Plan Review Stops For Permit 03110048 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2004-06-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2004-06-08 |
Time |
08:42 |
Rev Time |
2.00 |
Received By |
rmcdouga |
Date |
2004-06-08 |
Time |
08:42 |
Sent To |
|
|
Notes |
2004-06-08 00:00:00 | BUILDING PROVISO | | | | 1) STRUCTURE IS LOCATED IN AN "A5" FLOOD | | ZONE AN ELEVATION CERTIFICATE WILL BE | | REQUIRED. | | | | 2) THE STATE PRODUCT APPROVAL FOR THE | | WOOD FRENCH DOOR IS PENDING. AN APPROVED | | STATUS FROM THE STATE OR LOCAL PRODUCT | | APPROVAL WILL BE REQUIRED BEFORE A C.O. | | IS ISSUED. | | | | 3) SEPARATE PERMITS WILL BE REQUIRED FOR | | SUBCONTRACTORS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2004-06-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-06-07 |
Time |
07:56 |
Rev Time |
3.00 |
Received By |
rmcdouga |
Date |
2004-06-01 |
Time |
13:38 |
Sent To |
Z |
|
Notes |
2004-06-01 00:00:00 | BUILDING DENIED | | | | 1)SUBMIT STATE OR LOCAL PRODUCT APPROVAL | | FOR THE FOLLOWING: | | - THREE PANEL SLIDING GLASS DOOR | | - SOLID CORE OUTSWING DOOR AT GARAGE | | - STRUCTURAL WINDOW MULLIONS (IMPACT) | | | | 2) THE STATE PRODUCT APPROVAL FOR THE | | WOOD FRENCH DOORS IS LISTED AS PENDING. | | AN APPROVED STATUS IS REQUIRED BEFORE A | | C.O. WILL BE ISSUED OR LOCAL PRODUCT | | APPROVAL CAN BE APPLIED FOR. | | | | 3) THE STRUCTURE IS LOCATED IN AN "A5" | | FLOOD ZONE, AN ELEVATION CERTIFICATE | | WILL BE REQUIRED. THE LOWEST FLOOR | | ELEVATION IS REQUIRED TO BE 6" ABOVE | | BASE FLOOD ELEVATION PER CITY OF WPB | | MUNICIPLE CODE. | | | | 4) ENGINEERED HAMBRO FLOOR SYSTEM | | DRAWINGS ARE TO BE REVIEWED AND APPROVED | | BY THE DESIGNER OF RECORD. HAVE THEM | | STAMPED AND SIGNED BY HIM AS REVIEWED | | AND ACCEPTED. | | | | 5) SUBMIT THE INSTALLATION MANUAL FOR | | THE HAMBRO FLOOR SYSTEM. | | | | 6) THE ORIGIONAL PERMIT APPLICATION IS | | NOT WITH THIS RESUBMITTAL. ADDITIONAL | | FEES WILL BE REQUIRED TO ADD SUBS TO | | THIS PERMIT OR SEPARATE PERMITS WILL BE | | REQUIRED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2004-04-20 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2004-05-29 |
Time |
12:22 |
Rev Time |
2.00 |
Received By |
rmcdouga |
Date |
2004-04-19 |
Time |
16:21 |
Sent To |
|
|
Notes |
2004-04-19 00:00:00 | DENIED | | | | 1)PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | 2) SUBMIT STATE OR LOCAL PRODUCT | | APPROVAL FOR THE FOLLOWING ITEMS: | | - GARAGE DOORS | | - ARCHED TOP (DESIGNER) FIXED WINDOWS | | - MULTIEDGED FIXED GLASS WINDOW | | - THREE PANEL SLIDING GLASS DOOR | | - SOLID CORE OUTSWING DOOR AT GARAGE | | - CASEMENT WINDOW | | - STRUCTURAL MULLIONS | | | | 3) IN ADDITION TO THE MIAMI-DADE NOAS | | SUBMITTED FOR THE FRENCH DOORS AND THE | | SLIDING GLASS DOORS (TWO PANEL), STATE | | OR LOCAL PRODUCT APPROVAL IS REQUIRED. | | SUBMIT COVERSHEETS FROM STATE DCA | | WEBSITE WITH FLORIDA PRODUCT APPROVAL | | NUMBER OR LOCAL PRODUCT APPROVAL | | APPLICATION FORM. | | | | 4) THE STRUCTURE IS LOCATED IN AN "A5" | | FLOOD ZONE, AN ELEVATION CERTIFICATE | | WILL BE REQUIRED. THE LOWEST FLOOR | | ELEVATION IS REQUIRED TO BE 6" ABOVE | | BASE FLOOD ELEVATION PER CITY OF WPB | | MUNICIPAL CODE. | | | | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS | | AND UL OR OTHER LISTING INFORMATION FOR | | THE GAS BBQ SHOWN ON THE PLANS. | | | | 6) SEVERAL NOTES ON SHEET S3 SAY SEE | | SECTION A. HOWEVER, NO SECTION A IS | | GIVEN. PLEASE CLARIFY. | | | | 7) SUBMIT SIGNED AND SEALED ENGINEERED | | SHOP DRAWINGS AND LAYOUT FOR THE HAMBRO | | FLOOR SYSTEM THAT HAS BEEN REVIEWED AND | | APPROVED BY THE DESIGNER OF RECORD. | | | | 8) SUBMIT THE INSTALLATION MANUAL FOR | | THE HAMBRO FLOOR SYSTEM. | | | | 9) SPECIFY THE WELD TYPE AND THICKNESS | | FOR THE CONNECTION OF THE HAMBRO FLOOR | | JOISTS TO THE STEEL IMBEDS. | | | | 10) SPECIFY ALL PERMANENT BRACING AND | | ATTACHMENTS FOR THE HAMBRO SYSTEM. | | | | 11) CORRECT THE TYPO IN THE STAIR NOTES | | ON SHEET D2 WHERE DBC IS LISTED RATHER | | THAN FBC. | | | | 12) PROVIDE (2) PRODUCT APPROVALS, KEY | | PLANS AND INSTALLATION SCHEDULES | | INDICATING THE MOUNT TYPE AND SPECIFIC | | ANCHORS THAT WILL BE USED FOR THE STORM | | PANELS, UNLESS ALL OF THE EXTERIOR | | GLAZING IS IMPACT RATED. | | | | 13) ADDITIONAL FEES WILL BE CHARGED TO | | ADD SUBS TO PERMIT APPLICATION. ASK | | PERMIT CLERK WHEN RESUBMITTING TO ADD | | SUBCONTRACTORS TO PERMIT. | | | | IF YOU HAVE QUESTIONS PLEASE CALL: | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2004-03-11 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-04-17 |
Time |
05:46 |
Rev Time |
3.00 |
Received By |
rmcdouga |
Date |
2004-03-11 |
Time |
12:48 |
Sent To |
|
|
Notes |
2004-03-11 00:00:00 | DENIED | | | | 1) SUBMIT A SIGNED AND SEALED COPY OF A | | SUB-SURFACE SOIL TEST REPORT AS REQUIRED | | BY FBC 1804.2.2. THE REPORT SHALL | | CONTAIN THE CONCLUSIONS REACHED AS A | | RESULT OF THE TESTING AND SPECIFY THE | | SAFE BEARING CAPACITY OF THE SOIL. | | | | 2)PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE SAMPLE | | OF COVERSHEET FROM THE STATE WEBSITE FOR | | PGT SINGLE HUNG WINDOWS,ATTACHED. | | SUBMIT PRODUCT APPROVALS FOR EACH TYPE | | OF DOOR, WINDOW, ETC. THAT WILL BE | | INSTALLED IN THIS PROJECT. | | | | 3) SUBMIT PRODUCT APPROVALS AS SPECIFIED | | ABOVE FOR THE FOLLOWING: | | - GARAGE DOORS | | - ARCHED WINDOWS | | - MULTIEDGED FIXED GLASS WINDOW | | - THREE PANEL SLIDING GLASS DOOR | | - CUSTOM DOORS AT ENTRY | | - SOLID CORE OUTSWING DOOR AT GARAGE | | - CASEMENT WINDOW | | - STRUCTURAL MULLIONS | | | | 4) THE STRUCTURE IS LOCATED IN AN "A5" | | FLOOD ZONE AN ELEVATION CERTIFICATE WILL | | BE REQUIRED. | | | | 5) SPECIFY THE SIZES OF THE TWO ATTIC | | ACCESS OPENINGS AT THE SECOND FLOOR. SEE | | FBC 2309.6 (MIN.20"X 36"). | | | | 6) ENERGY CALCS. WERE NOT RESUBMITTED. | | SEE COMMENTS FROM SECOND REVIEW. | | | | 7) SUBMIT MANUFACTURER'S SPECS. AND UL | | LISTING INFORMATION FOR THE GAS BBQ. | | | | 8) SUBMIT SIGNED AND SEALED ENGINEERED | | SHOP DRAWINGS AND LAYOUT THAT HAS BEEN | | REVIEWED AND APPROVED BY THE DESIGNER OF | | RECORD. | | | | 9) SPECIFY THE WELD TYPE FOR THE | | CONNECTION OF THE HAMBRO JOISTS TO THE | | STEEL EMBEDS. | | | | 10)THE HAMBRO JOIST SPACING IS SPECIFIED | | AS 4'O.C. AND THE BEARING PLATES(EMBEDS) | | ARE SPACED 24"O.C. PLEASE CLARIFY. SEE | | SHEET S3. | | | | 11) PROVIDE A DETAIL INDICATING THE | | ATTACHMENT OF THE CEILING TO THE HAMBRO | | FLOOR SYSTEM. INDICATE FURRING,FASTENERS | | SPACINGS,ETC. | | | | 12) SPECIFY THE BRIDGING MATERIAL, | | SPACING, ATTCHMENT TO JOIST, ETC.FOR THE | | HAMBRO JOISTS ON THE PLANS. | | | | 13) CORRECT THE TYPO IN THE STAIR NOTES | | ON D2 WHERE DBC SHOULD BE FBC. | | | | 14) REVISE TRUSS CONNECTOR MARKS A4 AND | | A5 ON THE FIRST AND SECOND FLOOR ROOF | | PLANS ON S4 AND S5. THESE ID MARKS ARE | | NO LONGER LISTED IN THE REVISED TRUSS | | ANCHOR SCHEDULE. | | | | 15) THE PRODUCT APPROVAL SUBMITTED FOR | | THE FRENCH DOORS IS FOR NON-IMPACT RATED | | DOORS. STORM PANELS WILL BE REQUIRED. | | | | 16)PROVIDE (2) PRODUCT APPROVALS, KEY | | PLANS AND INSTALLATION SCHEDULES | | INDICATING THE SPECIFIC TYPES OF ANCHORS | | TO BE USED FOR STORM PANELS. UNLESS ALL | | EXTERIOR GLAZING IS IMPACT RATED. | | | | 17) SEPARATE PERMITS WILL BE REQUIRED | | FOR OTHER TRADES THAT WERE NOT SIGNED ON | | PERMIT APPLICATION. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2004-01-26 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-03-03 |
Time |
06:23 |
Rev Time |
3.00 |
Received By |
rmcdouga |
Date |
2004-01-26 |
Time |
14:31 |
Sent To |
Z |
|
Notes |
2004-01-26 00:00:00 | DENIED | | | | 1) BOTH SETS OF PLANS ARE REQUIRED TO BE | | STAMPED BY PB COUNTY FOR IMPACT FEES. | | | | 2) SUBMIT A SIGNED AND SEALED COPY OF A | | SUB-SURFACE SOIL TEST REPORT AS REQUIRED | | BY FBC 1804.2.2. | | | | 3)PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | SUBMIT FOR ALL WINDOWS, DOORS, GARAGE | | DOORS, STORM PANELS, TRUSS CONNECTORS, | | ETC. THAT IS SPECIFIED ON THE PLANS. | | | | 4) THE STRUCTURE IS LOCATED IN AN "A5" | | FLOOD ZONE AN ELEVATION CERTIFICATE WILL | | BE REQUIRED BEFORE THE C.O. IS ISSUED. | | | | 5) SPECIFY THE SIZES OF THE TWO ATTIC | | ACCESS OPENINGS ON THE SECOND FLOOR. | | | | 6) THE CONDITIONED FLOOR AREA LISTED ON | | THE ENERGY CALC. FORM DOES NOT AGREE | | WITH THE A/C AREA LISTED ON THE PLANS. | | THE FORM IS REQUIRED TO BE SIGNED AND | | DATED BY THE OWNER/AGENT. | | | | 7) SUBMIT MANUFACTURER'S SPECIFICATIONS | | AND LISTING INFORMATION FOR THE BBQ ON | | THE LANAI. | | | | 8) INDICATE THE BEAM ELEVATIONS (TOB) | | ON SHEETS S1 AND S2. | | | | 9) SPECIFY ON THE PLANS THAT THE WIRE | | MESH WILL BE SUPPORTED ON APPROVED | | SUPPORTS AT NO MORE THAN 3'OC PER FBC | | 1909.3. | | | | 10) SUBMIT SIGNED AND SEALED ENGINEERING | | FOR THE HAMBRO FLOOR SYSTEM. | | | | 11) PLEASE UPDATE THE ANCHOR SCHEDULES | | ON S4 AND S5. FAC RULE 9B-72 REQUIRES | | TRUSS CONNECTORS TO HAVE STATE PRODUCT | | APPROVAL. THERE IS NO USP RTPGA | | CONNECTOR LISTED. SEMCO AND HUGHES ARE | | NO LONGER IN BUSINESS AND ARE NOT LISTED | | WITH THE STATE, PLEASE REMOVE REFRENCES | | TO THEM. | | | | 12) 1609.4.3 LOAD REDUCTION. | | WHEN STRUCTURAL EFFECTS DUE TO TWO OR | | MORE LOADS IN COMBINATION WITH DEAD LOAD | | ARE INVESTIGATED IN LOAD COMBINATIONS OF | | 1609.4.1 OR 1609.4.2, THE COMBINED | | EFFECTS DUE TO THE TWO OR LOADS MULTI- | | PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD | | LOADS SHALL NOT BE LESS THAN THE EFFECTS | | FROM THE LOAD COMBINATION OF THE DEAD | | LOAD PLUS THE LOAD PRODUCING THE LARGEST | | EFFECTS.INCREASE IN ALLOWABLE STRESS SPE | | CIFIED IN THE MATERIALS SECTIONS OF THIS | | CODE OR A REFRENCED STANDARD SHALL NOT | | BE USED WITH THESE LOAD COMBINATIONS | | EXCEPT THAT A DURATION OF LOAD INCREASE | | SHALL BE PERMITTED IN ACCORDANCE WITH | | CHAPTER 23. | | REVISE TRUSS ANCHOR SCHEDULE WITH VALUES | | THAT DO NOT INCLUDE THIS STRESS INCREASE | | SEE LATEST USP CATALOG. | | | | 13) SPECIFY FIREBLOCKING ON THE WALL | | SECTIONS ON D1 AT THE INTERSECTIONS OF | | THE CONCEALED VERTICAL AND HORIZONTAL | | SPACES. SEE FBC 2305.1. | | | | 14) CLARIFY ON THE STAIR DETAILS ON D2 | | THAT THE HANDRAILS FOR THE CIRCULAR | | STAIRS ARE BETWEEN 34" AND 38" ABOVE THE | | LEADING EDGE OF THE TREADS AS REQUIRED | | BY FBC 1007.5. | | | | 15)PROVIDE (2) PRODUCT APPROVALS, KEY | | PLANS AND INSTALLATION SCHEDULES | | INDICATING THE SPECIFIC TYPES OF ANCHORS | | TO BE USED FOR STORM PANELS. | | A SEPARATE PERMIT AND FEES WILL BE | | REQUIRED IF ALL INFORMATION IS NOT | | SUBMITTED BEFORE PERMIT IS ISSUED. | | | | 16) SEPARATE PERMITS WILL BE REQUIRED | | FOR OTHER TRADES AS THEY WERE NOT SIGNED | | ONTO PERMIT APPLICATION. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2003-12-12 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-01-23 |
Time |
13:52 |
Rev Time |
4.00 |
Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2003-12-11 00:00:00 | DENIED | | | | 1) IMPACT FEES MUST BE PAID TO PALM | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | COPY OF RECEIPT SUBMITTED TO CITY OF | | WEST PALM BEACH BUILDING DEPARTMENT, | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | 2) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 3) PLANS ARE REQUIRED TO BE SIGNED, | | SEALED AND DATED BY THE DESIGNER OF | | RECORD. | | | | 4) INDICATE IN THE DESIGN INFORMATION ON | | A-3 THAT STRUCTURE IS DESIGNED AS | | ENCLOSED. | | | | 5) SPECIFY THE REQUIRED BEARING CAPACITY | | OF THE SOIL ON THE PLANS. | | | | 6) SUBMIT A SUB-SURFACE SOIL BEARING | | TEST REPORT AS REQUIRED BY FBC 1804.2.2. | | | | 7) SPECIFY THE FINISH FLOOR ELEVATION ON | | THE PLANS. THE STRUCTURE IS LOCATED IN | | AN A5 FLOOD ZONE. A MINIMUM ELEVATION OF | | 7'- 6" IS REQUIRED. AN ELEVATION | | CERTIFICATE WILL BE REQUIRED FOR C.O. | | | | 8)PRODUCT APPROVALS SUBMITTED FOR PERMIT | | APPLICATIONS AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. SUBMIT PRODUCT APPROVALS FOR | | WINDOWS, DOORS, ROOFING, ETC. | | | | 9) SUBMIT A SURVEY AND SITE PLAN FOR | | DETERMINING SETBACK REQUIREMENTS AND | | FBC TABLE 600. | | | | 10) THE WORD WIDTH IS MISSING FROM THE | | NET CLEAR OPENING FOR THE EGRESS WINDOWS | | ON A-3. | | | | 11) SPECIFY THE SIZES OF THE ATTIC | | ACCESSES ON A3 AND A4. | | | | 12) SPECIFY THE WINDOW TYPES ON THE | | PLANS (I.E. SINGLE HUNG, FIXED, CASEMENT | | ETC.). | | | | 13) THERE ARE ALOT OF ERRORS IN THE | | WINDOW LEGEND AND ON THE PLANS. THE | | SIZES & WINDOW TYPES, DO NOT CORRESPOND | | TO ELEVATIONS. PLEASE CORRECT. | | | | 14) DIMENSION FROM FRONT OF STRUCTURE TO | | FRONT OF COVERED ENTRY IS NOT GIVEN. | | PROVIDE EXTERIOR WALL DIMENSIONS ON THE | | FLOOR PLAN. | | | | 15) PROVIDE OVERALL DIMENSIONS FOR THE | | WALL SECTIONS ON S1 AND S2. | | | | 16) SUBMIT UL LISTING INFORMATION FOR | | THE BBQ GRILL ON LANAI. | | | | 17) PROVIDE AN EGRESS WINDOW AT THE | | STUDY OR SPECIFY ON THE PLAN THAT THIS | | ROOM WILL NOT BE USED FOR SLEEPING | | PURPOSES. | | | | 18) INDICATE ON THE PLANS THAT TEMPERED | | GLASS IS REQUIRED IN BATHROOM WINDOWS IF | | SILL HEIGHT IS LESS THAN 60" ABOVE | | STANDING AREA PER FBC 2405.2.1. (IMPACT | | RESISTANT GLASS IS ACCEPTABLE) | | | | 19) THE SECOND FLOOR BEDROOMS ARE | | REQUIRED TO COMPLY WITH FBC 1005.4 FOR | | EGRESS WINDOWS. (5.7 SQFT CLEAR OPENING | | AREA IS REQUIRED) | | | | 20) INDICATE THE TOP OF BEAM ELEVATIONS | | ON SHEETS S1 AND S2. | | | | 21) CORRECT FOOTING SIZE FOR FOOTING AT | | LIVING ROOM ON S1 THAT IS GIVEN AS 22"X | | 42". | | | | 22) SPECIFY THE SLAB THICKNESS, WIRE | | REINFORCEMENT SUPPORTED PER FBC 1909.3, | | VAPOR BARRIER AND TERMITE TREATED SOIL. | | | | 23) INDICATE THAT TIE BEAM IS FOR THE | | SECOND FLOOR IS 8"X 12" EXCEPT AT | | OPENINGS. | | | | 24) SUBMIT SIGNED AND SEALED ENGINEERING | | FOR THE HAMBRO FLOOR SYSTEM. | | | | 25) SUBMIT MORE COMPLETE DETAILS FOR THE | | WOOD FRAME TOWER. SPECIFY DIMENSIONS, | | FRAMING DETAILS, CONNECTORS, EXTERIOR | | FINISH, FIRE BLOCKING, ETC. | | | | 26) PLEASE REVISE THE TRUSS ANCHOR | | SCHEDULE S4 AND S5. THERE IS NO USP | | RTPGA836 CONNECTOR LISTED IN THE 2003 | | USP CATALOG OR ON THE STATE PRODUCT | | APPROVAL LISTING. USE VALUES THAT DO NOT | | INCLUDE A ONE THIRD INCREASE IN THE | | STEEL CALCULATIONS PER FBC 1609.4.3. | | REVIEW THE UPLIFT CAPACITY FOR THE A6 | | CONNECTOR IN THE SCHEDULE. DUE TO THE | | PROXIMITY OF THE THREE STRAPS, THE | | UPLIFT CAPACITIES ARE REDUCED BECAUSE | | OF OVERLAPPING CONE PULLOUTS OF THE | | CONCRETE BEAMS. REMOVE THE REFERENCE TO | | SEMCO AND HUGHES FROM THE SCHEDULES AS | | THEY NO LONGER EXIST. | | | | 27) PROVIDE AN ID TAG ON S4 FOR THE | | LEDGER THAT TIES IT TO THE DETAIL ON D2. | | THE UPLIFT FOR ONE OF THE GIRDERS IS | | 2100# WHICH EXCEEDS THE UPLIFT CAPACITY | | OF THE HUS28 HANGER. PLEASE CORRECT. | | | | 28) PUT THE NOTE THAT CLARIFIES THE | | DETAIL "O" AND "Q" ON SHEET S5 WHERE | | THESE CONNECTORS ARE SPECIFIED. | | | | 29) REVISE THE ROOFING NAIL TYPE THAT IS | | SPECIFIED ON D1. FOR A MEAN ROOF HEIGHT | | GREATER THAN 25' USE 8D RING-SHANK NAILS | | IN ZONE 3 AS REQUIRED BY THE CITY OF WPB | | AMENDMENTS TO FBC TABLE 2306.1. | | | | 30) PROVIDE INTERIOR WALL DETAILS. | | | | 31) SPECIFY FIRE BLOCKING ON THE WALL | | SECTIONS ON D1 AND THE TOWER DETAIL ON | | D2. | | | | 32) THE 2 STORY WALL SECTION ON D1 SHOWS | | PRECAST LINTELS AT OPENINGS AND THE | | REST OF THE PLANS INDICATE POURED BEAMS. | | PLEASE REVISE. | | | | 33) CLARIFY THE (2) 16" DIMENSIONS THAT | | ARE SHOWN AT THE FOOTER ON THE 2 STORY | | DETAIL ON D1. | | | | 34) PROVIDE ADDITIONAL DETAILS FOR THE | | CIRCULAR STAIRS. SPECIFY THE WIDTH OF | | THE STAIRS, HANDRAILS 34"- 38" ABOVE THE | | LEADING EDGE OF TREADS PER FBC 1007.5, | | GUARDRAILS WITH INTERMEDIATE RAILS PER | | FBC 1015 AND SHOW COMPLIANCE WITH FBC | | 1007.8.3 FOR MINIMUM TREAD DEPTHS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
P |
Date |
2004-06-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-06-07 |
Time |
07:56 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2004-06-07 |
Time |
07:56 |
Sent To |
B |
|
Notes |
2004-06-07 00:00:00 | REDLINED 400A MAIN ON OUTSIDE OF HOUSE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
F |
Date |
2004-05-26 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-06-03 |
Time |
11:01 |
Rev Time |
0.75 |
Received By |
dpalmer |
Date |
2004-05-26 |
Time |
07:54 |
Sent To |
P |
|
Notes |
2004-05-26 00:00:00 | ************UNSAT ************** | | | | 1)NOTE: PLEASE SEE NEW SHEET E-1 IS NOW | | SUBMITTED W/OUT PRINTED NAME AND SIGNAT- | | -URE OF THE PERSON RESPONSIBLE FOR | | PLANS. FBC 104.2.1 | | IF PLANS ARE DONE BY AN ARCH OR ENGINEER | | THEN A TITLE BLOCK WILL BE REQ'D WITH | | ALL INFORMATION AS SET FORTH IN | | FAC 61G1-16.004,61G15-23.002 | | SIGNED, DATED AND SEALED BY SAID ARCH/ | | ENGINEER. | | | | 2)NOTE: PLEASE SEE SHEET E-2, NOTE 5 | | FROM FIRST REVIEW NOT DONE. THIS CAN | | BE REDLINED. | | | | NOTE# 1 NEEDS TO BE ADDRESSED BEFORE | | STAMPING OF ELECTRICAL PLANS. PLANS | | ROUTED TO OTHER TRADES FOR REVIEW. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
F |
Date |
2004-04-16 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2004-05-24 |
Time |
11:18 |
Rev Time |
1.00 |
Received By |
dpalmer |
Date |
2004-04-16 |
Time |
18:40 |
Sent To |
P |
|
Notes |
2004-04-16 00:00:00 | ************ UNSAT *************** | | | | PLEASE SEE COMMENTS BELOW AND ALL PREVI- | | -OUS COMMENTS. PLEASE CALL IF THERE ARE | | ANY QUESTIONS, OR IF A MEETING CAN BE | | SET UP TO GO OVER PLANS AND COMMENTS. | | PREVIOUS REVIEWS GAVE # FOR QUESTIONS. | | | | 1)NOTE: PLEASE SEE 424.3B FOR MIN OCP | | FOR AHU'S AND 10KW HEAT. A MIN OF 125% | | IS REQ'D. PLANS INDICATE 50A OCP FOR | | ALL THREE UNITS. | | | | 2)NOTE: PLEASE SEE SERVICE RISER, | | PLEASE INDICATE METERCAN SIZE/AMPERAGE. | | PLEASE SEE RISER NOW SHOWS WHAT APPEARS | | TO BE A MAIN DISC? LOAD CALCS MENTION | | A 400A SERVICE, BUT MAIN DOES NOT INDI- | | -CATE THIS. SERVICE ENT CONDUCTORS ARE | | SHOWN AS 2/0'S, WHICH ARE ONLY RATED FOR | | A 200A SERVICE. PLEASE SEE 310.15B6 FOR | | MIN SIZE FOR 400A SERVICE. | | | | 3)NOTE: PLEASE SEE RISER, WHAT APPEARS | | TO BE A RISER MAIN DOES NOT LIST OR | | INDICATE OCP/BRKRS TO SUB-FEED OF EACH | | 200A PANELS. IF THIS IS A 400A SERVICE, | | WHERE IS THE OCP FOR 2/0'S TO EACH PANEL | | AND PANELS RATED FOR 200A'S??? | | | | THIS IS ONLY A NOTE: PANELS ARE SHOWN AS | | MCB. PANELS SHOULD BE FED W/ OCP, MCB | | ARE NOT REQ'D BUT MAY BE INSTALLED. | | IF SHOWN ON PLANS THEN THEY WILL BE | | REQ'D TO BE INSTALLED. | | | | 4)NOTE: PLEASE SIZE GROUNDING ELECTRODE | | CONDUCTOR FOR 400A SERVICE. 250.66,310. | | 15B6. 1/0 MIN. | | | | 5)NOTE:PLEASE LABEL PANELS. PLEASE | | ALSO SEE RISER INDICATES 2/0'S FOR | | ONE PANEL BUT NOT THE OTHER. | | PLANS ONLY SHOW A METERCAN ON OUTSIDE OF | | HOUSE. | | | | NEW NOTE: | | 6)NOTE: PLEASE INDICATE REQ'D LT/RECEPTS | | FOR AHU'S. 210.70/ 210.63 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | | | PLEASE SEE ATTACHED COPY OF FS 553.80(2) | | (B). THIS NOTICE IS GIVEN TO THE DESIGN | | PROFESSIONAL FOR PLANS FOR NEXT REVIEW. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2004-03-03 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-04-12 |
Time |
11:08 |
Rev Time |
1.50 |
Received By |
dpalmer |
Date |
2004-03-02 |
Time |
14:37 |
Sent To |
B |
|
Notes |
2004-03-03 00:00:00 | ************* UNSAT ************* | | | | 1)NOTE : PLANS NOW HAVE TITLE BLOCK | | REMOVED. HOWEVER, PLANS ARE STILL REQUI- | | -RED TO BE SIGNED BY THE PERSON EAL | | RESPONSIBLE FOR THE PLANS. 104.2.1 FBC | | IF ITS AN ARCH/ENGINEER, THEN SIGNED, | | DATED AND SEALED ALONG WITH THE TITLE | | BLOCK. | | FS 471/481, 61G15-23.002, 61G1-16.004 | | | | 2)NOTE: PLEASE SEE PLANS NOW HAVE | | PANEL SCHEDULE AS REQUESTED ON FIRST | | REVIEW, HOWEVER, PLEASE SEE THE FOLLOW- | | -ING COMMENTS. ALSO, SOME COMMENTS FROM | | FIRST REVIEW ARE NOT CLEAR. | | | | 3)NOTE: PLEASE SEE PLANS, ONLY SHOWS A | | METER ON THE OUTSIDE OF HOUSE. RISER | | SEEMS TO INDICATE TWO MCB PANELS OUTSIDE | | ?? AND SHOWS TWO 2" CONDUITS FROM TOP TO | | INSIDE PANELS?? PLEASE CORRELATE PLANS. | | ONLY TWO PANEL SCHEDULES ARE SUBMITTED. | | | | 4)NOTE: PLEASE ALSO SEE PANELS SCHEDULES | | SUBMITTED, THEY ARE NOW SHOWN AS 400A | | MCB PANELS, WHICH WOULD MAKE THE SERVICE | | 800A'S?? RISER SHOWS AS 200A EACH?? | | PLEASE CORRELATE AND INDICATE AMPERAGE | | OF METERCAN. | | | | 5)NOTE: PLEASE SEE 424.3B FOR MIN OCP | | FOR AHU'S/HEAT. PLEASE SEE PANEL "B", | | SHOWS 30A OCP FOR 10KW HEAT.? | | PLEASE CORRELATE PANEL SCHEDULES AND | | LOAD CALCULATIONS. | | | | 6)NOTE: PLEASE SEE SM APPL LOADS SHOWN | | ON LOAD CALCULATIONS. ONLY SHOWS TWO,YET | | PANEL SCHEDULES INDICATE 4. PLEASE SEE | | 220.16, 1500VA FOR EACH SM APPL. | | | | 7)NOTE: PLANS INDICATE A GAS POOL HEATER | | AND LOAD CALCAULTIONS SHOWS ELECTRICAL | | POOL HEATER?? PLEASE ALSO SEE PANEL | | SCHEDULES DO NOT INDICATE POOL HEATER?? | | | | 8)NOTE: PLEASE CLARIFY TWO WHIRLPOOL | | TUBS. FLOOR PLANS ONLY SHOW ONE. | | PLEASE CORRELATE. | | | | 9)NOTE: PANEL SCHEDULES INDICATE 45 CIR | | PANELS?? ALSO INDICATE ALL CIRCUITS ON | | RIGHT HAND SIDE AFTER (30) BEING THE | | SAME CIRCUIT #'S ON EACH SIDE??? | | | | 10)NOTE: PLEASE SEE WHIRLPOOL TUB ON | | PLANS, DO NOT INDICATE A GFI RECEPT.?? | | | | PLEASE CORRELATE PLANS AND ADDRESS THE | | ABOVE COMMENTS. PLEASE SUBMIT FOR REVIEW | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
N |
Date |
2004-02-27 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-03-01 |
Time |
16:27 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2004-02-27 00:00:00 | PLANS GIVEN TO DEAN RUNNELS. | | PLANS CAME BACK IN W/OUT RESUB SHEET, | | NO NOTES IN COMPUTER ETC. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2004-01-21 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-02-25 |
Time |
16:44 |
Rev Time |
1.00 |
Received By |
dpalmer |
Date |
2004-01-21 |
Time |
15:00 |
Sent To |
P |
|
Notes |
2004-01-21 00:00:00 | **************** UNSAT **************** | | | | 1)NOTE: PLANS WERE SUBMITTED FOR PLAN | | REVIEW ON FIRST REVIEW AND CONTAINED A | | TITLE BLOCK FOR AN ENGINEER. PLANS HAVE | | SINCE COME BACK AND DO NOT CONATIN ANY | | INFORMATION FOR PLAN/DESIGN. AS REQ'D | | UNDER FBC 104.2.1 | | PLANS ARE NOT REQ'D TO BE SIGNED AND | | SEALED UNLESS CONTAINING A TITLE BLOCK | | AND WERE DONE BY AN ARCH/ENG. | | PLANS STILL MUST BE NAMED AND SIGNED | | BY PERSON RESPONSIBLE FOR PLAN. | | | | 2)NOTE: PLEASE SEE SERVICE, SHOWN AS | | 400A SERVICE. SHOWS 42CIR MCB PANELS | | FEEDING SOME OTHER PANELS. PLANS ONLY | | SHOW TWO PANELS IN GARAGE AND NO MCB | | PANELS OUTSIDE WITH METER, AS RISER SHOW | | -S. PLEASE SEE FIRST SET OF NOTES | | ASKING FOR PANEL SCHEDULES. | | | | 3)NOTE: PLEASE SEE 210.52D,210.11C3 FOR | | MIN REQ'D FOR BATH RECEPTS. SEE RECEPTS | | MISSING FROM BATH(S). PLEASE LIST AS REQ | | 'D. | | | | 4)NOTE: PLEASE SEE MISSING LT FOR BATH | | DOWNSTAIRS NEXT TO MEDIA/BEDRM. | | 210.70 | | | | 5)NOTE: PLEASE SEE PLANS, PLEASE CLARIFY | | LOCATION OF AHU`S AND DISC'S. 440.11 | | | | 6)NOTE: PLEASE SIZE GROUNDING ELECTRODE | | CONDUCTOR PER 250.66 | | 310.15B6 REQ'S MIN 400MC TOTAL FOR | | SEC'S, 250.66 SIZES GEC FOR 400MCM/ | | WOULD BE 1/0. | | | | 7)NOTE: PLEASE SEE GFI NOTE ABOVE RISER, | | SHOWS GFI W/IN 15' OF POOL. PLEASE SEE | | 680.22A5 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2003-11-07 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-01-13 |
Time |
16:11 |
Rev Time |
0.75 |
Received By |
dpalmer |
Date |
2003-11-07 |
Time |
09:35 |
Sent To |
M |
|
Notes |
2003-11-07 00:00:00 | *************** UNSAT **************** | | | | PLEASE SEE THAT PLANS ARE ONLY IN FOR | | PLAN REVIEW AND NOT SUBMITTED FOR | | PERMIT AT THIS TIME. | | | | 1)NOTE: PLANS WILL BE REQ'D TO BE SIGNED | | DATED AND SEALED BY THE ARCH/ENGINEER | | OF RECORD PER FS 471.025,481.221 | | PLEASE NOTE: FBPE'S HAS GIVEN TO THIS | | OFFICE INFORMATION THAT REQUIRES A | | SIGNATURE THAT CONTAINS A MIN IF FIRST | | AND LAST NAME. | | | | 2)NOTE: PLEASE SEE PLANS, SHOWS BOTH | | PANEL IN GARAGE? PLEASE CLARIFY WHERE | | METER LOCATION IS. PLEASE SEE LOCAL | | AMENDMENTS, 210.70 NO MORE THAT 8' OF | | UNPROTECTED CONDUCTOS INSIDE HOUSE. | | | | 3)NOTE: PLEASE SUBMIT PANEL SCHEDULE(S) | | WITH CIRCUITS, AWG AND OCP REQ'D. 215.5 | | PLEASE LIST THE REQUIRED ARC FAULT | | PROTECTTION PER NEC 2002 210.12 | | PLEASE LIST BATH(S) AS PER 210.52D AND | | 210.11C3 AS 20A AND #12. ETC ETC | | | | 4)NOTE: PLEASE SEE PLANS SHOW 4 A/C COND | | UNITS AND PLEASE SHOW AHU'S AND DISC PER | | 440.11 | | | | 5)NOTE: PLEASE SEE 210.52E FOR MIN OF | | FRONT AND REAR GFI RECEPTS. | | | | 6)NOTE: PLEASE SEE 210.52 FOR RECEPTS | | REQUIRED FOR WALL SPACE, INCLUDING | | RAIL AREAS. THERE IS MANY RECEPTS MISS- | | ING UPSTAIRS. | | | | 7)NOTE: PLEASE SEE NFPA-72 8-1.4.2, | | SD'S ARE NOT PERMITTED IN KITCHENS AND | | INFACT MUST BE A MIN OF 3' FROM KITCHENS | | AND BATHS. | | PLEASE ALSO SEE THAT A SD IS REQ'D AT | | THE BASE OF STAIRS LEADING TO THE FLOOR | | ABOVE IN THE IMMEDIATE VICINITY OF STAIR | | -S. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2004-06-03 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-06-03 |
Time |
11:01 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-06-03 |
Time |
11:01 |
Sent To |
E |
|
Notes |
2004-06-03 00:00:00 | TO DP DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2004-05-24 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2004-06-01 |
Time |
16:23 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2004-05-24 |
Time |
11:18 |
Sent To |
E |
|
Notes |
2004-05-24 00:00:00 | TP DP DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2004-04-02 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-04-02 |
Time |
11:51 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-04-02 |
Time |
11:51 |
Sent To |
M |
|
Notes |
2004-04-02 00:00:00 | TO PK BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2004-03-01 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-03-01 |
Time |
10:06 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-03-01 |
Time |
10:06 |
Sent To |
P |
|
Notes |
2004-03-01 00:00:00 | TO KS BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2004-02-25 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-02-25 |
Time |
16:44 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-02-25 |
Time |
16:44 |
Sent To |
E |
|
Notes |
2004-02-25 00:00:00 | TO DP DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2004-02-25 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2004-02-25 |
Time |
16:42 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-02-25 |
Time |
15:30 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2004-02-25 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-02-25 |
Time |
15:23 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-02-25 |
Time |
15:23 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2004-01-13 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2004-01-29 |
Time |
10:16 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-01-13 |
Time |
16:05 |
Sent To |
E |
|
Notes |
2004-01-13 00:00:00 | TO DP DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-12-12 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2003-11-05 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-11-03 |
Time |
16:14 |
Sent To |
|
|
Notes |
2003-11-06 00:00:00 | TO SFD RACK/E | 2003-11-03 00:00:00 | TO Z |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2004-04-12 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-04-12 |
Time |
11:07 |
Rev Time |
0.20 |
Received By |
pkrauss |
Date |
2004-04-12 |
Time |
11:06 |
Sent To |
E |
|
Notes |
2004-04-12 00:00:00 | PLANS APPROVED 1-23-04 | | TITLE BLOCK NEEDS TO BE REMOVED |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2004-03-01 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-04-02 |
Time |
11:51 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2004-03-01 |
Time |
15:53 |
Sent To |
E |
|
Notes |
2004-03-01 00:00:00 | DENIED: | | 1.PER COMMENTS DATED 1-23-04, PLAN | | NOT SIGNED, SEALED OR DATED BY ENGINEER | | OR ARCHITECT.TITLE BLOCK ON PLAN SHEET | | M-1, "DESIGN TEAM OF THE PALM BEACHES", | | PER FS 471.025 & 481.221 1 (B) & 2. | | | | 2.PER COMMENTS DATED 1-23-04, PROVIDE | | ADDITIONAL COPY OF ENERGY & MANUAL J | | CALCULATIONS.NO ENERGY CALCULATION | | WERE PROVIDED WITH THE RE-SUBMITTAL. | | PROVIDE TWO COPIES OF ENERGY & MANUAL J | | CALCUALTIONS PER 2001 FBC(M) 101.4.5. | | | | PLANS ARE OTHERWISE CODE COMPLIANT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2004-01-23 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-03-01 |
Time |
14:57 |
Rev Time |
0.55 |
Received By |
pkrauss |
Date |
2004-01-23 |
Time |
12:15 |
Sent To |
B |
|
Notes |
2004-01-23 00:00:00 | DENIED: | | 1.SEE COMMENT #1 BY DEWEY PALMER, | | ELECTRICAL PLAN REVIEW. | | | | 2.ONE COPY OF THE MANUAL J | | CALCULATIONS SUBMITTED FOR SYSTEM 1 & | | 3, NO MANUAL J CALCS SUBMITTED FOR | | SYSTEM 2.TWO COPIES OF EACH REQUIRED. | | | | PROVISO: | | 1.ATTIC ACCESS FOR A/C 1 & 2 SHALL | | COMPLY WITH 2001 FBC CHAPTER 13 SUB | | SECTION 610.1.ABC.3.5.2. | | | | 2.AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2003-12-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-01-21 |
Time |
18:30 |
Rev Time |
1.00 |
Received By |
hmoser |
Date |
2003-12-03 |
Time |
16:45 |
Sent To |
P |
|
Notes |
2003-12-03 00:00:00 | PLAN DENIED | | 1) REFER TO SECTION 307.2.3 AUXILIARY | | DRAIN PAN.AUXILIARY DRAIN PANS SHALL BE | | INSTALLED UNDER ALL COILS ON WITCH | | CONDENSATION WILL OCCUR. | | 2) RETURN AIR REQUIREMENTS TO COMPLY | | WITH THE FLORIDA BUILDING CODE (M) 2003 | | CHANGES.CHANGES WENT INTO EFFECT JULY 1 | | 2003 | | 3) MECHANICAL PLANS DO NOT MATCH FLOOR | | PLAN | | PLAN REVIEW BY HAROLD MOSER | | (561)805-6732 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2004-05-29 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2004-05-29 |
Time |
12:22 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2004-05-29 |
Time |
12:22 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2004-04-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-05-26 |
Time |
08:34 |
Rev Time |
0.25 |
Received By |
kstevens |
Date |
2004-04-17 |
Time |
05:46 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2004-03-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-04-16 |
Time |
19:08 |
Rev Time |
1.25 |
Received By |
kstevens |
Date |
2004-03-01 |
Time |
14:57 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2004-01-21 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-03-01 |
Time |
10:06 |
Rev Time |
1.20 |
Received By |
kstevens |
Date |
2004-01-21 |
Time |
18:24 |
Sent To |
M |
|
Notes |
2004-01-21 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FLORIDA ADMIN. CODE | | FLORIDA STATUTES | | | | 1) SANITARY RISER DIAGRAM DOES NOT RE- | | FLECT THE FLOOR PLAN, NOR DOES IT MEET | | CODE REQUIREMENTS. (SEE EXAMPLE OF RISER | | DIAGRAM THAT MEETS CODE AND REFLECTS THE | | FLOOR PLAN). | | | | ENGINEERS SHALL LEGIBLY INDICATE THEIR | | NAME, ADDRESS AND LICENSE NUMBER ON EACH | | SHEET. IF PRACTICING THROUGH A DULY | | AUTHORIZED ENGINEERING BUSINESS, ENGIN- | | EERS, ENGINEERS SHALL LEGIBLY INDICATE | | THEIR NAME AND LICENSE NUMBER, AS WELL | | AS, THE NAME, ADDRESS AND CERTIFICATE OF | | AUTHORIZATION NUMBER OF THE ENGINEERING | | BUSINESS ON EACH SHEET. A TITLE BLOCK | | WILL SATISFY THIS REQUIREMENT. FAC | | 61G15-23.002(2) | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2003-12-03 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-01-21 |
Time |
15:00 |
Rev Time |
0.75 |
Received By |
jleech |
Date |
2003-12-03 |
Time |
17:35 |
Sent To |
B |
|
Notes |
2003-12-03 00:00:00 | DENIED; | | 1.PLANS ARE NOT SIGNED OR SEALED. | | 2.PLUMBING RISER DIAGRAM DOES NOT MATCH | | FLOOR PLAN. | | A.MASTER BATH AND LAUNDRY ROOM ARE | | ON THE 1ST FLOOR ON FLOOR PLAN A-3 | | RISER DIAGRAM SHOWS 2ND FLOOR. | | B.LAUNDRY TUB CANNOT BE ON SAME | | STACK AS W/M BECAUSE FIXTURES ARE | | ON DIFFERENT SIDES OF ROOM. | | C.BUTLER PANTRY SINK NOT ON RISER | | DIAGRAM. | | D.HIS BATHROOM HAS SHOWER NOT TUB. | | E.RISER DIAGRAM SHOULD BE AN IMAGE | | OF THE FLOOR PLAN, FIXTURES ARE | | NOT IN PROPER ORDER. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2004-06-01 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2004-06-01 |
Time |
16:23 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2004-06-01 |
Time |
16:23 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2004-02-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2004-06-01 |
Time |
14:21 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2004-02-25 |
Time |
16:42 |
Sent To |
I |
|
Notes |
2004-02-25 00:00:00 | DENIED, NEED TO HAVE ELEVATION TO SCALE | | CALLED CONTR |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2004-01-29 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-02-25 |
Time |
15:30 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2004-01-29 |
Time |
10:16 |
Sent To |
I |
|
Notes |
2004-01-29 00:00:00 | DENIED, NEED TO PROVIDE HAVE ELEVATIONS | | TO SCALE CALLED CONTR MM |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2003-11-05 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2004-01-26 |
Time |
15:52 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2003-11-05 |
Time |
16:19 |
Sent To |
I |
|
Notes |
2003-11-05 00:00:00 | 11/5/03 DENIED, NEED 2 COPY OF SURVEY | | CALLED CONTR LEFT MSG ON VOICE MAIL MM |
|
|