Plan Review Details - Permit 03101960
Plan Review Stops For Permit 03101960
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-12-09 Cont ID  
Sent By dpalmer Date 2003-12-08 Time 16:17 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2003-12-09 00:00:00 
 "PROVISO"
 -------
 SUBMIT REVISED SURVEY TO SHOW 50'
 LENGTH.
  
  
  
 L. MARTINEZ
 561-805-6710

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2003-12-17 Cont ID  
Sent By dpalmer Date 2003-12-17 Time 09:07 Rev Time 1.50
Received By dpalmer Date 2003-12-17 Time 09:07 Sent To  
Notes
2003-12-17 00:00:00*********** NOTE *************
  
 1)NOTE: PLEASE SEE THAT LOAD CALCULATION
 -S AND INFORMATION FAXED AND BROUGHT
 INTO OFFICE FROM EMPIRE ELEC FOR BLUE
 HAVEN POOLSARE STILL NOT CORRECT AS
 FOR ALL INFORMATION REQUESTED ON ORIG
 REVIEW. THREE SETS OF CALCS HAVE BEEN
 REVIEW.
 ELECTRICAL PERMIT HAS BEEN VOIDED AND
 POOL PERMIT IS BEING ISSUED.
 SEPARATE ELECTRICAL APPLICATION/FEES AND
 COMPLETE PLANS AND LOADS CALCULATIONS
 WILL BE REQ'D TO BE SUBMITTED AT A LATER
 DATE BEFORE ANY ELECTRICAL WORK ON POOL
 SHALL COMMENCE.
 PLEASE ALSO SUBMIT ALL MANF. SPECS ON
 ALL EQUIPMENT AT THAT TIME.
 ELEC PERMIT VOIDED PER JIM KILFEATHER
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-08 Cont ID  
Sent By csiegber Date 2003-12-16 Time 15:40 Rev Time 0.50
Received By dpalmer Date 2003-12-08 Time 16:00 Sent To B
Notes
2003-12-08 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE PROVIDE MORE INFORMATION
 ON SYSTEM AND HOW IT IS BEING FED AND
 FROM WHERE?
 PLEASE PROVIDE LOAD ON EQUIPMENT BEING
 FED. PLEASE SHOW/CLARIFY LOAD ON PANEL
 THAT IS FEEDING EQUIPMENT.
  
 2)NOTE: PLEASE SUBMIT WIRING DIAGRAM
 TO INCLUDE HEAT PUMP.
  
 3)NOTE: PLEASE PROVIDE MANF SPECS FOR
 VAK/PAK SYSTEM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-02-18 Time 10:08 Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 10:08 Sent To P
Notes
2004-02-18 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-16 Cont ID  
Sent By csiegber Date 2003-12-16 Time 15:40 Rev Time 0.00
Received By csiegber Date 2003-12-16 Time 15:40 Sent To E
Notes
2003-12-16 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-19 Cont ID  
Sent By csiegber Date 2003-11-19 Time 11:49 Rev Time 0.00
Received By csiegber Date 2003-11-19 Time 11:49 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-09 Cont ID  
Sent By lsmith Date 2003-10-31 Time 10:57 Rev Time 0.00
Received By lmartine Date 2003-10-31 Time 10:57 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-12-08 Cont ID  
Sent By csiegber Date 2004-02-18 Time 10:08 Rev Time 1.50
Received By kstevens Date 2003-12-08 Time 08:07 Sent To E
Notes
2003-12-08 00:00:00PASSED PROVISO - BACKWASH WASTE TO SANT.
 OVERFLOW TO STORM

Review Stop Z ZONING
Rev No 2 Status P Date 2003-11-25 Cont ID  
Sent By lmartine Date 2003-12-09 Time 14:22 Rev Time 0.00
Received By mmclean Date 2003-11-25 Time 15:47 Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-11-05 Cont ID  
Sent By csiegber Date 2003-11-19 Time 11:49 Rev Time 0.00
Received By mmclean Date 2003-11-05 Time 14:54 Sent To  
Notes
2003-11-05 00:00:0011/5/03 DENIED, NEED SITE PLAN CALLED
 CONTR FILE B MM