1 FBC
 IF ITS AN ARCH/ENGINEER, THEN SIGNED,
 DATED AND SEALED ALONG WITH THE TITLE
 BLOCK.
 FS 471/481, 61G15-23.002, 61G1-16.004
  
 2)NOTE: PLEASE SEE PLANS NOW HAVE
 PANEL SCHEDULE AS REQUESTED ON FIRST
 REVIEW, HOWEVER, PLEASE SEE THE FOLLOW-
 -ING COMMENTS. ALSO, SOME COMMENTS FROM
 FIRST REVIEW ARE NOT CLEAR.
  
 3)NOTE: PLEASE SEE PLANS, ONLY SHOWS A
 METER ON THE OUTSIDE OF HOUSE. RISER
 SEEMS TO INDICATE TWO MCB PANELS OUTSIDE
 ?? AND SHOWS TWO 2" CONDUITS FROM TOP TO
 INSIDE PANELS?? PLEASE CORRELATE PLANS.
 ONLY TWO PANEL SCHEDULES ARE SUBMITTED.
  
 4)NOTE: PLEASE ALSO SEE PANELS SCHEDULES
 SUBMITTED, THEY ARE NOW SHOWN AS 400A
 MCB PANELS, WHICH WOULD MAKE THE SERVICE
 800A'S?? RISER SHOWS AS 200A EACH??
 PLEASE CORRELATE AND INDICATE AMPERAGE
 OF METERCAN.
  
 5)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU'S/HEAT. PLEASE SEE PANEL "B",
 SHOWS 30A OCP FOR 10KW HEAT.?
 PLEASE CORRELATE PANEL SCHEDULES AND
 LOAD CALCULATIONS.
  
 6)NOTE: PLEASE SEE SM APPL LOADS SHOWN
 ON LOAD CALCULATIONS. ONLY SHOWS TWO,YET
 PANEL SCHEDULES INDICATE 4. PLEASE SEE
 220.16, 1500VA FOR EACH SM APPL.
  
 7)NOTE: PLANS INDICATE A GAS POOL HEATER
 AND LOAD CALCAULTIONS SHOWS ELECTRICAL
 POOL HEATER?? PLEASE ALSO SEE PANEL
 SCHEDULES DO NOT INDICATE POOL HEATER??
  
 8)NOTE: PLEASE CLARIFY TWO WHIRLPOOL
 TUBS. FLOOR PLANS ONLY SHOW ONE.
 PLEASE CORRELATE.
  
 9)NOTE: PANEL SCHEDULES INDICATE 45 CIR
 PANELS?? ALSO INDICATE ALL CIRCUITS ON
 RIGHT HAND SIDE AFTER (30) BEING THE
 SAME CIRCUIT #'S ON EACH SIDE???
  
 10)NOTE: PLEASE SEE WHIRLPOOL TUB ON
 PLANS, DO NOT INDICATE A GFI RECEPT.??
  
 PLEASE CORRELATE PLANS AND ADDRESS THE
 ABOVE COMMENTS. PLEASE SUBMIT FOR REVIEW
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2004-02-27 Cont ID  
Sent By pkrauss Date 2004-03-01 Time 16:27 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2004-02-27 00:00:00PLANS GIVEN TO DEAN RUNNELS.
 PLANS CAME BACK IN W/OUT RESUB SHEET,
 NO NOTES IN COMPUTER ETC.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-01-21 Cont ID  
Sent By csiegber Date 2004-02-25 Time 16:44 Rev Time 1.00
Received By dpalmer Date 2004-01-21 Time 15:00 Sent To P
Notes
2004-01-21 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLANS WERE SUBMITTED FOR PLAN
 REVIEW ON FIRST REVIEW AND CONTAINED A
 TITLE BLOCK FOR AN ENGINEER. PLANS HAVE
 SINCE COME BACK AND DO NOT CONATIN ANY
 INFORMATION FOR PLAN/DESIGN. AS REQ'D
 UNDER FBC 104.2.1
 PLANS ARE NOT REQ'D TO BE SIGNED AND
 SEALED UNLESS CONTAINING A TITLE BLOCK
 AND WERE DONE BY AN ARCH/ENG.
 PLANS STILL MUST BE NAMED AND SIGNED
 BY PERSON RESPONSIBLE FOR PLAN.
  
 2)NOTE: PLEASE SEE SERVICE, SHOWN AS
 400A SERVICE. SHOWS 42CIR MCB PANELS
 FEEDING SOME OTHER PANELS. PLANS ONLY
 SHOW TWO PANELS IN GARAGE AND NO MCB
 PANELS OUTSIDE WITH METER, AS RISER SHOW
 -S. PLEASE SEE FIRST SET OF NOTES
 ASKING FOR PANEL SCHEDULES.
  
 3)NOTE: PLEASE SEE 210.52D,210.11C3 FOR
 MIN REQ'D FOR BATH RECEPTS. SEE RECEPTS
 MISSING FROM BATH(S). PLEASE LIST AS REQ
 'D.
  
 4)NOTE: PLEASE SEE MISSING LT FOR BATH
 DOWNSTAIRS NEXT TO MEDIA/BEDRM.
 210.70
  
 5)NOTE: PLEASE SEE PLANS, PLEASE CLARIFY
 LOCATION OF AHU`S AND DISC'S. 440.11
  
 6)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250.66
 310.15B6 REQ'S MIN 400MC TOTAL FOR
 SEC'S, 250.66 SIZES GEC FOR 400MCM/
 WOULD BE 1/0.
  
 7)NOTE: PLEASE SEE GFI NOTE ABOVE RISER,
 SHOWS GFI W/IN 15' OF POOL. PLEASE SEE
 680.22A5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-11-07 Cont ID  
Sent By csiegber Date 2004-01-13 Time 16:11 Rev Time 0.75
Received By dpalmer Date 2003-11-07 Time 09:35 Sent To M
Notes
2003-11-07 00:00:00*************** UNSAT ****************
  
 PLEASE SEE THAT PLANS ARE ONLY IN FOR
 PLAN REVIEW AND NOT SUBMITTED FOR
 PERMIT AT THIS TIME.
  
 1)NOTE: PLANS WILL BE REQ'D TO BE SIGNED
 DATED AND SEALED BY THE ARCH/ENGINEER
 OF RECORD PER FS 471.025,481.221
 PLEASE NOTE: FBPE'S HAS GIVEN TO THIS
 OFFICE INFORMATION THAT REQUIRES A
 SIGNATURE THAT CONTAINS A MIN IF FIRST
 AND LAST NAME.
  
 2)NOTE: PLEASE SEE PLANS, SHOWS BOTH
 PANEL IN GARAGE? PLEASE CLARIFY WHERE
 METER LOCATION IS. PLEASE SEE LOCAL
 AMENDMENTS, 210.70 NO MORE THAT 8' OF
 UNPROTECTED CONDUCTOS INSIDE HOUSE.
  
 3)NOTE: PLEASE SUBMIT PANEL SCHEDULE(S)
 WITH CIRCUITS, AWG AND OCP REQ'D. 215.5
 PLEASE LIST THE REQUIRED ARC FAULT
 PROTECTTION PER NEC 2002 210.12
 PLEASE LIST BATH(S) AS PER 210.52D AND
 210.11C3 AS 20A AND #12. ETC ETC
  
 4)NOTE: PLEASE SEE PLANS SHOW 4 A/C COND
 UNITS AND PLEASE SHOW AHU'S AND DISC PER
 440.11
  
 5)NOTE: PLEASE SEE 210.52E FOR MIN OF
 FRONT AND REAR GFI RECEPTS.
  
 6)NOTE: PLEASE SEE 210.52 FOR RECEPTS
 REQUIRED FOR WALL SPACE, INCLUDING
 RAIL AREAS. THERE IS MANY RECEPTS MISS-
 ING UPSTAIRS.
  
 7)NOTE: PLEASE SEE NFPA-72 8-1.4.2,
 SD'S ARE NOT PERMITTED IN KITCHENS AND
 INFACT MUST BE A MIN OF 3' FROM KITCHENS
 AND BATHS.
 PLEASE ALSO SEE THAT A SD IS REQ'D AT
 THE BASE OF STAIRS LEADING TO THE FLOOR
 ABOVE IN THE IMMEDIATE VICINITY OF STAIR
 -S.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-06-03 Cont ID  
Sent By csiegber Date 2004-06-03 Time 11:01 Rev Time 0.00
Received By csiegber Date 2004-06-03 Time 11:01 Sent To E
Notes
2004-06-03 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-05-24 Cont ID  
Sent By mmclean Date 2004-06-01 Time 16:23 Rev Time 0.00
Received By alange Date 2004-05-24 Time 11:18 Sent To E
Notes
2004-05-24 00:00:00TP DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-04-02 Cont ID  
Sent By csiegber Date 2004-04-02 Time 11:51 Rev Time 0.00
Received By csiegber Date 2004-04-02 Time 11:51 Sent To M
Notes
2004-04-02 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-03-01 Cont ID  
Sent By csiegber Date 2004-03-01 Time 10:06 Rev Time 0.00
Received By csiegber Date 2004-03-01 Time 10:06 Sent To P
Notes
2004-03-01 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 16:44 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 16:44 Sent To E
Notes
2004-02-25 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-25 Cont ID  
Sent By mmclean Date 2004-02-25 Time 16:42 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 15:30 Sent To Z
Notes
2004-02-25 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 15:23 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 15:23 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-13 Cont ID  
Sent By mmclean Date 2004-01-29 Time 10:16 Rev Time 0.00
Received By csiegber Date 2004-01-13 Time 16:05 Sent To E
Notes
2004-01-13 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-12 Cont ID  
Sent By mmclean Date 2003-11-05 Time 16:21 Rev Time 0.00
Received By csiegber Date 2003-11-03 Time 16:14 Sent To  
Notes
2003-11-06 00:00:00TO SFD RACK/E
2003-11-03 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-04-12 Cont ID  
Sent By pkrauss Date 2004-04-12 Time 11:07 Rev Time 0.20
Received By pkrauss Date 2004-04-12 Time 11:06 Sent To E
Notes
2004-04-12 00:00:00PLANS APPROVED 1-23-04
 TITLE BLOCK NEEDS TO BE REMOVED

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2004-03-01 Cont ID  
Sent By csiegber Date 2004-04-02 Time 11:51 Rev Time 0.35
Received By pkrauss Date 2004-03-01 Time 15:53 Sent To E
Notes
2004-03-01 00:00:00DENIED:
 1.PER COMMENTS DATED 1-23-04, PLAN
 NOT SIGNED, SEALED OR DATED BY ENGINEER
 OR ARCHITECT.TITLE BLOCK ON PLAN SHEET
 M-1, "DESIGN TEAM OF THE PALM BEACHES",
 PER FS 471.025 & 481.221 1 (B) & 2.
  
 2.PER COMMENTS DATED 1-23-04, PROVIDE
 ADDITIONAL COPY OF ENERGY & MANUAL J
 CALCULATIONS.NO ENERGY CALCULATION
 WERE PROVIDED WITH THE RE-SUBMITTAL.
 PROVIDE TWO COPIES OF ENERGY & MANUAL J
 CALCUALTIONS PER 2001 FBC(M) 101.4.5.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-01-23 Cont ID  
Sent By kstevens Date 2004-03-01 Time 14:57 Rev Time 0.55
Received By pkrauss Date 2004-01-23 Time 12:15 Sent To B
Notes
2004-01-23 00:00:00DENIED:
 1.SEE COMMENT #1 BY DEWEY PALMER,
 ELECTRICAL PLAN REVIEW.
  
 2.ONE COPY OF THE MANUAL J
 CALCULATIONS SUBMITTED FOR SYSTEM 1 &
 3, NO MANUAL J CALCS SUBMITTED FOR
 SYSTEM 2.TWO COPIES OF EACH REQUIRED.
  
 PROVISO:
 1.ATTIC ACCESS FOR A/C 1 & 2 SHALL
 COMPLY WITH 2001 FBC CHAPTER 13 SUB
 SECTION 610.1.ABC.3.5.2.
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-12-03 Cont ID  
Sent By kstevens Date 2004-01-21 Time 18:30 Rev Time 1.00
Received By hmoser Date 2003-12-03 Time 16:45 Sent To P
Notes
2003-12-03 00:00:00PLAN DENIED
 1) REFER TO SECTION 307.2.3 AUXILIARY
 DRAIN PAN.AUXILIARY DRAIN PANS SHALL BE
 INSTALLED UNDER ALL COILS ON WITCH
 CONDENSATION WILL OCCUR.
 2) RETURN AIR REQUIREMENTS TO COMPLY
 WITH THE FLORIDA BUILDING CODE (M) 2003
 CHANGES.CHANGES WENT INTO EFFECT JULY 1
 2003
 3) MECHANICAL PLANS DO NOT MATCH FLOOR
 PLAN
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 5 Status P Date 2004-05-29 Cont ID  
Sent By jleech Date 2004-05-29 Time 12:22 Rev Time 0.33
Received By jleech Date 2004-05-29 Time 12:22 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-04-17 Cont ID  
Sent By dpalmer Date 2004-05-26 Time 08:34 Rev Time 0.25
Received By kstevens Date 2004-04-17 Time 05:46 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-03-01 Cont ID  
Sent By dpalmer Date 2004-04-16 Time 19:08 Rev Time 1.25
Received By kstevens Date 2004-03-01 Time 14:57 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-01-21 Cont ID  
Sent By csiegber Date 2004-03-01 Time 10:06 Rev Time 1.20
Received By kstevens Date 2004-01-21 Time 18:24 Sent To M
Notes
2004-01-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN, NOR DOES IT MEET
 CODE REQUIREMENTS. (SEE EXAMPLE OF RISER
 DIAGRAM THAT MEETS CODE AND REFLECTS THE
 FLOOR PLAN).
  
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-12-03 Cont ID  
Sent By dpalmer Date 2004-01-21 Time 15:00 Rev Time 0.75
Received By jleech Date 2003-12-03 Time 17:35 Sent To B
Notes
2003-12-03 00:00:00DENIED;
 1.PLANS ARE NOT SIGNED OR SEALED.
 2.PLUMBING RISER DIAGRAM DOES NOT MATCH
 FLOOR PLAN.
 A.MASTER BATH AND LAUNDRY ROOM ARE
 ON THE 1ST FLOOR ON FLOOR PLAN A-3
 RISER DIAGRAM SHOWS 2ND FLOOR.
 B.LAUNDRY TUB CANNOT BE ON SAME
 STACK AS W/M BECAUSE FIXTURES ARE
 ON DIFFERENT SIDES OF ROOM.
 C.BUTLER PANTRY SINK NOT ON RISER
 DIAGRAM.
 D.HIS BATHROOM HAS SHOWER NOT TUB.
 E.RISER DIAGRAM SHOULD BE AN IMAGE
 OF THE FLOOR PLAN, FIXTURES ARE
 NOT IN PROPER ORDER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2004-06-01 Cont ID  
Sent By mmclean Date 2004-06-01 Time 16:23 Rev Time 0.00
Received By mmclean Date 2004-06-01 Time 16:23 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2004-02-25 Cont ID  
Sent By rmcdouga Date 2004-06-01 Time 14:21 Rev Time 0.00
Received By mmclean Date 2004-02-25 Time 16:42 Sent To I
Notes
2004-02-25 00:00:00DENIED, NEED TO HAVE ELEVATION TO SCALE
 CALLED CONTR

Review Stop Z ZONING
Rev No 2 Status F Date 2004-01-29 Cont ID  
Sent By csiegber Date 2004-02-25 Time 15:30 Rev Time 0.00
Received By mmclean Date 2004-01-29 Time 10:16 Sent To I
Notes
2004-01-29 00:00:00DENIED, NEED TO PROVIDE HAVE ELEVATIONS
 TO SCALE CALLED CONTR MM

Review Stop Z ZONING
Rev No 1 Status F Date 2003-11-05 Cont ID  
Sent By rmcdouga Date 2004-01-26 Time 15:52 Rev Time 0.00
Received By mmclean Date 2003-11-05 Time 16:19 Sent To I
Notes
2003-11-05 00:00:0011/5/03 DENIED, NEED 2 COPY OF SURVEY
 CALLED CONTR LEFT MSG ON VOICE MAIL MM


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved